Calculators Motor FLC & Sizing Calculator
NEC 430

Motor FLC & Sizing Calculator

Full-load current, conductor, and overcurrent sizing for motors.

Motor details
Full-load current
A
Full-load current
Min conductor ampacity (125% FLC)
Recommended conductor (Cu, 75°C)
Branch-circuit OCPD (inverse-time CB)
Overload (125% FLC)
Note

Inverse-time breaker (250%), continuous duty, SF ≥ 1.15, conductor at 125% FLC / 75°C Cu. Simplified — verify Table 430.52 for your device type.

NEC 430

How NEC Article 430 motor sizing works

NEC Article 430 governs motor branch circuits, feeders, and overcurrent protection. The starting point is always the full-load current (FLC) from the NEC tables — Table 430.248 for single-phase motors and Table 430.250 for three-phase motors. These table values, not the nameplate amperes, drive all downstream sizing for conductors, overcurrent protective devices, and overloads.

Branch-circuit conductors must be sized at a minimum of 125% of motor FLC per 430.22(A), accounting for continuous motor operation. The branch-circuit overcurrent protective device uses 250% of FLC for an inverse-time circuit breaker per 430.52(C)(1) and Table 430.52 — this higher multiple intentionally accommodates motor starting inrush without nuisance tripping. Overload protection is set at 125% of FLC for motors with a service factor of 1.15 or greater, per 430.32(A)(1).

Loomi · NEC exam prep

Practice the NEC questions behind this.

Loomi turns these calcs into 9,000+ timed, NEC-referenced exam questions, with spaced repetition that hammers your weak spots. Reserve your founders' seat before launch.

Join the waitlist