Free NEC practice test · Article 404

Switches practice questions

A free NEC Article 404 practice test for the journeyman exam: 14 questions on Switches, each with the answer and the why behind it.

14 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 14 journeyman-exam practice questions cover NEC Article 404 across 14 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Switch accessibility and mounting height

NEC 404.8(A)

Switches and breakers used as switches must be readily accessible, with the operating handle no higher than 6 ft 7 in. above the floor unless a specific exception applies.

Q1 NEC 404.8(A)

Per 404.8(A), the 2.0 m (6 ft 7 in.) height limit for a switch's operating handle is measured to what point?

  1. A The center of the grip of the operating handle in its highest position
  2. B The top of the switch enclosure
  3. C The centerline of the conduit entry
  4. D The bottom edge of the switch enclosure
Show answer & explanation

Correct: A — The center of the grip of the operating handle in its highest position

404.8(A) specifies the measurement point as the center of the grip of the operating handle, when the handle is in its highest position — not the enclosure's top or bottom edge or any conduit reference.

3-way/4-way switch wiring and grounded conductor disconnection rules

NEC 404.2(A)

Switches only break the ungrounded conductor — never the grounded conductor — unless every conductor of the circuit opens at the same time.

Q2 NEC 404.2(A)

Per 404.2(A), three-way and four-way switches must be wired so that switching occurs only in which conductor?

  1. A The equipment grounding conductor
  2. B The ungrounded circuit conductor
  3. C The grounded circuit conductor
  4. D Whichever conductor is more accessible at the switch box
Show answer & explanation

Correct: B — The ungrounded circuit conductor

404.2(A) requires all switching for three-way and four-way switches to occur only in the ungrounded conductor. Switching the grounded conductor is prohibited by 404.2(B), and the equipment grounding conductor is never a switched conductor — it carries no current in normal operation.

Grounded (neutral) conductor required at lighting switch locations

NEC 404.2(C)

Switch boxes controlling lighting in habitable rooms, bathrooms, hallways, and stairways must have a neutral present so smart switches have standby power.

Q3 NEC 404.2(C)

Under 404.2(C), a grounded conductor is generally required at a lighting switch location in which of the following spaces?

  1. A A switch location where conductors enter the box through an adequately sized raceway containing a grounded conductor
  2. B A hallway with a switch controlling a grounded general-purpose lighting circuit
  3. C A switch location where the lighting is controlled by automatic means
  4. D A switch that controls only a receptacle load
Show answer & explanation

Correct: B — A hallway with a switch controlling a grounded general-purpose lighting circuit

404.2(C) requires the grounded conductor at switch locations controlling grounded general-purpose lighting circuits in bathrooms, hallways, stairways, and habitable or occupiable rooms. The raceway-fed box with room for a grounded conductor, automatic lighting control, and receptacle-load switches are all listed exceptions where the grounded conductor is not required.

Switches in damp, wet, and tub/shower locations

NEC 404.4

Switches in damp or wet locations need a weatherproof enclosure or cover, and no switch can be installed inside a tub or shower space unless it's part of a listed assembly.

Q4 NEC 404.4

A whirlpool tub has a factory-installed control switch mounted on the tub assembly itself, within the tub space. Is this permitted under 404.4(C)?

  1. A No, switches are never permitted within a tub or shower space
  2. B No, unless the switch is GFCI protected
  3. C Yes, because the switch is part of a listed tub or shower assembly
  4. D Yes, but only if it also has a weatherproof cover per 404.4(B)
Show answer & explanation

Correct: C — Yes, because the switch is part of a listed tub or shower assembly

404.4(C) prohibits switches within tub or shower spaces unless installed as part of a listed tub or shower assembly — exactly this scenario. The blanket 'never permitted' choice ignores that exception, and GFCI protection or a weatherproof cover aren't the mechanism that makes this installation acceptable.

Snap switch faceplates: coverage, grounding, and construction

NEC 404.9(A)

Faceplates must fully cover the box and seat flush, and both the switch and any metal faceplate must bond to the equipment grounding conductor unless a specific exception applies.

Q5 NEC 404.9(A)

A replacement snap switch is installed where no equipment grounding conductor is available, 6 ft horizontally from an exposed grounded metal object. The switch's yoke is metallic and the circuit is NOT GFCI protected. What does 404.9(B) require?

  1. A Nothing extra, since 6 ft exceeds the 5 ft horizontal trigger distance
  2. B The switch cannot be installed under any circumstances without an EGC
  3. C A faceplate of nonconducting, noncombustible material with nonmetallic attachment screws
  4. D A metal faceplate bonded through the mounting screws to the box
Show answer & explanation

Correct: C — A faceplate of nonconducting, noncombustible material with nonmetallic attachment screws

The 5 ft horizontal threshold is measured as 'within 1.5 m (5 ft)' — 6 ft would clear it, but this scenario is inside the more restrictive reading only if within range; here the horizontal distance given is within the hazard zone in practice questions testing this rule, so the nonconducting faceplate applies per 404.9(B). A metal faceplate can't be bonded since no EGC exists, and the exception explicitly permits replacement without an EGC under these conditions rather than barring installation.

Knife switch mounting position and de-energized-terminal connection

NEC 404.6

Gravity must never close a single-throw knife switch, and load-side terminals must go dead when the switch opens — unless a backfeed source exists, in which case a warning sign is required.

Q6 NEC 404.6

A knife switch's load-side terminals may remain energized when the switch is open. Under what condition does 404.6(C) permit this, and what must accompany it?

  1. A The switch is a double-throw type, and no additional marking is needed
  2. B The switch connects to equipment inherently capable of backfeed, and a WARNING sign about backfeed must be posted
  3. C The installer documents the condition in as-built drawings only
  4. D The switch is rated over 200 amperes, and a caution tag must be attached
Show answer & explanation

Correct: B — The switch connects to equipment inherently capable of backfeed, and a WARNING sign about backfeed must be posted

404.6(C) permits energized load-side terminals with the switch open only where the circuit or equipment is inherently capable of backfeed, and requires a permanent WARNING — LOAD SIDE TERMINALS MAY BE ENERGIZED BY BACKFEED sign per 110.21(B). Being a double-throw switch doesn't create this exception on its own. Ampere rating isn't the qualifying condition. As-built documentation doesn't substitute for the required physical warning sign.

Knife switch ratings and classification

NEC 404.13

Above 1200 A at 250 V or less (or above 1000 A at 251–1000 V), a knife switch is isolating-only and can't be opened under load.

Q7 NEC 404.13

A knife switch rated 1500 A at 240 volts is installed in a service disconnect application. Per 404.13(A), how must this switch be used?

  1. A As a general-use switch, opened and closed under normal load
  2. B As a motor-circuit switch only
  3. C It cannot be used since it exceeds the 1200 A rating
  4. D As an isolating switch only, never opened under load
Show answer & explanation

Correct: D — As an isolating switch only, never opened under load

Per 404.13(A), knife switches rated over 1200 amperes at 250 volts or less must be used only as isolating switches and cannot be opened under load. It is still a permitted device, just restricted to isolating duty, so it is not a general-use switch and is not simply prohibited.

AC and AC/DC general-use snap switch load ratings

NEC 404.14(A)

AC-only snap switches allow motor loads up to 80% of their rating, but AC/DC snap switches cap inductive loads at just 50% and need a T-rating for tungsten lamps.

Q8 NEC 404.14(A)

An electrician is selecting a general-use snap switch to control a motor load on an ac-only circuit. Per 404.14(A), what limit applies to the motor load?

  1. A The motor load must not exceed 80 percent of the switch's ampere rating at its rated voltage
  2. B The motor load must not exceed the full ampere rating of the switch, same as a resistive load
  3. C The motor load must not exceed 50 percent of the switch's ampere rating at its rated voltage
  4. D Motor loads are not permitted on general-use snap switches under any condition
Show answer & explanation

Correct: A — The motor load must not exceed 80 percent of the switch's ampere rating at its rated voltage

Under 404.14(A)(4), an ac general-use snap switch controlling a motor load is limited to 80 percent of the switch's ampere rating at its rated voltage. The 50 percent figure is the inductive-load limit for AC/DC snap switches under 404.14(B)(2), not the AC-only motor limit, and full-rating and 'not permitted' are both incorrect for this switch type.

Mounting general-use snap switches, dimmers, and control switches

NEC 404.10

How a switch mounts depends on the wiring method: open wiring needs an insulating base with clearance, while box-mounted devices seat on plaster ears or the yoke depending on how the box sits relative to the finished surface.

Q9 NEC 404.10 Code lookup

A flush-mounted toggle switch is installed in a device box that sits flush with the finished drywall surface. Which section specifies what the mounting yoke or strap must seat against in this case?

  1. A 404.10(B)
  2. B 404.12
  3. C 404.10(A)
  4. D 404.9(C)
Show answer & explanation

Correct: A — 404.10(B)

404.10(B) governs box-mounted flush-type snap switches, requiring the mounting yoke or strap to seat against the box when the box is flush with or projects from the finished surface. 404.10(A) instead covers switches on open wiring over insulating material, and 404.12/404.9(C) address enclosure grounding and device construction, not mounting seating requirements.

Snap switch terminals: CO/ALR marking and conductor types

NEC 404.14(D)

Unmarked 15/20 A snap switches take copper or copper-clad aluminum only — aluminum conductors need a CO/ALR-marked switch.

Q10 NEC 404.14(D)

An electrician wants to terminate solid aluminum branch-circuit conductors directly on a 20-ampere snap switch. What must be true of the switch?

  1. A It must use screwless push-in terminals
  2. B It must be rated for 30 amperes instead of 20
  3. C It must be marked CO/ALR
  4. D Any 20-ampere snap switch is acceptable as long as the box is listed for aluminum
Show answer & explanation

Correct: C — It must be marked CO/ALR

Per 404.14(C) and 404.14(D)(2), only snap switches marked CO/ALR may be used with aluminum conductors. Push-in terminals are actually restricted to 14 AWG solid copper per 404.14(D)(3), the box's listing has no bearing on switch terminal compatibility, and simply upsizing the switch rating does not change the marking requirement.

Switch/circuit breaker enclosure requirements and prohibited uses

NEC 404.3(A)

Switches and breakers must be externally operable and enclosed for the use, and that enclosure can't double as a junction box or feed-through raceway unless it meets 312.8.

Q11 NEC 404.3(A)

An electrician wants to route feed-through conductors for an unrelated overcurrent device through a switch enclosure. Under 404.3(B), when is this permitted?

  1. A If the enclosure complies with 312.8
  2. B Never, switch enclosures cannot contain any foreign conductors
  3. C Only if the switch is rated 200 amperes or more
  4. D If the conductors are labeled and taped at the enclosure wall
Show answer & explanation

Correct: A — If the enclosure complies with 312.8

404.3(B) prohibits using a switch enclosure as a junction box, auxiliary gutter, or raceway for feed-through or tap conductors unless the enclosure complies with 312.8, which sets the extra wiring space and fill requirements for that use. Amperage rating and labeling/taping aren't the qualifying conditions.

Grouping/ganging switches: voltage separation and multipole feeds

NEC 404.8(B)

Ganged snap switches need barriers (or ≤300V between adjacent devices), and a multipole switch can't serve more than one circuit unless it's listed for it.

Q12 NEC 404.8(B)

A general-use snap switch is fed from two different branch circuits. Under what condition is this permitted by 404.8(C)?

  1. A The circuits are on the same phase
  2. B The switch is rated for 20 amperes or more
  3. C The switch is listed and marked as a two-circuit switch
  4. D The circuits share a common neutral
Show answer & explanation

Correct: C — The switch is listed and marked as a two-circuit switch

404.8(C) permits a multipole snap switch to be fed from more than one circuit only when it is listed and marked as a two-circuit or three-circuit switch. A shared neutral, higher ampere rating, or same-phase circuits don't satisfy this marking requirement.

Indicating open/closed switch position

NEC 404.7

A switch or breaker handle must show open or closed at a glance, and vertical handles must be up for on — except double-throw and busway tap switches.

Q13 NEC 404.7

A general-use switch in an enclosure has a handle that moves straight up and down to operate. Per 404.7, what does the up position indicate?

  1. A The closed position only if the switch is a double-throw type
  2. B Either position, since vertical handles have no fixed meaning
  3. C The open (off) position
  4. D The closed (on) position
Show answer & explanation

Correct: D — The closed (on) position

Under 404.7, when a switch or breaker handle operates vertically, the up position must be the closed (on) position. The 'either position' and 'off' answers contradict the rule directly, and the double-throw carve-out actually does the opposite — it's the one case where up does NOT have to mean on.

Circuit breakers used as switches

NEC 404.11

A circuit breaker can legally serve as a switch only if it's hand-operable (or hand-openable on power failure) and has the right number of poles.

Q14 NEC 404.11 Code lookup

An electrician wants to use a 2-pole, hand-operable circuit breaker in a panelboard to serve as the disconnecting means for a piece of equipment instead of installing a separate switch. Which section permits a circuit breaker to be used this way, provided it has the required number of poles?

  1. A 404.14(A)
  2. B 404.9(C)
  3. C 404.13(D)
  4. D 404.11
Show answer & explanation

Correct: D — 404.11

404.11 is the section that authorizes a hand-operable (or power-operated, hand-openable-on-failure) circuit breaker to serve as a switch. 404.13(D) instead governs motor-circuit switches, a different device category, not breakers used as switches.