Free NEC practice test · Article 430

Motors practice questions

A free NEC Article 430 practice test for the journeyman exam: 74 questions on Motors, Motor Circuits, and Controllers, each with the answer and the why behind it.

74 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 74 journeyman-exam practice questions cover NEC Article 430 across 74 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Motor Calculations (NEC Article 430)

NEC 430.22

Every motor calculation starts from the full-load current in Table 430.250/430.248 — not the nameplate. Branch-circuit conductors carry 125% of FLC (430.22); the branch OCPD is a table percentage of FLC, rounded up to the next standard size (430.52).

Q1 NEC 430.22

What is the full-load current of a 10 HP, 230-volt, three-phase induction motor? (NEC Table 430.250)

  1. A 32.2 A
  2. B 30.8 A
  3. C 14 A
  4. D 28 A
Show answer & explanation

Correct: D — 28 A

Table 430.250 lists the full-load current of a 10 HP three-phase motor at 230 V as 28 A. The distractors are the FLC at other voltage columns — read the column for the motor's actual voltage.

Conductor ampacity basis: general motors vs. torque motors

NEC 430.6(A)

Size conductors from the NEC's motor tables for normal motors, but use the nameplate current instead for low-speed, high-torque, multispeed, or torque motors.

Q2 NEC 430.6(A)

When sizing branch-circuit conductors for a standard general-purpose motor, which current value should be used per 430.6(A)(1)?

  1. A The service factor amps listed on the motor label
  2. B The value from Table 430.247, 430.248, 430.249, or 430.250
  3. C The locked-rotor current stamped on the motor
  4. D The current rating marked on the motor nameplate
Show answer & explanation

Correct: B — The value from Table 430.247, 430.248, 430.249, or 430.250

Per 430.6(A)(1), conductor ampacity, switch ratings, and branch-circuit protection for general motor applications are based on the values in Table 430.247-430.250, not the nameplate current. Nameplate current and locked-rotor current apply to special cases like torque motors and overload protection, not general conductor sizing.

Locked-rotor indicating code letters and how to select them

NEC 430.7(B)

The nameplate code letter reflects locked-rotor kVA per hp under the worst-case condition the motor can actually start in — not just a single fixed rating.

Q3 NEC 430.7(B) Code lookup

You're checking a motor nameplate to decode the locked-rotor kVA per horsepower from its single letter marking. Which section contains the reference table that translates that letter into a kVA/hp range?

  1. A 430.6(A)(1)
  2. B 430.7(B)
  3. C 430.8
  4. D 430.7(A)
Show answer & explanation

Correct: B — 430.7(B)

Table 430.7(B) lives at 430.7(B) and lists the locked-rotor indicating code letters with their kVA/hp ranges. 430.6(A)(1) instead governs using ampacity table values for conductor sizing, not code-letter decoding.

Motor terminal housing material, sizing, and grounding means

NEC 430.12

Motor terminal housings must be metal (or noncombustible nonmetal with internal bonding), sized per Table 430.12(B)/(C) for field wiring, and always provide a place to land the equipment grounding conductor.

Q4 NEC 430.12

A motor is installed in an ordinary (non-hazardous) location. Under what condition is a nonmetallic terminal housing permitted?

  1. A The branch circuit is protected by GFCI
  2. B It is noncombustible and has an internal grounding means between the motor frame and the grounding connection
  3. C The motor is rated 1 hp or less
  4. D It is UV-rated for outdoor exposure
Show answer & explanation

Correct: B — It is noncombustible and has an internal grounding means between the motor frame and the grounding connection

Per 430.12(A), nonmetallic housings are allowed outside hazardous (classified) locations only when substantial, noncombustible, and fitted with an internal grounding means between the motor frame and the equipment grounding connection. UV rating, motor horsepower, and GFCI protection are not the qualifying conditions in this section.

Overload protection for continuous-duty motors over 1 hp

NEC 430.32(A)

A continuous-duty motor over 1 hp needs one of four listed overload protection methods, most commonly a separate overload device sized off the nameplate current.

Q5 NEC 430.32(A)

A 5 hp motor operates in a continuous-duty application. Per 430.32(A), which of the following is an approved method of overload protection?

  1. A Branch-circuit short-circuit protection sized per Table 430.52 alone, with no separate overload device
  2. B Embedded temperature detectors, since the motor exceeds 1 hp
  3. C A separate overload device responsive to motor current, sized per the motor nameplate full-load current
  4. D A thermal protector sized only for the motor's locked-rotor current
Show answer & explanation

Correct: C — A separate overload device responsive to motor current, sized per the motor nameplate full-load current

A separate overload device responsive to motor current and sized off the nameplate full-load current is one of the four permitted methods under 430.32(A)(1). Short-circuit protection alone does not satisfy overload protection requirements. A thermal protector must be approved to prevent dangerous overheating from overload and failure to start, not just sized to locked-rotor current. Embedded temperature detectors under 430.32(A)(4) apply only to motors larger than 1500 hp, not simply any motor over 1 hp.

Branch-circuit short-circuit/ground-fault protection for a single motor with a drive

NEC 430.130(A)

Size the branch-circuit SCPD from the motor's full-load current using 430.52 — unless the drive is listed and marked "Suitable for Output Motor Conductor Protection," and never exceed a rating the manufacturer marks on the equipment.

Q6 NEC 430.130(A)

A single motor is fed through a variable frequency drive that is NOT marked "Suitable for Output Motor Conductor Protection." How must the branch-circuit short-circuit and ground-fault protective device be sized?

  1. A From the drive's rated input current, per Table 430.52(C)(1)
  2. B From the drive's output current under stall conditions
  3. C From the sum of the motor nameplate current and the drive's rated input current
  4. D From the motor's full-load current rating per 430.6, applied to 430.52(C)(1), (C)(3), (C)(5), or (C)(6)
Show answer & explanation

Correct: D — From the motor's full-load current rating per 430.6, applied to 430.52(C)(1), (C)(3), (C)(5), or (C)(6)

Per 430.130(A)(1), absent the special listing/marking, protection rating and type are determined using the motor's full-load current rating from 430.6(A) or (B) applied through 430.52. Sizing from the drive's rated input current is only permitted when the equipment is listed and marked "Suitable for Output Motor Conductor Protection."

Motor overtemperature protection for drive-fed motors

NEC 430.126(A)

When an adjustable-speed drive can't keep the motor at nameplate current across its speed range, overtemperature protection is required in addition to normal conductor overload protection.

Q7 NEC 430.126(A)

A motor is fed by an adjustable-speed drive and is not rated to operate at nameplate current across the full speed range the application requires. Per 430.126(A), what must be provided?

  1. A A dedicated disconnecting means sized at 115% of nameplate current
  2. B Only the conductor protection required by 430.32, since it already accounts for reduced-speed operation
  3. C Group motor protection sized to the largest motor in the group
  4. D Overtemperature protection, in addition to the conductor protection already required by 430.32
Show answer & explanation

Correct: D — Overtemperature protection, in addition to the conductor protection already required by 430.32

430.126(A) requires overtemperature protection in addition to the conductor protection required in 430.32, because reduced-speed operation can overheat the motor even below its rated current. Conductor protection alone doesn't address this, and disconnect sizing or group protection are separate requirements not addressed by this section.

Sizing the branch-circuit short-circuit/ground-fault device from Table 430.52(C)(1)

NEC 430.52(C)(1)

Size the motor branch-circuit protective device from Table 430.52(C)(1) as a percentage of full-load current, rounding up to the next standard rating, then raising it further only if starting current trips it.

Q8 NEC 430.52(C)(1)

What is the primary purpose of the motor branch-circuit short-circuit and ground-fault protective device sized under 430.52?

  1. A To protect the branch-circuit conductors and equipment from short circuits and ground faults while carrying starting current
  2. B To limit the motor's running current to its nameplate rating
  3. C To protect the motor windings from sustained overload
  4. D To disconnect the motor for maintenance
Show answer & explanation

Correct: A — To protect the branch-circuit conductors and equipment from short circuits and ground faults while carrying starting current

430.52 governs the branch-circuit short-circuit and ground-fault protective device, which per 430.52(B) must be capable of carrying starting current while protecting against faults. Overload protection is a separate requirement (covered elsewhere in Article 430), not the function of this device.

Sizing feeder protection for an all-motor load

NEC 430.62

A feeder OCPD for an all-motor group is sized at the largest single branch-circuit protective device rating plus the full-load currents of all other motors.

Q9 NEC 430.62

A feeder supplies three motors, each with its own branch-circuit short-circuit and ground-fault protective device sized under 430.52. Per 430.62(A), how is the feeder protective device rated?

  1. A Equal to the sum of all three branch-circuit device ratings
  2. B Equal to the largest branch-circuit device rating among the three, plus the full-load currents of the other two motors
  3. C Equal to 125% of the largest motor's full-load current only
  4. D Equal to the sum of the full-load currents of all three motors
Show answer & explanation

Correct: B — Equal to the largest branch-circuit device rating among the three, plus the full-load currents of the other two motors

430.62(A) sets the feeder OCPD at the largest branch-circuit short-circuit/ground-fault device rating for any motor in the group, plus the full-load currents of the other motors in that group — not a simple sum of FLCs or of all the branch-circuit ratings, and not just 125% of one motor's FLC (that's a branch-circuit concept, not the feeder rule).

Feeder tap conductor rules for motor circuits

NEC 430.28

A motor feeder tap skips full feeder-size conductors only if it fits one of three length/ampacity/protection combos in 430.28.

Q10 NEC 430.28

An electrician installs a 10-ft feeder tap in a raceway, protected on the line side by an overcurrent device rated well above the tap conductor's ampacity. What limit applies to that line-side overcurrent device under 430.28(1)?

  1. A It must equal exactly one-third of the feeder conductor's ampacity
  2. B It cannot exceed 1000 percent of the tap conductor's ampacity
  3. C It cannot exceed 125 percent of the motor's full-load current
  4. D It must not exceed the ampacity of the feeder conductors
Show answer & explanation

Correct: B — It cannot exceed 1000 percent of the tap conductor's ampacity

430.28(1) caps the line-side overcurrent device at 1000% of the tap conductor's ampacity for the 10-ft tap option. The one-third ampacity figure belongs to the 25-ft tap option in 430.28(2), the 125% FLC figure is a motor branch-circuit sizing rule, and matching feeder ampacity describes the third, no-length-limit tap option under 430.28(3).

Motors on general-purpose branch circuits: overload protection rules

NEC 430.42

A motor can skip individual overload protection only at 1 hp or less under 430.32 limits; above that, the motor's own overload device is required.

Q11 NEC 430.42

A small motor is connected to a general-purpose branch circuit with no individual overload protection installed. Under which condition is this acceptable?

  1. A The motor is rated 1 hp or less and complies with 430.32(B), 430.32(D), and 430.53(A)(1) and (A)(2)
  2. B The motor controller is approved for group installation
  3. C The branch-circuit device has extra time delay to allow starting
  4. D The motor is cord-and-plug connected at any horsepower rating
Show answer & explanation

Correct: A — The motor is rated 1 hp or less and complies with 430.32(B), 430.32(D), and 430.53(A)(1) and (A)(2)

430.42(A) permits omitting individual overload protection only for motors at or below the 1 hp threshold that meet the limiting conditions in 430.32(B), 430.32(D), and 430.53(A)(1)-(A)(2). Time delay (430.42(D)) and group-installation approval (430.42(B)) address different requirements and don't by themselves justify skipping overload protection, and cord-and-plug connection alone doesn't remove the horsepower limit.

Instantaneous-trip circuit breakers (MCPs) as branch protection

NEC 430.52(C)(3)

An instantaneous-trip breaker (MCP) can protect a motor branch circuit only inside a listed combination controller, adjusted per Table 430.52(C)(1) or higher only under specific exceptions.

Q12 NEC 430.52(C)(3)

Under what condition does 430.52(C)(3) permit the use of an instantaneous-trip circuit breaker for motor branch-circuit protection?

  1. A It must be adjustable and part of a listed combination motor controller with coordinated overload and short-circuit/ground-fault protection
  2. B It must be a fixed, non-adjustable device sized directly from Table 430.52(C)(1)
  3. C It must be used alone, without any separate overload relay, since it already senses overload current
  4. D It must be installed only on motors rated 8 amperes full-load current or less
Show answer & explanation

Correct: A — It must be adjustable and part of a listed combination motor controller with coordinated overload and short-circuit/ground-fault protection

430.52(C)(3)(a) requires the instantaneous-trip breaker (MCP) to be adjustable and part of a listed combination motor controller that coordinates motor overload protection with the breaker's short-circuit and ground-fault protection — the MCP itself provides no overload protection. The 8 A full-load current option is only a special setting allowance under 430.52(C)(3)(b)(3), not a condition for using an MCP at all.

Sizing overcurrent protection for control circuit conductors

NEC 430.72(B)

Control conductors only need short-circuit and ground-fault protection, and the motor branch-circuit protective device can often provide it — but the allowed rating depends on whether conductors stay inside the enclosure or leave it.

Q13 NEC 430.72(B) Code lookup

A motor control circuit's conductors run inside the motor control equipment enclosure only, and the designer wants to rely on the motor branch-circuit short-circuit and ground-fault protective device for their protection instead of adding separate overcurrent devices. Which section's table gives the maximum protective device rating permitted for conductors that stay within the enclosure?

  1. A 430.72(C)(2)
  2. B 430.72(B)(1)
  3. C 430.72(A)
  4. D 430.72(B)(2)
Show answer & explanation

Correct: D — 430.72(B)(2)

430.72(B)(2) hosts Table 430.72(B)(2), which gives Column B ratings for control conductors protected by the motor branch-circuit device and not extending beyond the enclosure. 430.72(B)(1) applies only when separate overcurrent protection is required because the branch-circuit device doesn't qualify under (B)(2), so it doesn't govern this enclosure-only scenario.

Protecting motor control circuit transformers

NEC 430.72(C)

A control circuit transformer must be protected by one of five permitted methods in 430.72(C), unless opening the circuit itself would create a hazard.

Q14 NEC 430.72(C)

A control circuit transformer supplies the control circuit for a fire pump motor. What does 430.72(C) require for overcurrent protection?

  1. A Compliance with Part II of Article 725
  2. B Protection in accordance with 450.3
  3. C Overcurrent protection is permitted to be omitted because opening the circuit would create a hazard
  4. D An overcurrent device sized at no more than 500% of rated primary current
Show answer & explanation

Correct: C — Overcurrent protection is permitted to be omitted because opening the circuit would create a hazard

430.72(C) states overcurrent protection shall be omitted where opening the control circuit would create a hazard, citing a fire pump motor's control circuit as the example. The 500% primary device and Part II of Article 725 are protection methods used when protection IS required, and 450.3 is the general transformer protection option under 430.72(C)(2) — none apply once the hazard exception takes over.

Sizing a disconnect for combined motor and other loads

NEC 430.110(C)

Treat every motor plus resistance load on a shared disconnect as one giant motor: add full-load currents for the rating, add locked-rotor currents for starting, then apply 115%.

Q15 NEC 430.110(C)

Two motors and a resistance heater share a single disconnecting means and can operate simultaneously. How must the disconnect's rating be determined per 430.110(C)?

  1. A Treat the combined full-load and locked-rotor currents of all loads as if they were a single motor
  2. B Use the heater's rating alone since it has no locked-rotor current
  3. C Add the nameplate amps of each device with no adjustment for locked-rotor conditions
  4. D Size it to the largest individual motor only, ignoring the other loads
Show answer & explanation

Correct: A — Treat the combined full-load and locked-rotor currents of all loads as if they were a single motor

430.110(C)(1) requires summing full-load currents and locked-rotor currents of every motor and resistance load, then treating that combined figure as a single motor for disconnect sizing. Sizing to just the largest motor, or skipping the locked-rotor sum, ignores the simultaneous-load requirement in 430.110(C).

Using one switch/breaker as both controller and disconnect

NEC 430.111(A)

One device can serve as both motor controller and disconnecting means only if it opens all ungrounded conductors, is overcurrent-protected, and is one of three approved types.

Q16 NEC 430.111(A)

An electrician wants to use a single inverse time circuit breaker as both the motor controller and the disconnecting means. Which condition must also be satisfied for this to comply with 430.111?

  1. A The breaker must open all ungrounded conductors to the motor and be protected by an overcurrent device in each ungrounded conductor
  2. B The breaker must be located inside the motor terminal housing
  3. C The breaker must be power-operable only, with no manual lever
  4. D The breaker must be rated for autotransformer-type controllers
Show answer & explanation

Correct: A — The breaker must open all ungrounded conductors to the motor and be protected by an overcurrent device in each ungrounded conductor

Per 430.111(A), any device used as both controller and disconnecting means must open all ungrounded conductors to the motor and be protected by overcurrent devices in each ungrounded conductor. An inverse time breaker used this way must still be operable directly by hand per 430.111(B)(2), so power-operable-only fails that requirement. Autotransformer controllers are excluded from dual-role use entirely, and there's no NEC requirement tying the device's location to the motor terminal housing.

Disconnect location relative to the motor itself

NEC 430.102(B)

The motor itself needs a disconnect in sight from it and the driven machinery, unless the controller disconnect already sits in that sightline and is lockable.

Q17 NEC 430.102(B)

Under 430.102(B)(1), where must the disconnecting means for a motor be located?

  1. A Anywhere in the same room as the motor, regardless of sightline
  2. B Within sight from the branch-circuit overcurrent device only
  3. C Within 50 ft of the motor controller
  4. D Within sight from the motor location and the driven machinery location
Show answer & explanation

Correct: D — Within sight from the motor location and the driven machinery location

430.102(B)(1) requires the motor's disconnecting means to be located in sight from both the motor location and the driven machinery location. A distance-only rule (like '50 ft') or 'same room' without sightline doesn't satisfy the requirement, and sight from the overcurrent device isn't the standard used here.

Purpose and location of the motor disconnecting means

NEC 430.102(A)

The motor controller disconnect must be in sight from the controller, with narrow exceptions for over-1000-volt circuits and valve actuator motor assemblies.

Q18 NEC 430.102(A)

Under 430.102(A), where must the disconnecting means for a motor controller normally be located?

  1. A Anywhere, provided it is lockable per 110.25
  2. B Within 50 ft of the motor controller, sight not required
  3. C In sight from the motor controller
  4. D In the same room as the motor it controls
Show answer & explanation

Correct: C — In sight from the motor controller

430.102(A) requires the disconnecting means to be located in sight from the motor controller. A distance-only rule, a same-room rule, or a lockable-anywhere rule are not what the section states; the lockable-out-of-sight option only applies under the specific over-1000-volt or VAM exceptions.

Approved disconnect device types (general rule)

NEC 430.109(A)

Every motor disconnecting means between the feeder/branch circuit and the motor must be one of the listed device types in 430.109(A) unless a specific exception in 430.109(B)–(G) applies.

Q19 NEC 430.109(A)

Under the general rule of 430.109(A), which of the following is a listed device type permitted as a motor disconnecting means?

  1. A An unmarked manual motor controller
  2. B A listed molded case switch
  3. C A plug fuse assembly rated in horsepower
  4. D Any general-use snap switch rated for the motor's full-load current
Show answer & explanation

Correct: B — A listed molded case switch

430.109(A)(3) lists a listed molded case switch as an approved type. A general-use snap switch is not on the 430.109(A) list, an unmarked manual motor controller is excluded by 430.109(A)(6) (it must carry the 'Suitable as Motor Disconnect' marking), and fuse assemblies are not a disconnect type under this section.

When stationary and portable motor frames must be grounded

NEC 430.242

Stationary motor frames must be grounded if fed by metal wiring, wet, hazardous-classified, or over 150V to ground; portable motor frames must be grounded or guarded only above 150V to ground.

Q20 NEC 430.242

A stationary motor is fed by nonmetallic wiring, is in a dry indoor location, is not in a hazardous location, and operates at 120 volts to ground. Does its frame need to be grounded under 430.242?

  1. A Yes, because dry locations always require grounding under 150 volts
  2. B No, none of the triggering conditions apply
  3. C Yes, all stationary motors must be grounded regardless of wiring or voltage
  4. D Yes, because it is not in a hazardous location
Show answer & explanation

Correct: B — No, none of the triggering conditions apply

Per 430.242, grounding is required only if fed by metal-enclosed wiring, in an unguarded wet location, in a hazardous (classified) location, or over 150V to ground. None of these apply here, so the frame can instead be permanently insulated from ground — grounding is not mandatory.

Sizing feeders for multiple motors and combination loads

NEC 430.24

Feeder ampacity for several motors equals 125% of the largest motor's FLC plus the sum of all other motor FLCs plus the non-motor loads (100% noncontinuous, 125% continuous).

Q21 NEC 430.24

A feeder supplies three motors of different full-load currents and no other loads. Per 430.24, how should the conductor ampacity be determined?

  1. A 100% of the full-load current of the highest-rated motor plus 125% of the others
  2. B 125% of the full-load current of the highest-rated motor plus 100% of the full-load currents of the other motors
  3. C 125% of the sum of all the motors' full-load currents combined
  4. D 125% of the full-load current of every motor in the group, summed together
Show answer & explanation

Correct: B — 125% of the full-load current of the highest-rated motor plus 100% of the full-load currents of the other motors

Under 430.24, only the highest-rated motor's full-load current is multiplied by 125%; every other motor in the group is added at 100% of its full-load current. Applying 125% to every motor, or to the whole sum, overstates the required ampacity, and swapping which motor gets the 125% factor reverses the rule.

One controller per motor — and when one controller can serve a group

NEC 430.87

Every motor needs its own controller unless it fits one of three group exceptions — same machine, shared overcurrent protection, or same room within sight.

Q22 NEC 430.87

Under 430.87, what is required for each motor unless a specific exception applies?

  1. A A dedicated room separate from other motors
  2. B An individual branch-circuit disconnecting means only
  3. C An individual motor controller
  4. D An individual overcurrent device sized per 430.53(A)
Show answer & explanation

Correct: C — An individual motor controller

430.87 states each motor shall be provided with an individual motor controller. Shared overcurrent protection under 430.53(A) and a shared room are conditions that permit a single controller to serve a group — they are not requirements imposed on every motor. A branch-circuit disconnecting means may serve as the controller, but the base rule is about the controller itself, not a separate disconnect requirement.

Grouping small motors (≤1 hp) on one branch circuit without individual protection

NEC 430.53(A)

Small motors rated 6 A or less can share one 20 A (120V) or 15 A branch circuit without individual branch-circuit protection, if controller ratings and overload protection are still met.

Q23 NEC 430.53(A)

An electrician wants to place four small motors on one nominal 120-volt branch circuit protected at 20 amperes, relying on 430.53(A). Which condition must ALL four motors meet?

  1. A Each motor is rated not more than 2 hp as long as the combined full-load current stays under 20 amperes
  2. B Each motor has its own overload protection but no motor needs to meet a horsepower limit
  3. C Only the largest motor on the circuit needs to meet the 6-ampere full-load current limit
  4. D Each motor is rated not more than 1 hp and its full-load current does not exceed 6 amperes
Show answer & explanation

Correct: D — Each motor is rated not more than 1 hp and its full-load current does not exceed 6 amperes

430.53(A) requires every motor on the shared circuit to be rated not over 1 hp with a full-load rating not exceeding 6 amperes each — the limit applies to each motor individually, not just the largest one, and there's no 2 hp allowance under this exception.

How Part X applies to adjustable-speed drive systems

NEC 430.120

Part X supplements — not replaces — Parts I through IX of Article 430, and the 1000-volt threshold decides whether Part X or Part XI governs a drive.

Q24 NEC 430.120 Code lookup

A 480V adjustable-speed drive feeds a single motor. The drive has a bypass contactor that allows the motor to run across-the-line if the drive faults out. Which section specifies the overload protection requirements that must still be provided for the motor when it's running through the bypass circuit?

  1. A 430.124(B)
  2. B 430.122(C)
  3. C 430.124(A)
  4. D 430.126(B)
Show answer & explanation

Correct: A — 430.124(B)

430.124(B) Bypass Circuits specifically requires overload protection per Part III when a bypass device is used to run the motor across-the-line. 430.124(A) instead addresses overload protection already included in the power conversion equipment (no bypass involved), 430.126(B) covers overtemperature protection (not overload) for multiple motors, and 430.122(C) covers conductor sizing for the bypass device, not overload protection.

Sizing output conductors between drive and motor

NEC 430.122(B)

Output conductors from an adjustable-speed drive to the motor need at least 125% of motor full-load current, unless the drive is listed for output conductor protection with a marked minimum size.

Q25 NEC 430.122(B)

A power conversion unit supplying a motor is listed and marked 'Suitable for Output Motor Conductor Protection.' How must the output conductor ampacity be determined?

  1. A Use whichever is larger: 125% of motor full-load current, or the ampacity of the minimum conductor size marked on the equipment
  2. B Always use 125% of the motor full-load current, regardless of any marking
  3. C Use the same ampacity required for the conductors feeding the power conversion equipment
  4. D Use the ampacity marked on the equipment only, since the listing supersedes the percentage rule
Show answer & explanation

Correct: A — Use whichever is larger: 125% of motor full-load current, or the ampacity of the minimum conductor size marked on the equipment

Per 430.122(B), when the power conversion equipment is listed and marked 'Suitable for Output Motor Conductor Protection,' the output conductor ampacity must be the larger of 125% of motor FLC or the marked minimum conductor size ampacity — not one or the other alone, and not simply the default 125% rule that applies to unlisted equipment.

Group motor installations using listed assemblies and coordinated overload devices

NEC 430.53(C)

Multiple motors (or motors plus other loads) can share one branch circuit only if every controller, overload device, and the circuit protection itself meet listing and sizing rules in 430.53(C)(1) through (C)(5).

Q26 NEC 430.53(C)

Under 430.53(C), what must be true of each motor before several motors can be grouped onto a single branch circuit?

  1. A Each motor must be listed for use without any overload protection
  2. B Each motor must be the same horsepower rating
  3. C Each motor must have its own dedicated disconnecting means only, with shared overload protection
  4. D Each motor must have individual overload protection
Show answer & explanation

Correct: D — Each motor must have individual overload protection

430.53(C) permits grouping motors of any size (or motors with other loads) on one branch circuit specifically because each motor still carries individual overload protection. Requiring matched horsepower, omitting overload protection, or sharing overload protection across motors all contradict that core condition.

Motor control circuit scope and fault-safe arrangement

NEC 430.74

A grounded control circuit must be wired so a remote ground fault can't start the motor or defeat a shutdown device.

Q27 NEC 430.74

A remote motor control circuit has one conductor grounded. Per 430.74, the circuit's electrical arrangement must ensure that a ground fault remote from the controller will do what?

  1. A Automatically transfer control to a backup controller
  2. B Neither start the motor nor bypass shutdown devices
  3. C Trip the motor's overload relay within 2 seconds
  4. D Sound an audible alarm at the controller enclosure
Show answer & explanation

Correct: B — Neither start the motor nor bypass shutdown devices

430.74 requires that a ground fault in a grounded control circuit, occurring remote from the motor controller, will not start the motor and will not bypass manually operated or automatic safety shutdown devices. There is no NEC requirement in this section for a timed overload trip, automatic transfer to a backup controller, or an audible alarm — those are plausible-sounding but not what 430.74 mandates.

Control transformer wiring inside the motor controller enclosure

NEC 430.75(B)

A control transformer mounted inside the motor controller enclosure must tap the load side of the disconnecting means, so opening the disconnect kills it too.

Q28 NEC 430.75(B) Code lookup

A motor control circuit uses a control transformer to step down voltage, and the transformer is mounted inside the motor controller's own enclosure. Which section specifies which side of the controller's disconnecting means this transformer must be connected to?

  1. A 430.75(B)
  2. B 430.82(A)
  3. C 430.74
  4. D 430.72(C)(2)
Show answer & explanation

Correct: A — 430.75(B)

430.75(B) specifically governs a control transformer located inside the motor controller enclosure, requiring it to be connected to the load side of the disconnecting means. 430.72(C)(2) instead addresses overcurrent protection sizing for control circuit transformers generally, not disconnect-side placement, and doesn't apply when the transformer sits inside the controller enclosure itself.

Disconnecting means for motor control circuits

NEC 430.75(A)

Motor control circuits must be fully disconnected from every power source when the disconnect is open, whether that takes one device or several.

Q29 NEC 430.75(A) Code lookup

A wye-delta reduced-voltage motor controller enclosure has a control transformer feeding the motor control circuit. The panel has two separate disconnects — one for the motor/controller power and one for the control circuit — mounted immediately adjacent to each other as required. A designer wants to know which section actually requires that these two disconnects be located immediately adjacent to each other (absent the multi-conductor exception).

  1. A 430.72(A)
  2. B 430.81(A)
  3. C 430.74
  4. D 430.75(A)
Show answer & explanation

Correct: D — 430.75(A)

430.75(A) is the disconnection rule that requires separate motor and motor-control-circuit disconnects to be located immediately adjacent to each other (with the 12-conductor exception). 430.74 covers electrical arrangement of control circuits, not disconnect location, and 430.72(A) is general overcurrent protection — neither addresses disconnect placement.

Busbar support, conductor routing, and wire-bending space

NEC 430.97(A)

Vertical sections of a motor control center are for terminating conductors only — busbars must be barrier-protected from anything just passing through, and gutter space follows Table 312.6.

Q30 NEC 430.97(A)

An electrician wants to route feeder conductors horizontally through a vertical section of a motor control center on their way to a different section, without terminating anything there. What does 430.97(A) require?

  1. A The conductors must terminate somewhere in that same section to be allowed
  2. B The conductors must be labeled as control wiring to qualify
  3. C The conductors must be isolated from the busbars by a barrier
  4. D This is prohibited outright, with no exception for pass-through wiring
Show answer & explanation

Correct: C — The conductors must be isolated from the busbars by a barrier

430.97(A) permits conductors to travel horizontally through a vertical section only where they are isolated from the busbars by a barrier — it doesn't ban pass-through wiring, and it doesn't require relabeling as control wiring or termination in that section.

Standard phase arrangement (A-B-C) on MCC buses

NEC 430.97(B)

MCC buses run A, B, C front-to-back, top-to-bottom, or left-to-right, with B always the high leg on 4-wire delta systems.

Q31 NEC 430.97(B)

Viewed from the front of a motor control center, what is the standard phase arrangement on the horizontal common power and vertical buses?

  1. A B, A, C in every orientation
  2. B Whatever order the manufacturer prewires, with no standard required
  3. C A, B, C from front to back, top to bottom, or left to right
  4. D C, B, A from front to back, top to bottom, or left to right
Show answer & explanation

Correct: C — A, B, C from front to back, top to bottom, or left to right

Per 430.97(B), the standard phase arrangement is A, B, C from front to back, top to bottom, or left to right as viewed from the front of the MCC. C, B, A is only permitted for rear-mounted units on a shared vertical bus, not as the general standard, and a fixed order is required rather than being left to the manufacturer.

Using a motor control center as service equipment

NEC 430.95

An MCC used as service equipment needs one main disconnect for all ungrounded service conductors, plus a main bonding jumper sized per 250.28(D) if a grounded conductor is present.

Q32 NEC 430.95

A motor control center is being installed as service equipment for a facility. Per 430.95, how must the ungrounded service conductors be disconnected?

  1. A By a separate disconnect in each section of the MCC
  2. B By up to six disconnects grouped together, as allowed for service equipment generally
  3. C By a single main disconnecting means for all ungrounded service conductors
  4. D By the main bonding jumper acting as the disconnecting means
Show answer & explanation

Correct: C — By a single main disconnecting means for all ungrounded service conductors

430.95 requires a single main disconnecting means to disconnect all ungrounded service conductors when an MCC is used as service equipment. The 'up to six disconnects' rule applies to services generally under Article 230, not to this MCC-specific requirement; a disconnect per section and using the bonding jumper as a disconnect are not what this section describes.

Wiring and wire-bending space inside controller enclosures

NEC 430.10

A motor controller enclosure can't double as a junction box or raceway for other circuits, and its terminals need the minimum bending space set by Table 430.10(B).

Q33 NEC 430.10 Code lookup

You're installing a combination motor controller with disconnect and need to know the minimum wire-bending space required at the terminals for the conductor lugs being used. Which section provides this data?

  1. A 430.9(C)
  2. B 430.10(A)
  3. C 430.10(B)
  4. D 430.12(B)
Show answer & explanation

Correct: C — 430.10(B)

430.10(B) hosts Table 430.10(B), the minimum wire-bending space table for enclosed motor controller terminals. 430.12(B) covers dimensions and space for wire-to-wire connections inside motor terminal housings, not controller enclosures, and 430.9(C) covers terminal torque requirements, not bending space.

Required markings on motor controllers, including SCCR

NEC 430.8

Every motor controller needs manufacturer, voltage, current or hp rating, and SCCR — but SCCR marking has several valid exceptions.

Q34 NEC 430.8 Code lookup

A contractor is installing a combination motor controller for a 15 hp, 480V motor and needs to mark it with its short-circuit current rating along with the manufacturer's name, voltage, and current rating. Which section covers this marking requirement?

  1. A 430.9
  2. B 430.7
  3. C 430.6
  4. D 430.8
Show answer & explanation

Correct: D — 430.8

430.8 requires motor controllers to be marked with the manufacturer's name, voltage, current or horsepower rating, and short-circuit current rating. 430.7 governs marking on motors themselves (not controllers), 430.9 covers controller terminal markings/torque, and 430.6 addresses conductor ampacity and motor rating determination, not controller nameplate marking.

Sizing the disconnect's current rating

NEC 430.110(A)

A motor disconnecting means must be rated at least 115% of the motor's full-load current, or 115% of nameplate current for a torque motor.

Q35 NEC 430.110(A)

Per 430.110(A), what is the minimum current rating required for a motor disconnecting means rated 1000 volts or less?

  1. A 115% of the motor full-load current rating
  2. B 80% of the motor full-load current rating
  3. C 100% of the motor full-load current rating
  4. D 125% of the motor full-load current rating
Show answer & explanation

Correct: A — 115% of the motor full-load current rating

430.110(A) sets the minimum disconnect current rating at 115% of the motor's full-load current rating. The 125% figure is a common motor branch-circuit conductor and overload factor elsewhere in Article 430, and 100% or 80% would leave no margin, which the disconnect rule doesn't allow.

Disconnects for motors fed from more than one energy source

NEC 430.113

A motor fed from more than one source needs a disconnect for each source next to the equipment, plus warning signs cross-referencing the other disconnects.

Q36 NEC 430.113 Code lookup

A machine shop has a motor that can be powered either from the utility service or from an on-site standby generator, switched over as needed. A journeyman needs to identify the code requirement for disconnecting means at the equipment when a motor can receive power from either of these two separate sources. Which section governs this installation?

  1. A 430.112
  2. B 430.113
  3. C 430.111
  4. D 430.109
Show answer & explanation

Correct: B — 430.113

430.113 specifically addresses motors receiving energy from more than one source, requiring a disconnecting means from each source immediately adjacent to the equipment (or a lockable controller disconnect per 110.25) plus warning signage. 430.112 by contrast covers the opposite case — multiple motors/loads served by a single disconnecting means — so it doesn't apply here.

How the disconnect must open, indicate, and behave

NEC 430.103

A motor disconnect must open all ungrounded conductors together, show its position plainly, and never be able to close by itself.

Q37 NEC 430.103

Which statement correctly describes how a motor disconnecting means must operate per 430.103?

  1. A It must open all ungrounded supply conductors, and no pole can be operated independently
  2. B It may open one ungrounded conductor at a time as long as the motor stops within 2 seconds
  3. C It must open only the conductor with the highest load current
  4. D It must open all conductors including the grounded conductor pole first
Show answer & explanation

Correct: A — It must open all ungrounded supply conductors, and no pole can be operated independently

430.103 requires the disconnecting means to open all ungrounded supply conductors, with no pole operable independently. There's no allowance for sequential or single-conductor opening, and 430.105 actually requires the grounded-conductor pole (if present) to open simultaneously with the others, not first.

One disconnect serving multiple motors

NEC 430.112

Every motor needs its own disconnect unless it fits one of three group exceptions in 430.112: single machine, shared branch-circuit protection under 430.53(A), or same room in sight of the disconnect.

Q38 NEC 430.112

Under 430.112, which situation permits a single disconnecting means to serve more than one motor?

  1. A The motors are supplied by the same feeder but separate branch circuits with separate protection
  2. B The motors are in the same building but different rooms
  3. C The motors drive several parts of a single machine, such as a crane or hoist
  4. D The motors are all rated 1 hp or less
Show answer & explanation

Correct: C — The motors drive several parts of a single machine, such as a crane or hoist

430.112(1) permits one disconnect for motors driving several parts of a single machine or piece of apparatus, like cranes, hoists, or metal- and woodworking machines. Being in the same building but different rooms doesn't qualify — the 'single room, in sight' condition in 430.112(3) requires one room. Motor horsepower rating isn't a listed condition, and separate branch-circuit protection on each motor doesn't meet the shared-protection condition in 430.112(2), which requires one set of branch-circuit protective devices under 430.53(A).

Alternate disconnect types for small/stationary motors by hp

NEC 430.109(B)

Small stationary motors don't need a dedicated disconnect switch — the breaker, a general-use switch, or a listed manual controller can legally do the job.

Q39 NEC 430.109(B)

A stationary motor rated at 15 hp needs a disconnecting means. Which option is permitted under 430.109(B)?

  1. A A general-use switch rated at twice the motor's full-load current
  2. B A general-use snap switch rated for ac-dc use
  3. C The branch-circuit overcurrent device serving the motor
  4. D A listed manual motor controller marked "Suitable as Motor Disconnect"
Show answer & explanation

Correct: C — The branch-circuit overcurrent device serving the motor

Per 430.109(B), stationary motors of 18 hp or less can use the branch-circuit overcurrent device itself as the disconnecting means. The general-use switch, ac-dc snap switch, and listed manual controller options in 430.109(C) only apply at 2 hp or less, not 15 hp.

Special-case disconnect types (autotransformer, isolating, cord-and-plug, torque)

NEC 430.109(D)

General-use switches, isolating switches, and cord-and-plug sets can serve as the motor disconnect — but only under the specific conditions each 430.109 exception spells out.

Q40 NEC 430.109(D)

A stationary AC motor rated 125 hp needs a disconnecting means. Which option is explicitly permitted by 430.109(E)?

  1. A Any general-use switch as long as branch fuses are set at 150 percent of full-load current
  2. B A general-use or isolating switch marked 'Do not operate under load'
  3. C A general-use switch with no special marking, since the motor is AC
  4. D A horsepower-rated attachment plug and receptacle
Show answer & explanation

Correct: B — A general-use or isolating switch marked 'Do not operate under load'

430.109(E) permits a general-use or isolating switch for stationary motors rated more than 40 hp dc or 100 hp ac, but only when it is plainly marked 'Do not operate under load.' An unmarked general-use switch doesn't satisfy the exception, the plug-and-receptacle option belongs to cord-and-plug-connected motors under 430.109(F), and the 150 percent fuse/breaker condition is part of the autotransformer controller exception in 430.109(D), not this one.

Feeder for Several Motors (NEC 430.24)

NEC 430.24

A feeder supplying several motors must have an ampacity of at least 125% of the highest-rated motor's full-load current plus the sum of the full-load currents of all the other motors (430.24).

Q41 NEC 430.24

A feeder supplies 3 three-phase motors — 10, 25 and 50 HP at 460 V. What minimum feeder conductor ampacity does NEC 430.24 require?

  1. A 116.5 A
  2. B 113 A
  3. C 141.25 A
  4. D 129.25 A
Show answer & explanation

Correct: D — 129.25 A

Full-load currents (Table 430.250): 14, 34, 65 A. 430.24: 125% of the largest (65 A) plus the rest — 1.25 × 65 + 48 = 129.25 A. Distractors skip the 125%, apply it to all motors, or to the wrong motor.

How to run the equipment grounding conductor to a motor

NEC 430.245

Bond the raceway or cable armor to a terminal housing junction box, which can sit up to 6 ft from the motor if flexible wiring methods with stranded leads connect the two.

Q42 NEC 430.245

A motor is wired with rigid metal conduit, and the junction box for the motor terminals is located 5 ft from the motor. Stranded leads run between the box and the motor within the conduit. Is this separation permitted?

  1. A No, the junction box must always be mounted directly on the motor frame
  2. B Yes, because the raceway is bonded to both the motor and the box and the separation is within the 6 ft limit
  3. C No, rigid metal conduit is not a permitted method for this separation
  4. D Yes, but only if the conductors are solid, not stranded
Show answer & explanation

Correct: B — Yes, because the raceway is bonded to both the motor and the box and the separation is within the 6 ft limit

Per 430.245(B), the junction box may be separated from the motor by not more than 1.8 m (6 ft) when stranded leads run through rigid metal conduit (among other listed flexible methods), with the raceway connected to both the motor and the box. Rigid metal conduit is explicitly permitted, and solid conductors are not allowed under this separation rule — leads must be stranded.

Guarding exposed live parts of motors and controllers

NEC 430.232

Exposed live parts at 50V or more must be guarded by enclosure or by location — height, room access, or platform — and if guarded only by location, attendants need insulating mats.

Q43 NEC 430.232 Code lookup

A 480-volt stationary motor without any commutator/brush assembly has exposed live terminals inside its terminal box, located in a general production area accessible to all plant employees, not elevated and not in a qualified-persons-only room. Which section specifies the acceptable methods (enclosure, location, or elevation) for guarding these live parts against accidental contact?

  1. A 430.245(A)
  2. B 430.242
  3. C 430.233
  4. D 430.232
Show answer & explanation

Correct: D — 430.232

430.232 lists the permitted guarding methods (qualified-persons-only room, elevated balcony/gallery/platform, or 2.5 m/8 ft elevation) for exposed live parts of motors/controllers at 50V or more. 430.233 only applies once 430.232's location-based guarding is used and an attendant needs access, addressing insulating mats/platforms rather than the guarding methods themselves.

Required nameplate markings for standard motors

NEC 430.7(A)

Every motor nameplate must show manufacturer, volts, full-load current, speed, and time rating — plus horsepower, code letter, and protection markings once size or features trigger them.

Q44 NEC 430.7(A) Code lookup

A 25 hp, 460V polyphase wound-rotor induction motor is being nameplated at the factory. In addition to the standard markings, the technician needs to confirm what secondary-side electrical values must also appear on the nameplate. Which section lists this requirement?

  1. A 430.6(A)(2)
  2. B 430.7(B)
  3. C 430.7(A)
  4. D 430.9(A)
Show answer & explanation

Correct: C — 430.7(A)

430.7(A) item (10) requires wound-rotor induction motors to be marked with secondary volts and full-load current in addition to the primary nameplate data; 430.7(B) only covers locked-rotor code letters, not secondary voltage/current, and 430.9(A) covers controller/terminal markings, not motor nameplate content.

Terminal marking, conductor material, and torque for control circuits

NEC 430.9

Motor and controller terminals must be clearly marked, wired with copper unless otherwise identified, and torqued to at least 0.8 N·m (7 lb-in) on small control-circuit screw terminals.

Q45 NEC 430.9

A screw-type pressure terminal on a control circuit device is being landed with a 14 AWG copper conductor. The terminal carries no torque marking. What minimum torque applies per 430.9(C)?

  1. A Whatever torque is listed in Table 430.9(C), regardless of marking
  2. B No minimum applies to control circuit terminals
  3. C 1.4 N·m (12 lb-in)
  4. D 0.8 N·m (7 lb-in)
Show answer & explanation

Correct: D — 0.8 N·m (7 lb-in)

430.9(C) sets a minimum torque of 0.8 N·m (7 lb-in) for screw-type pressure terminals used with 14 AWG or smaller copper conductors, unless the terminal itself is identified for a different value. There is no separate table referenced in this section, and a minimum does apply — it isn't optional.

Nameplate marking for multimotor and combination-load equipment

NEC 430.7(D)

Factory-wired multimotor equipment needs one nameplate with volts, phase, minimum circuit ampacity, and max protective device rating — figured with every simultaneous load counted.

Q46 NEC 430.7(D)

A factory-wired piece of multimotor equipment must have a visible nameplate showing all of the following EXCEPT:

  1. A The maximum ampere rating of the circuit short-circuit and ground-fault protective device
  2. B The minimum supply circuit conductor ampacity
  3. C The individual full-load current of each motor inside the equipment
  4. D The manufacturer's name
Show answer & explanation

Correct: C — The individual full-load current of each motor inside the equipment

Per 430.7(D)(1), the nameplate must show manufacturer's name, voltage, frequency, phases, minimum supply conductor ampacity, and maximum protective device rating — a single combined ampacity and protective device figure, not a per-motor breakdown of individual full-load currents.

Disconnecting means for high-voltage motor controllers

NEC 430.208

The disconnect for a motor controller over 1000V must match or exceed the circuit voltage, be lockable, and be rated at least 100% of the motor's (or drive's) full-load current — no sizing margin required, but no shortfall allowed either.

Q47 NEC 430.208

A high-voltage motor has a full-load current rating of 40 A. What is the minimum current rating required for its disconnecting means under 430.208?

  1. A Whatever rating matches the branch-circuit short-circuit protective device
  2. B 32 A, applying an 80% derating factor
  3. C 50 A, applying a 125% continuous-duty margin
  4. D 40 A
Show answer & explanation

Correct: D — 40 A

430.208 sets the minimum disconnect current rating at not less than 100 percent of the motor's full-load current rating — no additional 125% continuous-duty margin or 80% derating applies to this specific requirement, and the disconnect rating is independent of the short-circuit protective device rating.

Fault-current protection devices for high-voltage motors

NEC 430.206(C)

Over-1000V motor circuits need a breaker or fuses that clear faults, disconnect safely without arc hazard, and don't auto-reclose unless faults are transient and safe.

Q48 NEC 430.206(C) Code lookup

A 2400-volt synchronous motor circuit is being protected with fuses installed in each ungrounded conductor to clear short-circuit and ground-fault current. Which section specifies the requirements for arranging these fuses so they cannot be serviced while energized and must be used with (or serve as) a suitable disconnecting means?

  1. A 430.206(C)(3)
  2. B 430.206(C)(1)
  3. C 430.206(C)(2)
  4. D 430.206(B)(1)
Show answer & explanation

Correct: B — 430.206(C)(1)

430.206(C)(1) lists the two acceptable forms of fault-current protection for high-voltage motor circuits — a circuit breaker or fuses in each ungrounded conductor — and spells out the fuse servicing/disconnect requirements. 430.206(B)(1) instead covers the type of overload device permitted, a different protection function.

Overload protection devices for high-voltage motors

NEC 430.206(B)

Over 1000V motors need thermal or current-sensing overload protection sized under engineering supervision, and it must trip all ungrounded conductors together without unsafe auto-restart.

Q49 NEC 430.206(B)

When the overload interrupting device operates on a high-voltage motor circuit, what is required?

  1. A Only the ungrounded conductor carrying the highest current must open
  2. B All ungrounded conductors must be disconnected simultaneously
  3. C Each ungrounded conductor may open on its own independent timer
  4. D The neutral conductor must open before the ungrounded conductors
Show answer & explanation

Correct: B — All ungrounded conductors must be disconnected simultaneously

430.206(B)(3) requires the overload interrupting device to simultaneously disconnect all ungrounded conductors, preventing single-phasing. Opening only one conductor, staggering the openings, or involving the neutral doesn't meet this requirement.

Overload protection for small automatically-started motors (≤1 hp)

NEC 430.32(B)

A motor of 1 hp or less that starts automatically needs overload protection by one of four permitted methods — separate device, integral thermal/electronic protector, failure-to-start protection, or sufficient winding impedance.

Q50 NEC 430.32(B)

Which of the following is NOT one of the permitted overload protection methods for an automatically started motor of 1 hp or less under 430.32(B)?

  1. A A separate overload device sized per 430.32(A)(1)
  2. B Motor windings with impedance sufficient to prevent overheating on failure to start
  3. C Sizing the branch-circuit short-circuit protective device at 250% of full-load current
  4. D A thermal protector integral with the motor
Show answer & explanation

Correct: C — Sizing the branch-circuit short-circuit protective device at 250% of full-load current

430.32(B) lists exactly four methods: a separate overload device, a thermal protector or electronic protection, a device integral with the motor protecting against failure-to-start damage, and impedance protection. Branch-circuit short-circuit protection sizing is a separate topic (430 Part IV) and is not one of the four overload options here.

Sizing conductors for a single continuous-duty motor

NEC 430.22

Branch-circuit conductors for a single continuous-duty motor need an ampacity of at least 125% of the motor's full-load current rating from 430.6(A)(1).

Q51 NEC 430.22

A single motor operates in a continuous duty application. Per 430.22, what minimum ampacity must its branch-circuit conductors have?

  1. A 125% of the motor full-load current rating
  2. B 115% of the motor service factor rating
  3. C 100% of the motor full-load current rating
  4. D 80% of the motor full-load current rating
Show answer & explanation

Correct: A — 125% of the motor full-load current rating

430.22 requires conductors supplying a single continuous-duty motor to have an ampacity of not less than 125% of the motor full-load current rating from 430.6(A)(1). Sizing at 100% ignores the required margin, and the service-factor and 80% figures aren't the basis this rule uses.

Tap conductor rules for a single motor fed from a group installation

NEC 430.53(D)

A tap to one motor in a group installation skips its own branch-circuit protection only if the tap's length and ampacity fit one of 430.53(D)'s two size-for-length trade-offs.

Q52 NEC 430.53(D)

A tap conductor runs from a group installation's branch circuit directly to a single motor's overload device, 22 ft away, with no individual branch-circuit protective device. Which condition must it meet under 430.53(D)(1)?

  1. A Ampacity not less than one-third the branch-circuit conductor ampacity
  2. B Length not exceeding 3 m (10 ft)
  3. C Ampacity not less than one-tenth the branch-circuit protective device rating
  4. D Ampacity not less than the full branch-circuit conductor ampacity
Show answer & explanation

Correct: A — Ampacity not less than one-third the branch-circuit conductor ampacity

430.53(D)(1) allows the tap to be sized at not less than one-third the branch-circuit conductor ampacity (never below 430.22) as long as it's 25 ft or less and physically protected. The one-tenth ampacity option and the 10 ft length belong to the separate 430.53(D)(2) path for taps ending at a listed manual controller or protective device. Requiring full branch-circuit ampacity would defeat the point of the tap exception.

Minimum conductor sizes for small motors, including 16/18 AWG exceptions

NEC 430.22(G)

Motor conductors default to a 14 AWG minimum, but 18 AWG and 16 AWG copper are allowed for small motors when overload class and overcurrent protection meet strict amperage-tied conditions.

Q53 NEC 430.22(G) Code lookup

A technician is installing 18 AWG copper conductors inside a control cabinet to supply a 4-amp full-load-current motor, protected per 430.52 with Class 10 overload protection. Which section permits using conductors smaller than 14 AWG for this small motor circuit?

  1. A 430.22(G)(1)
  2. B 430.22(G)
  3. C 430.22(F)
  4. D 430.22(G)(2)
Show answer & explanation

Correct: A — 430.22(G)(1)

430.22(G)(1) specifically permits 18 AWG copper conductors for motors with FLC greater than 3.5A up to 5A under the listed protection conditions. 430.22(G)(2) covers 16 AWG conductors for a different FLC range (5.5-8A), and 430.22(F) applies only to conductors between a stationary motor and a separate terminal enclosure, not general small-motor branch circuits.

Sizing shared branch protection to the smallest motor in a group

NEC 430.53(B)

One branch-circuit protective device can serve several motors only if it's sized to 430.52 for the smallest motor, each motor has its own overload protection, and it won't nuisance-trip under normal service.

Q54 NEC 430.53(B)

Per 430.53(B), when two or more motors are supplied by a single branch-circuit short-circuit and ground-fault protective device, that device must be sized based on which motor?

  1. A The largest rated motor in the group
  2. B The smallest rated motor in the group
  3. C Whichever motor starts first in sequence
  4. D The average full-load current of all motors in the group
Show answer & explanation

Correct: B — The smallest rated motor in the group

430.53(B)(1) requires the shared protective device to be selected not to exceed what 430.52 allows for the smallest rated motor supplied by the circuit — sizing to the largest motor or an average current would let the device pass fault current too large to protect the smaller motor's conductors.

Speed-limiting devices for dc/series motors and converters

NEC 430.89

Separately excited dc motors, series motors, and converters that can overspeed from the dc end need a speed-limiting device unless inherent design or a qualified operator already limits speed.

Q55 NEC 430.89

Per 430.89, which of the following machines is required to have a speed-limiting device or other speed-limiting means?

  1. A A squirrel-cage induction motor
  2. B A series motor
  3. C A shunt-wound dc motor with a fixed field connection
  4. D A synchronous motor used at constant load
Show answer & explanation

Correct: B — A series motor

430.89 lists separately excited dc motors, series motors, and motor-generators/converters that can overspeed from the dc end as requiring speed-limiting means. A series motor is explicitly named. The other machine types listed are not among the three categories 430.89 addresses.

Conductor sizing for wye-start/delta-run and part-winding motors

NEC 430.22(C)

Line-side conductors are always sized at 125% of motor full-load current; motor-side conductors get a reduced percentage because they only carry part of the winding current.

Q56 NEC 430.22(C)

Which statement correctly describes conductor sizing for a wye-start, delta-run connected motor?

  1. A Both the line-side and motor-side conductors are sized at 125% of full-load current
  2. B Line-side conductors are sized at 125% of full-load current; motor-side conductors are sized at 72%
  3. C Both the line-side and motor-side conductors are sized at 58% of full-load current
  4. D Line-side conductors are sized at 72% of full-load current; motor-side conductors are sized at 125%
Show answer & explanation

Correct: B — Line-side conductors are sized at 125% of full-load current; motor-side conductors are sized at 72%

Per 430.22(C), branch-circuit conductors on the line side of the controller must have an ampacity of at least 125% of motor full-load current, while conductors between the controller and motor need only 72% because they carry just the 58% winding current (58% × 1.25 = 72%). Sizing both sides the same at 125%, swapping which side gets which percentage, or using the raw 58% figure instead of the adjusted 72% are all incorrect readings of the rule.

What Article 430 covers and where related articles apply

NEC 430.1

Article 430 is the master article for motors — conductors, protection, overload, control circuits, controllers, and control centers — but special equipment sends you elsewhere.

Q57 NEC 430.1

An electrician is sizing conductors and overload protection for a rooftop air-conditioning unit's compressor motor. Which article applies instead of Article 430?

  1. A Article 430, Part I only
  2. B Article 430, Part X
  3. C Article 430, Part XI
  4. D Article 440
Show answer & explanation

Correct: D — Article 440

Per 430.1, air-conditioning and refrigerating equipment is directed to Article 440, not the general motor article. Part X of 430 covers adjustable-speed drives and Part XI covers motors over 1000 volts nominal — neither applies just because the load is a compressor motor.

Conductor sizing when a bypass device is used

NEC 430.122(C)

With a bypass device, size the drive's supply conductors at 125% of the larger of the drive's rated input current or the motor's full-load current.

Q58 NEC 430.122(C)

An adjustable-speed drive system includes a bypass device. Per 430.122(C), how must the supply conductor ampacity be determined?

  1. A The larger of 125% of the drive's rated input current or 125% of the motor full-load current
  2. B The sum of 125% of the drive's rated input current and 125% of the motor full-load current
  3. C 100% of the motor full-load current, since the bypass runs the motor across the line
  4. D 125% of the drive's rated input current only
Show answer & explanation

Correct: A — The larger of 125% of the drive's rated input current or 125% of the motor full-load current

430.122(C) requires comparing 125% of the drive's rated input current with 125% of the motor full-load current (per 430.6) and using whichever is larger. Using only the drive's input current ignores the bypass path, summing the two overstates the load, and using 100% of FLC skips the required 125% factor.

Motor overload protection with adjustable-speed drives

NEC 430.124

A motor always needs overload protection — the drive can provide it, but a bypass circuit or multi-motor setup needs its own Part III protection.

Q59 NEC 430.124 Code lookup

A rooftop AHU is fed by an adjustable-speed drive whose nameplate states that motor overload protection is built into the power conversion equipment. The installer wants to confirm whether a separate overload relay must still be installed ahead of the motor. Which section governs whether additional overload protection is required in this case?

  1. A 430.126(A)
  2. B 430.124(C)
  3. C 430.124(A)
  4. D 430.130(A)
Show answer & explanation

Correct: C — 430.124(A)

430.124(A) directly addresses power conversion equipment marked as including motor overload protection, waiving the need for a separate device. 430.126(A) instead covers overtemperature protection (a different protective function), and 430.124(C) applies only to multiple-motor installations, not this single marked-drive scenario.

Automatic restart limits and orderly shutdown alternatives

NEC 430.43

Overload devices can't auto-restart a motor if that restart could hurt someone, but they can trip an alarm instead of an instant shutdown when stopping the motor is the more dangerous option.

Q60 NEC 430.43

A facility wants to install a motor overload device that automatically restarts the motor after it trips on overload. Under 430.43, when is this NOT permitted?

  1. A When automatic restarting of the motor could result in injury to persons
  2. B When the overload device is connected to a supervised alarm
  3. C When the motor is part of a continuous process
  4. D When the device is approved for use with the motor it protects
Show answer & explanation

Correct: A — When automatic restarting of the motor could result in injury to persons

430.43 prohibits an automatic-restarting overload device whenever restarting the motor could injure a person, regardless of approval status otherwise. Approval for use with the motor is a separate, necessary condition, not itself a bar to installation. Continuous-process operation and alarm connections relate to 430.44's orderly-shutdown alternative, not the restart prohibition in 430.43.

Autotransformer starter position requirements

NEC 430.82(B)

An autotransformer starter must have off, running, and starting positions, and it can't rest anywhere that bypasses overload protection.

Q61 NEC 430.82(B)

According to 430.82(B), which positions must an autotransformer starter provide?

  1. A Off, running, and at least one starting position
  2. B Starting and running only, with no off position
  3. C A single combined start/run position and an off position
  4. D Off and running only, with no separate starting position
Show answer & explanation

Correct: A — Off, running, and at least one starting position

430.82(B) requires an autotransformer starter to have an off position, a running position, and at least one starting position. Options that drop the starting position or the off position don't meet this three-position requirement.

When equipment/relay-table markings cap the protective device rating

NEC 430.52(C)(2)

A manufacturer's overload relay table or equipment marking is a hard ceiling on branch-circuit short-circuit and ground-fault protection — it wins even when 430.52's percentage tables allow a bigger device.

Q62 NEC 430.52(C)(2)

A motor controller's overload relay table specifies a maximum branch-circuit short-circuit and ground-fault protective device rating that is lower than the value permitted by the standard percentage-of-full-load-current table. What is the electrician required to do?

  1. A Average the two values to find an acceptable compromise rating
  2. B Use whichever value is higher to allow for motor starting current
  3. C Not exceed the rating shown in the overload relay table
  4. D Use the percentage-of-full-load-current table value since it is derived directly from the NEC
Show answer & explanation

Correct: C — Not exceed the rating shown in the overload relay table

Per 430.52(C)(2), where a maximum protective device rating is shown in a manufacturer's overload relay table or otherwise marked on the equipment, that value shall not be exceeded even if the percentage-based tables would allow a higher rating. Using the percentage table value, a higher value, or an averaged value all ignore the marked limit.

Purpose and scope of motor branch-circuit short-circuit/ground-fault protection

NEC 430.51

Part IV devices protect motor branch-circuit conductors, controllers, and motors against short circuits and ground faults only — not against overload, and not above 1000 volts.

Q63 NEC 430.51 Code lookup

A single 10 hp, 480V, three-phase motor's branch circuit needs short-circuit and ground-fault protection sized before the motor is even installed. Which section covers the general scope of the devices used for this protection under Part IV of Article 430?

  1. A 430.56
  2. B 430.55
  3. C 430.51
  4. D 430.52
Show answer & explanation

Correct: C — 430.51

430.51 states the purpose of Part IV — protecting motor branch-circuit conductors, control apparatus, and motors against short circuits and ground faults — and notably excludes GFCI/GFPE devices under 210.8, 230.95, and 590.6. 430.52 covers actual rating/setting calculations, not the scope statement, so it's the closer but wrong distractor.

Circuit breakers and molded case switches used as controllers

NEC 430.83(A)(2)

An ampere-rated inverse time circuit breaker or a molded case switch can serve as the motor controller for any motor — no horsepower rating needed.

Q64 NEC 430.83(A)(2) Code lookup

A 5 hp, 480V three-phase motor branch circuit uses an inverse time circuit breaker as the motor controller, and that same breaker is also being relied on to provide the motor's overload protection. Which section requires this dual-use breaker to also meet the article's overload-protection provisions?

  1. A 430.83(A)(3)
  2. B 430.83(A)(2)
  3. C 430.55
  4. D 430.82
Show answer & explanation

Correct: B — 430.83(A)(2)

430.83(A)(2) permits an inverse time circuit breaker as a controller for all motors, and specifically states that when it doubles as overload protection it must meet the article's overload provisions. 430.83(A)(3) covers molded case switches, not breakers, and 430.82 governs general controller design (starting/stopping duty), not the breaker-as-overload-device rule.

Conductor ampacity for adjustable-voltage drives and valve actuator motors

NEC 430.6(C)

AC adjustable-voltage drive motors size conductors from the nameplate max operating current (or 150% of Table 430.249/430.250 if none is marked); valve actuator motor assemblies always size from nameplate full-load current.

Q65 NEC 430.6(C)

An AC adjustable voltage, variable torque drive motor has a maximum operating current clearly marked on its control nameplate. How should conductor ampacity be determined per 430.6(C)?

  1. A Use the marked maximum operating current from the nameplate
  2. B Use the Table 430.249 value directly with no adjustment
  3. C Use 150 percent of the Table 430.250 value regardless of the nameplate
  4. D Use the nameplate full-load current as required for valve actuator motor assemblies
Show answer & explanation

Correct: A — Use the marked maximum operating current from the nameplate

Per 430.6(C), when the maximum operating current is marked on the motor or control nameplate, that value governs conductor ampacity. The 150 percent of Table 430.249/430.250 method is only a fallback used when no such marking exists, and the full-load-current method belongs to valve actuator motor assemblies under 430.6(D), not adjustable-voltage drives.

Using a motor controller as the overload protective device

NEC 430.39

A motor controller can double as the overload device only if it has the right number of overload units per Table 430.37 and they're active in running position (and starting position too, for DC motors).

Q66 NEC 430.39 Code lookup

A 5 hp, 480V ac motor on continuous duty has separate overload relays sized per Table 430.37, but the electrician wants to skip a dedicated overload relay and instead use the motor controller itself as the overload device. Which section permits this and sets the condition that the overload units be operative in the running position for an ac motor?

  1. A 430.38
  2. B 430.39
  3. C 430.32(A)(1)
  4. D 430.40
Show answer & explanation

Correct: B — 430.39

430.39 specifically allows a motor controller to double as the overload device, conditioned on the number of overload units matching Table 430.37 and being operative in the running position (ac) or starting and running (dc). 430.40 covers overload relay ratings/settings, not using the controller itself as the device, and 430.38 addresses how many conductors an overload device must open, not the controller-as-overload permission.

Controller need not open all conductors (unless it's also the disconnect)

NEC 430.84

A motor controller only has to switch enough conductors to start and stop the motor — it must open all ungrounded conductors only when it's also doing disconnect duty.

Q67 NEC 430.84 Code lookup

A 15 hp, 480V three-phase motor has its controller mounted separately from a disconnecting means that is located within sight of the motor. An inspector asks whether the controller itself is required to open every ungrounded conductor to the motor. Which section answers whether the controller must open all conductors?

  1. A 430.111
  2. B 430.84
  3. C 430.87
  4. D 430.75
Show answer & explanation

Correct: B — 430.84

430.84 states the motor controller is not required to open all conductors to the motor, unless it also serves as the disconnecting means. 430.75 governs disconnection of control circuits, not the controller's conductor-opening duty, and 430.87 addresses how many motors one controller may serve — neither answers this question.

How a motor controller's horsepower/ampere rating is set

NEC 430.83(A)(1)

A motor controller's horsepower rating at the application voltage must be at least equal to the motor's horsepower rating.

Q68 NEC 430.83(A)(1) Code lookup

An electrician is selecting a manual motor starter (not an inverse time circuit breaker or molded case switch) to control a 10 HP, 480V three-phase motor. Which section specifies the minimum horsepower rating the controller must have?

  1. A 430.82(A)
  2. B 430.83(A)(2)
  3. C 430.81(A)
  4. D 430.83(A)(1)
Show answer & explanation

Correct: D — 430.83(A)(1)

430.83(A)(1) requires motor controllers (other than inverse time circuit breakers and molded case switches) to carry a horsepower rating at the application voltage not lower than the motor's horsepower. 430.83(A)(2) instead addresses circuit breakers used as controllers, and 430.81(A) covers general-use switches for stationary motors of 1/8 HP or less, neither of which sets this rating requirement.

Short-circuit current rating limits for controllers

NEC 430.83(F)

Never install a motor controller where available fault current exceeds its short-circuit current rating (SCCR).

Q69 NEC 430.83(F)

Per 430.83(F), what determines whether a motor controller is permitted at a given location?

  1. A The controller's horsepower rating must match the motor's horsepower rating
  2. B The controller must have a disconnecting means within sight of the motor
  3. C The available fault current at that location must not exceed the controller's short-circuit current rating
  4. D The controller must be rated for at least 125% of the motor's full-load current
Show answer & explanation

Correct: C — The available fault current at that location must not exceed the controller's short-circuit current rating

430.83(F) prohibits installing a motor controller where available fault current exceeds its short-circuit current rating (SCCR). Horsepower matching, the 125% full-load current factor, and sight-disconnect rules are real 430 requirements but are governed by other subsections, not the SCCR limit in 430.83(F).

Straight vs. slash voltage ratings on controllers

NEC 430.83(E)

A straight-rated controller just needs a rating ≥ the circuit's line-to-line voltage; a slash-rated controller needs the circuit solidly grounded, with both its line-to-ground and line-to-line voltages fitting the two label values.

Q70 NEC 430.83(E) Code lookup

A shop is wiring a motor controller that will be installed on an ungrounded 480-volt, 3-phase delta system where no conductor is referenced to ground. The controller nameplate shows a single voltage rating rather than two values separated by a slash. Which section governs whether this straight-rated controller may be applied on this circuit?

  1. A 430.83(A)
  2. B 430.83(E)
  3. C 430.82
  4. D 430.85
Show answer & explanation

Correct: B — 430.83(E)

430.83(E) is the Voltage Rating provision distinguishing straight-rated controllers (permitted if nominal voltage between any two conductors doesn't exceed the rating) from slash-rated controllers (which require a solidly grounded system). 430.83(A) covers General ratings tied to horsepower/breaker/switch selection, not voltage rating rules, so it doesn't answer this scenario.

Sizing conductors to power/braking resistors on DC motors

NEC 430.29

Conductors to separately mounted power accelerating and dynamic braking resistors are sized from Table 430.29 using motor full-load current, not the ampacity tables you'd use for regular branch-circuit conductors.

Q71 NEC 430.29

A DC motor controller connects to a separately mounted dynamic braking resistor. Per 430.29, what value is the starting point for sizing the connecting conductors using Table 430.29?

  1. A The motor controller's horsepower rating converted to amperes
  2. B The motor's full-load current
  3. C The resistor's nameplate wattage divided by system voltage
  4. D The branch-circuit short-circuit protective device rating
Show answer & explanation

Correct: B — The motor's full-load current

430.29 states that conductors connecting the motor controller to separately mounted power accelerating and dynamic braking resistors must have an ampacity not less than the value calculated from Table 430.29 using motor full-load current. The resistor wattage-based figure, the horsepower-to-amperes conversion, and the protective device rating are not the basis this section specifies.

Conductor sizing for DC motors fed through rectifiers

NEC 430.22(A)

Size the rectifier's input conductors at 125% of rated input current, then size the DC output conductors at 150% or 190% of motor full-load current depending on bridge type.

Q72 NEC 430.22(A)

A DC motor is supplied through a single-phase, full-wave rectifier bridge. Per 430.22(A), how must the conductors between the rectifier's output terminals and the motor be sized?

  1. A Not less than 125% of the motor full-load current rating
  2. B Not less than 190% of the motor full-load current rating
  3. C Not less than 125% of the rectifier's rated input current
  4. D Not less than 150% of the motor full-load current rating
Show answer & explanation

Correct: D — Not less than 150% of the motor full-load current rating

430.22(A) requires output conductors on a full-wave rectifier-supplied DC motor to have an ampacity of at least 150% of motor full-load current. The 190% figure applies only to half-wave bridges, and the 125% figures describe the input side of the rectifier, not the motor-side output conductors.

Using the disconnect as the controller for small stationary/portable motors

NEC 430.81(A)

A dedicated controller isn't always required — small motors can use the branch-circuit disconnect (≤18 hp, stationary) or a plug/cord connector (≤13 hp, portable) instead.

Q73 NEC 430.81(A)

A stationary clock motor rated at 1/12 hp runs continuously and cannot be damaged by overload or failure to start. What can serve as its motor controller?

  1. A A cord connector, since the motor is under 13 hp
  2. B A separate magnetic starter is always required regardless of horsepower
  3. C An attachment plug and receptacle only
  4. D The branch-circuit disconnecting means
Show answer & explanation

Correct: D — The branch-circuit disconnecting means

Per 430.81(A), a stationary motor of 1/8 hp or less that is normally left running and cannot be damaged by overload or failure to start may use the branch-circuit disconnecting means as its controller. The plug/receptacle and cord connector options apply to portable motors under 430.81(B), not stationary ones.

Sizing feeder protection for mixed motor and other loads

NEC 430.63

When a feeder serves motors plus other loads, size the protective device for the other loads' full rating plus the largest allowed motor-branch-circuit protection value.

Q74 NEC 430.63 Code lookup

A feeder supplies one 25 hp, 460V, 3-phase motor plus a 30A continuous non-motor load such as lighting. Which section establishes the required rating of the feeder overcurrent protective device by combining the motor's branch-circuit rating with the other load?

  1. A 430.63
  2. B 430.62
  3. C 430.53
  4. D 430.54
Show answer & explanation

Correct: A — 430.63

430.63 covers feeders supplying a motor load plus other (non-motor) load(s), setting the device rating at the sum of the other load(s) plus the motor's permitted rating per 430.52/430.62. 430.62 only addresses feeders serving motor loads alone, with no other load added in.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access