Free NEC practice test · Article 406

Receptacles practice questions

A free NEC Article 406 practice test for the journeyman exam: 14 questions on Receptacles, Cord Connectors, and Attachment Plugs (Caps), each with the answer and the why behind it.

14 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 14 journeyman-exam practice questions cover NEC Article 406 across 14 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Tamper-Resistant Receptacle Locations

NEC 406.12

TR receptacles are required at 15- and 20-amp, 125- and 250-volt nonlocking outlets in dwellings and a defined list of public and care occupancies, with narrow exceptions for height, appliance-dedicated, and luminaire/appliance receptacles.

Q1 NEC 406.12

Under 406.12, which of the following spaces is explicitly listed as requiring tamper-resistant receptacles?

  1. A Commercial kitchens in restaurants
  2. B Industrial machine shops
  3. C Dormitory units
  4. D Rooftop mechanical equipment rooms
Show answer & explanation

Correct: C — Dormitory units

406.12(7) lists dormitory units as a required TR location. Restaurant kitchens, rooftop mechanical rooms, and industrial machine shops are not on the enumerated list in 406.12.

Bathtub/Shower Receptacle Clearance Zone

NEC 406.9(C)

No receptacle can sit within 3 ft horizontally of a tub or shower, or within 8 ft vertically above its rim or threshold.

Q2 NEC 406.9(C)

Under 406.9(C), which installation correctly interrupts (limits) the bathtub/shower receptacle keep-out zone?

  1. A A full wall separating the receptacle location from the tub/shower space
  2. B A half-wall partition that doesn't reach the ceiling
  3. C Simply being more than 3 ft away in a diagonal line rather than a wall
  4. D An open doorway leading to an adjacent room
Show answer & explanation

Correct: A — A full wall separating the receptacle location from the tub/shower space

406.9(C) says the zone is all-encompassing except for space separated by a floor, wall, ceiling, room door, window, or fixed barrier. A full wall qualifies as a separating barrier. A half-wall or open doorway does not fully separate the space, so the zone still applies through them, and distance alone without a qualifying barrier doesn't remove the space from the zone.

Receptacle Orientation in Countertops, Work Surfaces, and Seating Areas

NEC 406.5(G)

Face-up receptacles are banned in countertops, work surfaces, under sinks, and seating areas unless the assembly is specifically listed for that use.

Q3 NEC 406.5(G)

An electrician wants to mount a receptacle face-up directly into a kitchen countertop. Under what condition is this permitted?

  1. A Only if the receptacle assembly is listed for countertop applications
  2. B Only if the countertop is more than 12 inches from the sink
  3. C Only if the circuit is protected by AFCI instead of GFCI
  4. D Never — countertop receptacles must always be installed on the wall behind the counter
Show answer & explanation

Correct: A — Only if the receptacle assembly is listed for countertop applications

Per 406.5(G)(1), a face-up receptacle in a countertop or work surface is prohibited unless the assembly is listed for that countertop or work-surface application. AFCI protection and distance from the sink don't factor into orientation permission; wall-mounting behind the counter is a separate, non-exclusive option.

Grounding Pole: Design, Identification, and Use

NEC 406.10(B)

The grounding pole is green-marked, mates first, and is off-limits for anything but the equipment grounding conductor.

Q4 NEC 406.10(B) Code lookup

A residential electrician installs a new duplex receptacle where the equipment grounding conductor terminal screw is hidden inside a recessed pressure wire connector, not visible from outside the device. Which section specifies how the conductor entrance hole must be marked in this case?

  1. A 406.10(B)
  2. B 406.10(A)
  3. C 406.10(C)
  4. D 406.10(D)
Show answer & explanation

Correct: A — 406.10(B)

406.10(B) covers grounding-pole identification, including the requirement that when the grounding terminal isn't visible, the conductor entrance hole must be marked with the word green/ground, letters G or GR, a grounding symbol, or a distinctive green color. 406.10(A) only requires the fixed grounding pole itself, not its marking, and 406.10(C)/(D) address terminal use restrictions and connection sequencing, not identification markings.

Grounding-Type Receptacles and EGC Connection

NEC 406.4(A)

15- and 20-amp receptacles must be grounding type, and their ground contacts must actually bond to an equipment grounding conductor per 250.146 — not just be present.

Q5 NEC 406.4(A)

An electrician installs a new 20-ampere general-purpose receptacle in a dwelling. Which statement about grounding is correct?

  1. A The receptacle only needs a grounding-type slot; wiring the ground contact is optional if space is tight
  2. B The receptacle must be grounding type, with its EGC contact connected to the circuit's equipment grounding conductor per 250.146
  3. C Grounding-type receptacles are only required on 20-ampere circuits, not 15-ampere circuits
  4. D Because the receptacle is grounding type, any appliance plugged into it must also have a grounded cord
Show answer & explanation

Correct: B — The receptacle must be grounding type, with its EGC contact connected to the circuit's equipment grounding conductor per 250.146

406.4(A) requires grounding-type receptacles on both 15- and 20-ampere branch circuits, and 406.4(B) and (C) require the EGC contacts to actually be connected per 250.146 — a slot alone doesn't satisfy the rule. 406.4(E) clarifies that this doesn't extend to requiring grounded cord-and-plug equipment.

Receptacle Terminals: CO/ALR Marking and Wire Compatibility

NEC 406.3(D)

Only CO/ALR-marked receptacles rated 20A or less may connect directly to aluminum conductors; unmarked 15/20A receptacles take copper or copper-clad aluminum only.

Q6 NEC 406.3(D)

An electrician wants to land an aluminum branch-circuit conductor directly on a 20-ampere receptacle. What must the receptacle be marked?

  1. A No marking required if the receptacle is rated 20 amperes or less
  2. B CC (copper-clad only)
  3. C AL-CU
  4. D CO/ALR
Show answer & explanation

Correct: D — CO/ALR

Per 406.3(C), receptacles rated 20 amperes or less designed for direct connection of aluminum conductors must be marked CO/ALR. There is no exception that waives marking for 20-ampere-or-less receptacles, and 'AL-CU' and 'CC' are not the designations this section uses.

Choosing Receptacle Type When Replacing (Grounded vs. Non-Grounding)

NEC 406.4(D)(1)

If an equipment grounding conductor is present, install a grounding-type receptacle; if not, you're limited to non-grounding, GFCI-marked, or GFCI-fed grounding-type with proper labels.

Q7 NEC 406.4(D)(1)

An electrician is replacing a worn receptacle in an older home. The outlet box has no equipment grounding conductor and no other grounding means. Which replacement is NOT permitted as described?

  1. A A grounding-type receptacle wired with a jumper to the metal box screw, with no verified ground path
  2. B A GFCI receptacle marked "No Equipment Ground"
  3. C A non-grounding-type receptacle in place of the old one
  4. D A grounding-type receptacle fed through a GFCI, marked "GFCI Protected" and "No Equipment Ground"
Show answer & explanation

Correct: A — A grounding-type receptacle wired with a jumper to the metal box screw, with no verified ground path

406.4(D)(1) only allows a grounding-type receptacle where a grounding means or equipment grounding conductor actually exists and is properly connected — bonding to an ungrounded box without a verified ground path doesn't satisfy this. Where no ground path exists, 406.4(D)(2) permits only a non-grounding replacement, a GFCI marked "No Equipment Ground," or a GFCI-fed grounding-type receptacle with the "GFCI Protected"/"No Equipment Ground" markings.

Replacements Must Preserve Required Protection (GFCI/AFCI/TR/WR/GFPE)

NEC 406.4(D)(3)

Swapping a receptacle never lowers its protection — if the outlet needs GFCI, AFCI, tamper-resistant, weather-resistant, control, or GFPE today, the replacement must have it too.

Q8 NEC 406.4(D)(3)

An electrician is replacing a receptacle in a bedroom that falls under the AFCI-required areas of 210.12. The existing receptacle currently has no arc-fault protection. What must the replacement be?

  1. A Any listed receptacle matching the existing device type, since only new installations require AFCI
  2. B A listed outlet branch-circuit type AFCI receptacle, or a receptacle protected by one, or protected by a listed combination-type AFCI breaker
  3. C A GFCI receptacle, since GFCI protection satisfies both shock and arc-fault requirements
  4. D A standard receptacle, since 210.12(E) Exception exempts replacements from AFCI protection
Show answer & explanation

Correct: B — A listed outlet branch-circuit type AFCI receptacle, or a receptacle protected by one, or protected by a listed combination-type AFCI breaker

406.4(D)(4) requires AFCI protection on replacement whenever the outlet is in a 210.12(A)-(C) area, and explicitly states the 210.12(E) Exception does not apply to replacements. GFCI protection addresses ground faults, not arc faults, so it does not substitute for AFCI.

Wet-Location Receptacle Enclosures

NEC 406.9(B)(1)

In a wet location, a 15/20 A receptacle's enclosure must stay weatherproof whether the plug is in or out — being covered while unplugged isn't enough.

Q9 NEC 406.9(B)(1)

A 20-ampere, 125-volt receptacle is installed outdoors on a patio where unattended equipment will be plugged in continuously. Per 406.9(B)(1), what must its enclosure do?

  1. A Stay weatherproof whether or not the attachment plug cap is inserted
  2. B Be weatherproof only during rainfall events
  3. C Meet only the damp-location cover requirement since it is a patio
  4. D Stay weatherproof only when the attachment plug cap is removed
Show answer & explanation

Correct: A — Stay weatherproof whether or not the attachment plug cap is inserted

406.9(B)(1) requires that 15 A and 20 A, 125- and 250-volt receptacles in a wet location have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. The weatherproof-only-when-unplugged option is a narrower exception reserved for receptacles subject to routine high-pressure spray washing, not general outdoor use.

Attachment Plug and Cord Connector Construction Safety

NEC 406.7

Plugs and connectors must have dead-front construction, and prongs can never be energized until plugged into a live source.

Q10 NEC 406.7

Under 406.7(A), which parts of an attachment plug or cord connector are permitted to be exposed current-carrying parts?

  1. A Only the prongs, blades, or pins
  2. B Any metal part not directly touching the cord jacket
  3. C The wire-termination screws, as long as a cover plate is available as an accessory
  4. D The grounding strap on the connector body
Show answer & explanation

Correct: A — Only the prongs, blades, or pins

406.7(A) requires dead-front construction: no exposed current-carrying parts except the prongs, blades, or pins, and the wire-termination cover is essential to the device's operation, not an optional accessory. The other choices describe exposed metal that dead-front construction is meant to prevent.

Damp-Location Receptacle Enclosures

NEC 406.9(A)

Outdoor receptacles in protected spots need an enclosure that stays weatherproof with the cap out and the cover closed, and must be listed weather-resistant.

Q11 NEC 406.9(A)

A receptacle is installed under a roofed open porch, shielded from beating rain and runoff. Per 406.9(A), what enclosure condition must it meet?

  1. A The enclosure must be weatherproof only while an attachment plug is inserted
  2. B The enclosure must be weatherproof when covered — plug cap not inserted and cover closed
  3. C The enclosure must be weatherproof only during rain events
  4. D No special enclosure is needed since the location isn't a wet location
Show answer & explanation

Correct: B — The enclosure must be weatherproof when covered — plug cap not inserted and cover closed

406.9(A) requires the enclosure to be weatherproof when the receptacle is covered — attachment plug cap not inserted and receptacle covers closed. It's the opposite of the 'weatherproof while in use' misconception, and the location still counts as damp even though it's not exposed to beating rain.

Faceplate Construction and Grounding

NEC 406.6

Faceplates must fully cover the opening and seat against the mounting surface; metal ones need minimum thickness and grounding, insulating ones need minimum thickness or reinforcement.

Q12 NEC 406.6

Which requirement applies to ALL metal receptacle faceplates regardless of thickness?

  1. A They must be at least 2.54 mm thick
  2. B They must be grounded
  3. C They must be listed as noncombustible
  4. D They must be reinforced for mechanical strength
Show answer & explanation

Correct: B — They must be grounded

406.6(B) requires that metal faceplates be grounded, with no exception based on thickness or material type. The noncombustible and reinforcement requirements apply to insulating faceplates under 406.6(C), and 2.54 mm (0.10 in.) is the insulating-material minimum, not a metal faceplate requirement.

Receptacle Mounting: Box Fastening and Flush Positioning

NEC 406.5

Receptacles must sit in securely fastened, identified boxes with the yoke held rigid, and the face must end up flush with or slightly proud of the faceplate.

Q13 NEC 406.5

After installation with a metal faceplate, where must the receptacle face end up per 406.5(D)?

  1. A Recessed at least 0.4 mm behind the metal faceplate
  2. B Flush with or projecting from the faceplate, same as insulating material faceplates
  3. C Projecting a minimum of 0.4 mm (0.015 in.) from the metal faceplate
  4. D Flush with the metal faceplate, never projecting
Show answer & explanation

Correct: C — Projecting a minimum of 0.4 mm (0.015 in.) from the metal faceplate

406.5(D) sets a stricter rule for metal faceplates than for insulating ones: the face must project a minimum of 0.4 mm (0.015 in.) from the plate, not merely sit flush. 'Flush, never projecting' and 'recessed' both contradict the minimum projection requirement. The 'flush with or projecting' standard is the rule for insulating faceplates, not metal ones — metal plates need that guaranteed clearance for shock protection.

Single-Pole Separable Connector Requirements

NEC 406.13

Single-pole separable connectors must be locking/latching, color-coded white for grounded and green for grounding, and connected/disconnected only in the correct sequence by a qualified person.

Q14 NEC 406.13

Under 406.13(D), which condition allows single-pole separable connectors to be connected and disconnected without sequential-interlocking connectors or a posted caution notice?

  1. A The connectors are of the locking type rather than the latching type
  2. B The supply connectors are interlocked to the source so connection/disconnection is impossible while energized
  3. C The connectors are listed and labeled for the application
  4. D The connectors are marked with the manufacturer's name and ratings
Show answer & explanation

Correct: B — The supply connectors are interlocked to the source so connection/disconnection is impossible while energized

406.13(D)(1) permits skipping the sequential-interlocking hardware or caution notice only when the supply connectors are source-interlocked so they physically cannot be mated or separated while energized. Listing, marking, and locking-vs-latching are baseline requirements under 406.13(A), not substitutes for one of the three connect/disconnect safeguards.