Free NEC practice test · Article 450

Transformers practice questions

A free NEC Article 450 practice test for the journeyman exam: 22 questions on Transformers and Transformer Vaults (Including Secondary Ties), each with the answer and the why behind it.

22 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 22 journeyman-exam practice questions cover NEC Article 450 across 22 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Overcurrent protection for autotransformers ≤1000V

NEC 450.4(A)

Protect each ungrounded input conductor at 125% of rated full-load input current (167% if under 9 A), and never put a device in the shunt winding between Points A and B.

Q1 NEC 450.4(A)

Per 450.4(A), where must the individual overcurrent device for a 1000-volt-or-less autotransformer be installed?

  1. A In series with the shunt winding between Points A and B
  2. B In series with each ungrounded input conductor
  3. C In series with each ungrounded output conductor only
  4. D In the grounded conductor feeding the autotransformer
Show answer & explanation

Correct: B — In series with each ungrounded input conductor

450.4(A) requires the overcurrent device in series with each ungrounded input conductor. It explicitly forbids placing a device in the shunt winding between Points A and B, and grounded conductors are not overcurrent-protected this way.

Grounding autotransformer creating a 3-phase 4-wire system

NEC 450.5(A)

A grounding autotransformer that derives a 4-wire system from a 3-wire ungrounded source must trip the main at 125% load, trip on 50% current unbalance, and have a neutral rating that covers the worst-case unbalanced load.

Q2 NEC 450.5(A)

Under 450.5(A)(2), at what load level must the overcurrent sensing device cause the main switch or common-trip protection to open?

  1. A At or above 80 percent of the autotransformer's continuous current rating
  2. B At or above 100 percent of the autotransformer's continuous rating
  3. C At or above 125 percent of the autotransformer's continuous current per-phase or neutral rating
  4. D At or above 150 percent of the autotransformer's continuous current rating
Show answer & explanation

Correct: C — At or above 125 percent of the autotransformer's continuous current per-phase or neutral rating

450.5(A)(2) sets the trip threshold at 125 percent of the autotransformer's continuous current per-phase or neutral rating. 100 percent, 150 percent, and 80 percent are all plausible-sounding thresholds borrowed from other continuous-load or conductor-sizing rules, but they are not the value specified here.

Oil-insulated transformers indoors: vault construction and size exceptions

NEC 450.26

Indoor oil-insulated transformers need a fire-rated vault unless they qualify for a small-kVA or special-use exception in 450.26.

Q3 NEC 450.26

An indoor oil-insulated transformer rated 480 volts is installed in a section of a building classified as combustible. What is the maximum total capacity permitted at that location without a vault?

  1. A 112½ kVA
  2. B 75 kVA
  3. C 10 kVA
  4. D 150 kVA
Show answer & explanation

Correct: C — 10 kVA

Per 450.26, at 1000 volts or less, a vault is not required if suitable fire-prevention arrangements are made and the total capacity does not exceed 10 kVA where the surrounding construction is combustible. The 75 kVA figure applies only where the surrounding structure is fire-resistant construction, and 112½ kVA is the threshold for using thinner reinforced-concrete vault walls, not a no-vault allowance.

Overcurrent protection sizing for tie conductors by load location

NEC 450.6(A)

Where tie conductors skip normal Article 240 overcurrent protection, the required ampacity depends entirely on whether loads tap the tie mid-run or only sit at the transformer ends.

Q4 NEC 450.6(A)

A secondary tie has loads connected only at the transformer supply points at each end, and the installer wants to omit standard Article 240 overcurrent protection. What must the tie's ampacity be at minimum?

  1. A 67% of the rated secondary current of the highest rated transformer
  2. B 100% of the rated secondary current of the highest rated transformer
  3. C 133% of the rated secondary current of the highest rated transformer
  4. D 50% of the rated secondary current of the highest rated transformer
Show answer & explanation

Correct: A — 67% of the rated secondary current of the highest rated transformer

Per 450.6(A)(1), when all loads sit at the transformer supply points and standard overcurrent protection isn't used, tie ampacity must be at least 67% of the highest-rated transformer's secondary current. The 100% figure applies instead when loads tap the tie between supply points (450.6(A)(2)), and 133% applies only to non-interconnected paralleled conductors (450.6(A)(4)(b)).

Dry-type transformer indoor clearance/room rules by kVA size

NEC 450.21

Indoor dry-type transformers 112½ kVA or less need 12 in. from combustibles (or a barrier); above 112½ kVA they need a 1-hour fire-rated room unless high-temperature insulation and enclosure or clearance rules let them skip it.

Q5 NEC 450.21

A 75 kVA dry-type transformer is installed indoors near combustible framing, with no barrier. What does 450.21(A) require?

  1. A 6 ft horizontal and 12 ft vertical separation from the combustible material
  2. B Installation in a 1-hour fire-rated transformer room
  3. C No separation required, since it is rated 112½ kVA or less
  4. D At least 300 mm (12 in.) separation from the combustible material
Show answer & explanation

Correct: D — At least 300 mm (12 in.) separation from the combustible material

Under 450.21(A), transformers rated 112½ kVA or less need only 300 mm (12 in.) separation from combustible material unless a fire-resistant, heat-insulated barrier is used instead. The 1-hour room and the 6 ft/12 ft clearance option belong to 450.21(B) for units over 112½ kVA, and skipping separation entirely only applies to enclosed units rated 1000 V or less.

Grounding autotransformers: purpose and current ratings

NEC 450.5

A zigzag or T-connected grounding autotransformer manufactures a neutral point on a 3-phase, 3-wire system, and its phase current always runs one-third of the neutral current.

Q6 NEC 450.5

Where is a zigzag-connected grounding transformer prohibited from being installed per 450.5?

  1. A On the line side of the service disconnecting means
  2. B On the load side of an existing system grounding connection
  3. C In any outdoor location subject to weather
  4. D Anywhere within a healthcare facility's essential electrical system
Show answer & explanation

Correct: B — On the load side of an existing system grounding connection

450.5 specifically prohibits installing a zigzag-connected transformer on the load side of any system grounding connection, including those made under 250.24(C), 250.30(A)(1), or 250.32(B), Exception No. 1. Line-side service location, outdoor weather exposure, and healthcare essential systems are not restrictions this section imposes.

Grounding autotransformer providing ground-fault current reference

NEC 450.5(B)

A grounding autotransformer that manufactures ground-fault current on a 3-phase, 3-wire ungrounded system must be rated for that fault current and protected so all ungrounded conductors open together.

Q7 NEC 450.5(B)

A grounding autotransformer is installed to supply a ground-fault current reference on a 3-phase, 3-wire ungrounded system. What is required regarding its neutral-current rating?

  1. A It must have a continuous neutral-current rating not less than the specified ground-fault current
  2. B It must have a short-time rating equal to the interrupting rating of the main overcurrent device
  3. C It must have a continuous neutral-current rating exactly equal to 125% of the system's full-load current
  4. D It must have a neutral-current rating of at least 42% of the per-phase continuous rating
Show answer & explanation

Correct: A — It must have a continuous neutral-current rating not less than the specified ground-fault current

450.5(B)(1) requires the autotransformer's continuous neutral-current rating to be not less than the specified ground-fault current. The 125% figure and the 42% figure both relate to overcurrent protection sizing under 450.5(B)(2)(b), not to the transformer's neutral-current rating itself.

Less-flammable liquid-insulated transformers indoors

NEC 450.23(A)

A less-flammable liquid transformer (fire point ≥300°C) can go indoors under any one of three paths: strict Type I/II building conditions, fire suppression plus confinement, or full 450.26 compliance.

Q8 NEC 450.23(A)

A transformer insulated with a listed less-flammable liquid is being installed indoors in a Type I building rated at 34,500 volts. Combustible materials are stored nearby and no liquid confinement area exists. Which requirement of 450.23(A)(1) is violated?

  1. A The fire point of the liquid is too low for indoor use
  2. B The transformer voltage rating exceeds the allowed limit
  3. C No combustible materials may be stored and a liquid confinement area must be provided
  4. D Type I buildings are not permitted to house less-flammable liquid transformers
Show answer & explanation

Correct: C — No combustible materials may be stored and a liquid confinement area must be provided

450.23(A)(1) requires that no combustible materials be stored and that a liquid confinement area be provided, in addition to the 35,000-volt cap. The scenario's voltage (34,500 V) is within the limit, and Type I buildings are explicitly permitted — the failure is the stored combustibles and missing confinement area.

Nonflammable fluid-insulated transformer requirements

NEC 450.24

Nonflammable-fluid transformers can go indoors or outdoors, but indoor units over 35,000 volts need a vault, and all indoor units need liquid confinement plus a pressure-relief vent.

Q9 NEC 450.24

A nonflammable fluid-insulated transformer rated 25,000 volts is installed indoors. Per 450.24, what is required?

  1. A A 1-hour fire-rated enclosure
  2. B Installation in a vault
  3. C A liquid confinement area and a pressure-relief vent
  4. D No special provisions since the fluid is nonflammable
Show answer & explanation

Correct: C — A liquid confinement area and a pressure-relief vent

450.24 requires every indoor nonflammable fluid-insulated transformer to have a liquid confinement area and a pressure-relief vent, regardless of voltage. A vault is only required indoors above 35,000 volts, so this 25,000-volt unit doesn't need one. Fire-rated enclosures aren't the 450.24 requirement, and the nonflammable rating doesn't eliminate the confinement/venting requirement.

Accessibility requirements and exceptions for transformers

NEC 450.13

Transformers must be readily accessible unless they're a dry-type, 1000 V or less, installed either in the open or in a qualifying hollow space.

Q10 NEC 450.13 Code lookup

A dry-type transformer rated 480V, 45 kVA is installed in a hollow space above a suspended ceiling that is not permanently closed in by the building structure. The installer wants to confirm which section permits omitting ready accessibility for this installation, provided ventilation and combustible-separation requirements are met. Which section applies?

  1. A 450.21
  2. B 450.9
  3. C 450.13(A)
  4. D 450.13(B)
Show answer & explanation

Correct: D — 450.13(B)

450.13(B) is the specific exception allowing dry-type transformers 1000V or less and not exceeding 50 kVA to be installed in hollow spaces without being readily accessible, provided 450.9 ventilation and 450.21(A) separation are met. 450.13(A) covers open wall/column mounting, not hollow spaces, and 450.9 only addresses ventilation itself, not the accessibility exception.

Grounding and bonding of transformer enclosures and metal parts

NEC 450.10

Every grounding and bonding conductor lands on a dedicated terminal bar bonded to the enclosure, and any exposed metal near the transformer — fences, guards, enclosures — gets grounded like any other electrical equipment.

Q11 NEC 450.10

A dry-type transformer installation uses separate equipment grounding conductors and supply-side bonding jumpers. Per 450.10(A), where must these connect?

  1. A A terminal bar secured inside the enclosure and bonded to the enclosure per 250.12
  2. B The neutral bus bar shared with the secondary conductors
  3. C Directly to the core lamination screws
  4. D A terminal bar mounted on the ventilated louvers for accessibility
Show answer & explanation

Correct: A — A terminal bar secured inside the enclosure and bonded to the enclosure per 250.12

450.10(A) requires a terminal bar secured inside the enclosure for all grounding and bonding conductor connections, bonded to the enclosure per 250.12. Mounting it on the vented louvers is specifically prohibited, and landing conductors on core screws or the neutral bus isn't the specified method.

Guarding transformers from damage and contact

NEC 450.8

Transformers need physical protection from damage, enclosures that keep out objects and hands, and voltage markings wherever live parts are exposed.

Q12 NEC 450.8

Under what condition may a switch rated 1000 volts or less be installed inside a transformer enclosure?

  1. A It is rated for outdoor use and mounted at least 8 ft above grade
  2. B It is bonded to the transformer core and labeled with a warning sign
  3. C It serves any branch circuit in the building and is locked at all times
  4. D It serves only equipment within that transformer enclosure and is accessible to qualified persons only
Show answer & explanation

Correct: D — It serves only equipment within that transformer enclosure and is accessible to qualified persons only

450.8(C) permits switches or equipment operating at 1000 V nominal or less inside a transformer enclosure only if they serve equipment within that same enclosure and are accessible to qualified persons only. Serving building-wide circuits, height above grade, and bonding/labeling alone don't satisfy the qualified-persons-only condition in 450.8(C).

Overcurrent protection for transformers 1000 volts or less

NEC 450.3(B)

Size primary (and secondary, if required) overcurrent protection off Table 450.3(B) unless the transformer is a motor-control circuit transformer covered under 430.72(C).

Q13 NEC 450.3(B)

A 480Y/277V dry-type transformer is installed as general building power, not tied to any motor control circuit. Which rule sets the maximum overcurrent protection rating?

  1. A The motor-control transformer exception in 450.3(B)
  2. B Table 450.3(A)
  3. C Table 450.3(B)
  4. D 430.72(C)(1) through (C)(5)
Show answer & explanation

Correct: C — Table 450.3(B)

Per 450.3(B), general-purpose transformers rated 1000 volts or less are protected in accordance with Table 450.3(B). The 430.72(C) path and the motor-control exception only apply when the transformer is installed as a motor control circuit transformer, which this one is not. Table 450.3(A) applies to transformers over 1000 volts, not this case.

Transformer Overcurrent Protection (NEC 450.3(B))

NEC 450.3

For a transformer 1000 V or less with primary-only protection, the primary OCPD is 125% of the rated primary current (Table 450.3(B), for currents ≥9 A), rounded up to the next standard size.

Q14 NEC 450.3

A 45 kVA, three-phase transformer has a 480-volt primary and primary-only overcurrent protection. What is the maximum standard primary OCPD per NEC Table 450.3(B)?

  1. A 67.66 A
  2. B 60 A
  3. C 100 A
  4. D 70 A
Show answer & explanation

Correct: D — 70 A

Primary FLA = (45 × 1000) ÷ (480 × √3) = 54.1 A. Being ≥9 A with primary-only protection, Table 450.3(B) allows 125%: 54.1 × 1.25 = 67.7 A, rounded up to the next standard size = 70 A. Distractors skip the 125%, use 167%, or don't round to a standard size.

Fire-resistance requirements for vault walls, roofs, and floors

NEC 450.42

Transformer vault walls, roofs, and floors need 3-hour fire resistance, dropping to 1-hour only if the transformer has automatic fire suppression.

Q15 NEC 450.42

What is the minimum fire resistance rating required for the walls and roof of a transformer vault under standard conditions?

  1. A 2 hours
  2. B 3 hours
  3. C 4 hours
  4. D 1 hour
Show answer & explanation

Correct: B — 3 hours

Per 450.42, vault walls and roofs must have a minimum fire resistance of 3 hours. The 1-hour rating is only allowed as a reduction when the transformer is protected by automatic sprinkler, water spray, CO2, or halon — not the standard baseline.

Vault door fire rating and oil-containment sills

NEC 450.43(A)

Vault doors need a 3-hour fire rating (1-hour if the transformer has automatic fire suppression), and every vault needs a sill at least 4 inches high to contain oil.

Q16 NEC 450.43(A)

A transformer vault has an interior doorway with no automatic fire suppression inside the vault. What is the minimum required fire rating for that door?

  1. A 4 hours
  2. B 2 hours
  3. C 3 hours
  4. D 1 hour
Show answer & explanation

Correct: C — 3 hours

Per 450.43(A), an interior vault doorway needs a tight-fitting door with a minimum 3-hour fire rating. The 1-hour option only applies where the transformers are protected by automatic sprinkler, water spray, CO2, or halon suppression — not the baseline case described here.

Askarel-insulated transformers installed indoors

NEC 450.25

Indoor askarel transformers over 25 kVA need a pressure-relief vent, poorly ventilated spaces need gas venting to outside, and over 35,000 volts requires a vault.

Q17 NEC 450.25

An askarel-insulated transformer rated 30 kVA is installed indoors in a poorly ventilated room. Per 450.25, what is required?

  1. A A pressure-relief vent, plus a means to absorb arcing gases or a vent connected to a chimney or flue to outside
  2. B Installation in a vault, since the room is poorly ventilated
  3. C A pressure-relief vent only, since ventilation doesn't matter below 35,000 volts
  4. D No special requirements, since askarel is fire-resistant
Show answer & explanation

Correct: A — A pressure-relief vent, plus a means to absorb arcing gases or a vent connected to a chimney or flue to outside

450.25 requires a pressure-relief vent for indoor askarel transformers over 25 kVA, and in poorly ventilated locations also requires either a means to absorb gases from arcing or a vent connected to a chimney or flue carrying gases outside. The vault requirement only applies above 35,000 volts, not due to poor ventilation, and askarel's fire resistance doesn't eliminate the venting requirement.

Using a transformer field-connected as an autotransformer

NEC 450.4(B)

A transformer wired in the field to act as an autotransformer must be identified for use at that elevated voltage.

Q18 NEC 450.4(B)

An electrician wants to reconnect a standard two-winding transformer in the field so it functions as an autotransformer at a higher output voltage. Per 450.4(B), what must be true of the transformer?

  1. A It must be identified for use at the elevated voltage
  2. B It must be derated to its original nameplate voltage before reconnection
  3. C It must be relabeled with a new overcurrent protection rating only
  4. D It must be listed for use only as a two-winding isolation transformer
Show answer & explanation

Correct: A — It must be identified for use at the elevated voltage

450.4(B) requires that a transformer field-connected as an autotransformer be identified for use at the elevated voltage that connection creates. Simply changing an overcurrent rating doesn't address the insulation and voltage-stress concern, and derating to the original nameplate voltage would defeat the purpose of the autotransformer connection. Isolation-transformer-only listings don't satisfy this identification requirement.

Dry-type transformers installed outdoors

NEC 450.22

Outdoor dry-type transformers need a weatherproof enclosure, and units over 112½ kVA need 12 in. of combustible clearance unless insulated Class 155+ and fully enclosed.

Q19 NEC 450.22 Code lookup

A dry-type transformer rated 30 kVA with a Class 155 insulation system is being mounted outdoors on the exterior wall of a building, 8 in. from combustible siding. Which section governs whether this clearance is acceptable?

  1. A 450.22
  2. B 450.9
  3. C 450.21(A)
  4. D 450.27
Show answer & explanation

Correct: A — 450.22

450.22 sets the outdoor dry-type transformer rules, including the 300 mm (12 in.) clearance to combustibles for units over 112 1/2 kVA and the Class 155-or-higher insulation exception; 450.21(A) covers indoor units not over 112 1/2 kVA, and 450.27 governs oil-insulated outdoor transformers, not dry-type.

Less-flammable liquid-insulated transformers outdoors

NEC 450.23(B)

Outdoor less-flammable liquid transformers on or near buildings must follow either the liquid's listing restrictions on Type I/II buildings or the added safeguards in 450.27.

Q20 NEC 450.23(B)

A less-flammable liquid-filled transformer is to be mounted on the roof of a Type II building. Per 450.23(B), what must the installation comply with?

  1. A All restrictions provided in the listing of the liquid
  2. B Only local fire code, since NEC does not address Type II buildings
  3. C The vault construction requirements in 450.42
  4. D The indoor dry-type transformer clearance rules
Show answer & explanation

Correct: A — All restrictions provided in the listing of the liquid

450.23(B)(1) requires that installations on Type I and Type II buildings comply with all restrictions in the liquid's listing, such as maximum tank pressure, pressure relief valves, fuse types, and overcurrent protection sizing. Vault construction rules and dry-type clearance rules belong to other transformer installation methods, and NEC does address Type I/II buildings directly in this section.

Oil-insulated transformers outdoors: fire safeguards near buildings

NEC 450.27

An outdoor oil-filled transformer near a building must be protected by space separation, fire-resistant barriers, automatic suppression, or an oil-confining enclosure — matched to the hazard.

Q21 NEC 450.27

An oil-insulated transformer is installed on a roof, adjacent to combustible building material, in a way that presents a fire hazard. Per 450.27, which approach satisfies the safeguard requirement?

  1. A No safeguard is required as long as the transformer tank is sealed
  2. B An automatic fire suppression system only, regardless of hazard level
  3. C A fire-resistant barrier only, since it is the sole method recognized for rooftop installations
  4. D Any one or more of: space separation, fire-resistant barriers, automatic fire suppression, or an oil-confining enclosure, matched to the degree of hazard
Show answer & explanation

Correct: D — Any one or more of: space separation, fire-resistant barriers, automatic fire suppression, or an oil-confining enclosure, matched to the degree of hazard

450.27 lists space separations, fire-resistant barriers, automatic fire suppression systems, and oil-confining enclosures as acceptable safeguards, applied according to the degree of hazard — not a single mandatory method. A sealed tank does not remove the requirement since the rule addresses fire originating from a ruptured tank.

Secondary ties: definition and scope

NEC 450.6

A secondary tie is a circuit of 1000 volts or less that connects two separate power sources together — not the conductors joining a transformer bank's own secondaries.

Q22 NEC 450.6

Per Article 450, what distinguishes a secondary tie from other transformer secondary conductors?

  1. A A secondary tie is any conductor inside a transformer enclosure
  2. B A secondary tie must always use exactly one conductor per phase
  3. C A secondary tie operates at more than 1000 volts between phases
  4. D A secondary tie connects two separate power sources or supply points
Show answer & explanation

Correct: D — A secondary tie connects two separate power sources or supply points

Per 450.6, a secondary tie is a circuit at 1000 volts or less between phases that connects two power sources or power supply points, such as the secondaries of two transformers. It is not limited to one conductor per phase — one or more conductors per phase or neutral are permitted. The 1000 V figure is a ceiling ('or less'), not a minimum.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access