Free NEC practice test · Article 680

Swimming Pools and Fountains practice questions

A free NEC Article 680 practice test for the journeyman exam: 59 questions on Swimming Pools, Fountains, and Similar Installations, each with the answer and the why behind it.

59 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 59 journeyman-exam practice questions cover NEC Article 680 across 59 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

GFCI vs SPGFCI: When Each Applies by Voltage

NEC 680.5

Pick the device by voltage to ground: 150 volts or less uses a Class A GFCI, and above 150 volts (up to 480 volts phase-to-phase) needs SPGFCI protection at 20 mA or less.

Q1 NEC 680.5

A branch circuit supplying pool equipment receptacles is 120 volts to ground and rated 50 amperes. Which device satisfies 680.5(B)?

  1. A No ground-fault protection, because the circuit exceeds 40 amperes
  2. B A Class A GFCI
  3. C A ground-fault protection of equipment (GFPE) device
  4. D An SPGFCI rated for 20 mA
Show answer & explanation

Correct: B — A Class A GFCI

680.5(B) requires a Class A GFCI for receptacles and outlets on branch circuits 150 volts or less to ground and 60 amperes or less. The SPGFCI option only applies above 150 volts to ground per 680.5(C), and there is no 40-ampere cutoff in this rule.

Bonding conductive pool shells (rebar / copper grid)

NEC 680.26(B)(1)

Conductive pool shells need a bonded conductive path — tied rebar if exposed, or an 8 AWG copper grid if the rebar is encapsulated.

Q2 NEC 680.26(B)(1)

A pool has a cast-in-place concrete shell with painted block coping. Under 680.26(B)(1), how must this shell be classified?

  1. A Nonconductive as long as the surface is painted
  2. B Conductive only if it uses unencapsulated rebar
  3. C Conductive, due to water permeability and porosity
  4. D Nonconductive, like a fiberglass composite shell
Show answer & explanation

Correct: C — Conductive, due to water permeability and porosity

680.26(B)(1) explicitly treats cast-in-place concrete, sprayed concrete, and painted or plastered concrete block as conductive materials because they are water-permeable and porous. Classification doesn't depend on whether the rebar is encapsulated — that only determines which bonding method (tie wire vs. copper grid) applies. Painting the surface doesn't change the classification; only vinyl liners and fiberglass composite shells are considered nonconductive.

Bonding conductor material and sizing (8 AWG rule)

NEC 680.26(B)

Pool bonding uses solid copper 8 AWG or larger (or brass/corrosion-resistant rigid metal conduit), and that bonding grid never has to tie back to panelboards, service equipment, or grounding electrodes.

Q3 NEC 680.26(B)

Under 680.26(B), which conductor is acceptable for bonding the parts listed in 680.26(B)(1) through (B)(7)?

  1. A 8 AWG solid aluminum, insulated
  2. B 8 AWG solid copper, bare
  3. C 10 AWG solid copper, insulated
  4. D 8 AWG stranded copper, covered
Show answer & explanation

Correct: B — 8 AWG solid copper, bare

680.26(B) requires solid copper conductor, insulated, covered, or bare, not smaller than 8 AWG. The 8 AWG bare solid copper option satisfies all three requirements. 10 AWG is undersized, stranded copper doesn't meet the 'solid' requirement, and aluminum is not the specified material.

Bonding electrical equipment near the pool

NEC 680.26(B)(6)

Bond metal parts of pool equipment and nearby electrical equipment to eliminate voltage gradients — but listed double-insulated equipment is never bonded.

Q4 NEC 680.26(B)(6)

A double-insulated water pump motor is installed at a pool per 680.26(B)(6). What is required instead of bonding the motor's metal parts?

  1. A A solid 8 AWG copper conductor extended from the pool equipotential bonding means to an accessible point near the pump motor
  2. B Bonding the motor frame directly to the nearest rebar in the pool shell
  3. C No additional provision, since double-insulated equipment is fully exempt from all pool bonding requirements
  4. D A dedicated GFCI breaker for the pump circuit only
Show answer & explanation

Correct: A — A solid 8 AWG copper conductor extended from the pool equipotential bonding means to an accessible point near the pump motor

680.26(B)(6)(a) requires a solid 8 AWG copper conductor run from the equipotential bonding means to an accessible point near the pump, sized for a future non-double-insulated replacement motor. A dedicated GFCI breaker and direct bonding to rebar aren't what the rule specifies, and the exemption from bonding doesn't mean no provision at all — the spare conductor is still mandatory.

Fountain grounding and bonding requirements

NEC 680.54

Everything electrical within 5 ft of a fountain must be grounded, and all metal parts near it must be bonded with at least an 8 AWG solid copper conductor.

Q5 NEC 680.54

Which piece of equipment is exempt from the equipment grounding requirement for a fountain?

  1. A A listed low-voltage luminaire not requiring grounding
  2. B A non-service panelboard that supplies fountain equipment
  3. C Electrical equipment located within 1.5 m of the inside wall
  4. D Electrical equipment associated with the recirculating system
Show answer & explanation

Correct: A — A listed low-voltage luminaire not requiring grounding

680.54(A) requires grounding for equipment within 5 ft of the fountain, recirculating-system equipment, and non-service panelboards feeding fountain gear — except listed low-voltage luminaires not requiring grounding, which are specifically exempted.

Junction boxes and enclosures for fountains, above and below water

NEC 680.52

Dry-location fountain boxes just follow the general pool rules in 680.24, but anything installed underwater needs listed submersion-rated construction, corrosion-resistant metal, potting compound, and bonded corrosion-resistant support.

Q6 NEC 680.52 Code lookup

An in-ground fountain has an underwater junction box that receives conduit from a nonmetallic raceway system and is supported only by that conduit. Which section specifies the construction and support requirements for this underwater enclosure?

  1. A 680.51(E)
  2. B 680.54(B)
  3. C 680.52(A)
  4. D 680.52(B)(2)
Show answer & explanation

Correct: D — 680.52(B)(2)

680.52(B)(2) covers installation requirements for underwater enclosures, including potting compound and support/fastener material rules when fed by nonmetallic conduit. 680.52(A) only addresses non-underwater enclosures (which defer to 680.24), and 680.51(E) concerns wiring for submersible equipment, not junction box support.

Electric signs at fountains: GFCI, placement, disconnect, bonding

NEC 680.57

Any electric sign in or near a fountain needs GFCI protection, a local disconnect, proper bonding, and enough setback from the water — fixed signs need 5 ft, portable signs can't come any closer than 5 ft either.

Q7 NEC 680.57

An electrician is installing an electric sign 8 ft from the edge of a decorative fountain. Which requirement applies?

  1. A The sign is within the 10 ft scope of 680.57 and must meet its GFCI, location, disconnect, and bonding requirements
  2. B Only the GFCI requirement applies since the sign is more than 5 ft away
  3. C None of 680.57 applies because the sign is outside the fountain itself
  4. D Only the bonding requirement applies since the sign is not submerged
Show answer & explanation

Correct: A — The sign is within the 10 ft scope of 680.57 and must meet its GFCI, location, disconnect, and bonding requirements

Per 680.57(A), the section covers signs installed within a fountain or within 3.0 m (10 ft) of the fountain edge. At 8 ft, the sign falls inside that 10 ft scope, so all of 680.57's requirements (GFCI, location, disconnect, bonding) apply — not just one piece of it.

Submersible luminaires and pumps: GFCI, voltage, and lens rules

NEC 680.51

Submersible fountain equipment must be GFCI protected, luminaires capped at 150V and pumps at 300V, with lenses kept below water or guarded.

Q8 NEC 680.51

Under what condition can a submersible fountain pump be installed WITHOUT GFCI protection?

  1. A When the pump operates at 300 volts or less between conductors
  2. B When it is listed for operation at the low-voltage contact limit or less and supplied by a transformer or power supply complying with 680.23(A)(2)
  3. C When the pump is installed in a fountain with no wading area
  4. D When the pump is bonded to the equipotential bonding grid
Show answer & explanation

Correct: B — When it is listed for operation at the low-voltage contact limit or less and supplied by a transformer or power supply complying with 680.23(A)(2)

680.51(A) only excuses GFCI protection for equipment listed for low-voltage contact limit or less supplied by a compliant transformer or power supply per 680.23(A)(2). Operating at 300 volts or less is simply the general voltage cap for submersible equipment under 680.51(B), not a GFCI exemption, and bonding addresses a different hazard.

Portable pumps and heaters for immersion pools

NEC 680.35(B)

Cord-connected pumps and heaters used with storable/portable immersion pools each need pool/spa listing, and heaters add rating limits, a 6–15 ft cord, and GFCI protection.

Q9 NEC 680.35(B)

A cord-and-plug-connected heater is used with a portable immersion pool. Under 680.35(C), when is GFCI protection required for this heater?

  1. A When the supply cord is longer than 15 ft
  2. B When the heater is rated above 250 volts, single phase
  3. C When the heater is supplied by a branch circuit rated 150 volts or less to ground
  4. D Only when it is a circulation heater rather than a plain water heater
Show answer & explanation

Correct: C — When the heater is supplied by a branch circuit rated 150 volts or less to ground

680.35(C) requires GFCI protection for portable heaters supplied by branch circuits rated 150 volts or less to ground. There's no GFCI trigger tied to heater voltage rating or cord length in this section, and circulation heaters are explicitly included alongside other portable heaters, not singled out.

Box/enclosure protection, terminals, strain relief, grounding

NEC 680.24(F)

Pool light junction boxes and enclosures need physical protection from foot traffic, one extra grounding terminal per conduit entry, strain relief on the cord, and a direct grounding path back to the panelboard enclosure.

Q10 NEC 680.24(F)

A junction box connects via conduit to the forming shell of a no-niche luminaire, with two conduit entries into the box. Per 680.24(D), what is the minimum number of grounding terminals the box must have?

  1. A One
  2. B Three
  3. C Two
  4. D Four
Show answer & explanation

Correct: B — Three

680.24(D) requires no fewer than one more grounding terminal than the number of conduit entries. With two conduit entries, the box needs at least three grounding terminals. Matching the terminal count to the conduit entries (two) doesn't provide the required extra terminal.

Luminaire and paddle-fan height clearances above pools

NEC 680.22(B)(1)

Outdoor pool luminaires and paddle fans need 12 ft above max water level within 5 ft of the pool walls, unless GFCI protection and totally enclosed fixtures drop that to 7 ft 6 in. indoors.

Q11 NEC 680.22(B)(1)

A new luminaire is being installed directly above an outdoor pool. What is the minimum required height above the maximum water level?

  1. A 12 ft, with no GFCI-based reduction available outdoors
  2. B 7 ft 6 in., since GFCI protection is standard on pool circuits
  3. C 10 ft, per the general lighting outlet clearance
  4. D 5 ft, matching the existing-installation allowance
Show answer & explanation

Correct: A — 12 ft, with no GFCI-based reduction available outdoors

Per 680.22(B)(1), new outdoor installations above the pool or within 5 ft of its inside walls require 12 ft of clearance above max water level. The 7 ft 6 in. GFCI-based reduction in 680.22(B)(2) only applies to indoor installations with totally enclosed luminaires or qualifying paddle fans, and the 5 ft option in 680.22(B)(3) is limited to existing installations.

GFCI protection for pool pump motors, new & replacement

NEC 680.21(C)

Every outlet feeding a pool motor at 150V-to-ground/60A or less needs Class A GFCI protection, placed on the line side of any drive, and that rule follows the motor through replacement or repair.

Q12 NEC 680.21(C)

An outlet supplies a single-phase pool pump motor on a branch circuit rated 120 volts to ground, 20 amperes. What protection does 680.21(C) require?

  1. A Class A ground-fault circuit-interrupter protection
  2. B GFCI protection only if the motor is 3-phase
  3. C No GFCI protection is required because the circuit is under 30 amperes
  4. D AFCI protection only
Show answer & explanation

Correct: A — Class A ground-fault circuit-interrupter protection

Per 680.21(C), outlets supplying pool motors on branch circuits rated 150 volts or less to ground and 60 amperes or less — single- or 3-phase — require Class A GFCI protection. There's no current-rating carve-out below 60 A, and the single-phase vs. 3-phase distinction doesn't change the requirement.

Receptacle setback distances around a pool

NEC 680.22(A)(1)

Every receptacle near a permanent pool sits at least 6 ft from the pool's inside wall, measured along the path a cord would actually travel.

Q13 NEC 680.22(A)(1)

A required 125-volt, 20-ampere general-purpose receptacle is being located near a permanently installed pool. Which placement satisfies 680.22(A)(1)?

  1. A 6 ft from the inside pool wall but 8 ft above grade
  2. B 12 ft from the inside pool wall
  3. C 25 ft from the inside pool wall
  4. D 5 ft from the inside pool wall
Show answer & explanation

Correct: B — 12 ft from the inside pool wall

680.22(A)(1) requires the receptacle to be not less than 6 ft and not more than 20 ft from the pool's inside wall, and not more than 6 ft 6 in. above grade. 12 ft satisfies both the minimum and maximum. 5 ft is too close, 25 ft exceeds the 20 ft cap, and 8 ft above grade exceeds the height limit even though the horizontal distance is fine.

What to bond and how to bond it at spas/hot tubs

NEC 680.43(D)

Bond every metal fitting, pump part, and metal surface or raceway within 5 ft of a spa unless a permanent barrier separates it, using bonded piping, a common frame, or an 8 AWG solid copper jumper.

Q14 NEC 680.43(D)

A metal towel bar is mounted 3 ft from the inside wall of a hot tub. It is not connected to any metallic piping. Under 680.43(D), what is required?

  1. A It is exempt because it is a small conductive surface not likely to become energized and not connected to metallic piping
  2. B It must be bonded with an 8 AWG jumper regardless of connection to piping
  3. C It must be bonded because it is within the 5 ft zone
  4. D It must be bonded only if a permanent barrier is absent
Show answer & explanation

Correct: A — It is exempt because it is a small conductive surface not likely to become energized and not connected to metallic piping

680.43(D)(4) specifically exempts small conductive surfaces not likely to become energized, such as towel bars and mirror frames, from bonding when they are not connected to metallic piping — even though they sit inside the 5 ft zone. The other choices treat the towel bar like ordinary metal surfaces or raceways, which is the confusion this exception is meant to prevent.

Indoor spa and hot tub installation rules

NEC 680.43

Indoor spas and hot tubs use Chapter 3 wiring methods like other Article 680 equipment, but listed units rated 20 A or less may be cord-and-plug-connected.

Q15 NEC 680.43

A listed indoor hot tub package unit is rated 25 amperes. Under 680.43, how must it be connected?

  1. A By Chapter 3 wiring methods, since cord-and-plug connection is only permitted for units rated 20 A or less
  2. B By cord-and-plug connection, since indoor units are always permitted a flexible cord for maintenance access
  3. C By any wiring method, since amperage rating does not affect indoor connection requirements
  4. D By the flexible cord methods used for outdoor spa installations
Show answer & explanation

Correct: A — By Chapter 3 wiring methods, since cord-and-plug connection is only permitted for units rated 20 A or less

680.43 permits cord-and-plug connection only for listed spa/hot tub packaged units rated 20 amperes or less; above that, the unit must be connected using Chapter 3 wiring methods. The outdoor flexible cord provisions and an amperage-independent 'any method' reading don't reflect the 20 A cap in this section.

Luminaire, lighting outlet, and paddle fan clearance above spas

NEC 680.43(B)(1)

No GFCI means 12 ft minimum mounting height over a spa or hot tub; GFCI protection drops that to 7 ft 6 in., and certain damp-rated fixtures can go even lower.

Q16 NEC 680.43(B)(1)

A recessed luminaire is to be installed over a residential hot tub with no GFCI protection anywhere in the circuit. What is the minimum required mounting height above the maximum water level?

  1. A 12 ft
  2. B 7 ft 6 in.
  3. C 5 ft
  4. D 10 ft
Show answer & explanation

Correct: A — 12 ft

Per 680.43(B)(1)(a), without GFCI protection the mounting height must be not less than 12 ft (3.7 m). The 7 ft 6 in. height only applies when GFCI protection is provided, per 680.43(B)(1)(b).

Receptacle placement and GFCI protection near spas/hot tubs

NEC 680.43(A)

Every receptacle within 10 ft of a spa needs GFCI protection, but general-purpose receptacles must also sit at least 6 ft away.

Q17 NEC 680.43(A)

A contractor wants to install the required general-purpose 20-amp receptacle near a new hot tub. Where can it go?

  1. A 4 ft from the inside wall of the hot tub
  2. B Directly adjacent to the hot tub for convenient cord access
  3. C Anywhere, as long as it's GFCI protected
  4. D 8 ft from the inside wall of the hot tub
Show answer & explanation

Correct: D — 8 ft from the inside wall of the hot tub

680.43(A) requires the general-purpose receptacle to be not less than 6 ft and not more than 10 ft from the inside wall, so 8 ft satisfies both bounds. The 4-ft option violates the 6-ft minimum, and GFCI protection alone (or ignoring distance entirely) doesn't satisfy the placement rule.

Underground Wiring Near and Under Pools

NEC 680.11

Within 5 ft of a pool wall, only listed burial-rated wiring methods are allowed, and running wiring under the pool itself is banned except to feed pool equipment.

Q18 NEC 680.11

An electrician needs to route underground wiring 3 ft from the inside wall of an in-ground pool. Which of the following is a permitted wiring method under 680.11(A)?

  1. A Electrical metallic tubing (EMT)
  2. B Standard (non-burial-listed) liquidtight flexible metal conduit
  3. C Type MC cable not listed for burial use
  4. D Rigid polyvinyl chloride (PVC) conduit
Show answer & explanation

Correct: D — Rigid polyvinyl chloride (PVC) conduit

680.11(A) permits rigid PVC conduit for underground wiring within 5 ft of a pool. EMT isn't listed in the permitted methods, and both the liquidtight flexible metal conduit and MC cable must specifically be listed for direct burial use to qualify — unlisted versions don't meet the requirement.

Underwater luminaire shock-safety design basics

NEC 680.23(A)(1)

An underwater luminaire must be designed so no shock hazard exists even without a GFCI, but compliance is still only reached with a listed fixture plus a listed GFCI or low-voltage supply.

Q19 NEC 680.23(A)(1)

An underwater pool luminaire is properly installed without a GFCI. Per 680.23(A)(1), what must be true during normal use?

  1. A There must be no shock hazard under any likely combination of fault conditions
  2. B A shock hazard is acceptable as long as relamping is not being performed
  3. C The installation is automatically noncompliant regardless of design
  4. D The luminaire must be rewired to include an internal GFCI device
Show answer & explanation

Correct: A — There must be no shock hazard under any likely combination of fault conditions

680.23(A)(1) requires the luminaire's design itself to prevent any shock hazard under likely fault conditions during normal use, even absent a GFCI. This is a design-intent standard, not a statement that GFCI-less installations are automatically fine or automatically illegal, and it doesn't call for an internal GFCI device.

Transformers and power supplies for underwater luminaires

NEC 680.23(A)(2)

Underwater luminaire transformers must be pool-listed, isolate primary from secondary, and stay at or under 150 volts, with GFCI protection above the low-voltage contact limit.

Q20 NEC 680.23(A)(2)

Which design satisfies the isolation requirement for a transformer supplying an underwater luminaire?

  1. A A standard dry-type transformer with a grounded secondary conductor
  2. B A buck-boost transformer wired for step-down only
  3. C An isolated winding type transformer with an ungrounded secondary and a grounded metal barrier between windings
  4. D An autotransformer with a bonded neutral
Show answer & explanation

Correct: C — An isolated winding type transformer with an ungrounded secondary and a grounded metal barrier between windings

680.23(A)(2) requires either an isolated winding type transformer with an ungrounded secondary and a grounded metal barrier between primary and secondary windings, or an approved system of double insulation between the windings. An autotransformer doesn't isolate primary from secondary at all, and a standard dry-type transformer with a grounded secondary doesn't meet the ungrounded-secondary requirement, so neither qualifies. A buck-boost transformer wired for step-down likewise provides no isolation between windings.

Wet-niche forming shell and conduit wiring

NEC 680.23(B)(1)

Wet-niche luminaires mount in a corrosion-resistant forming shell fed by rigid metal, IMC, LFNC, or PVC conduit, with an 8 AWG copper bonding jumper required whenever nonmetallic conduit is used.

Q21 NEC 680.23(B)(1)

A wet-niche underwater luminaire forming shell is fed with rigid PVC conduit. What is required inside that conduit?

  1. A No bonding conductor, since PVC is nonconductive
  2. B A 12 AWG insulated copper equipment grounding conductor
  3. C A bare 6 AWG copper conductor sized per Table 250.66
  4. D An 8 AWG insulated solid or stranded copper bonding jumper
Show answer & explanation

Correct: D — An 8 AWG insulated solid or stranded copper bonding jumper

Per 680.23(B)(2)(b), nonmetallic conduit to a forming shell requires an 8 AWG insulated solid or stranded copper bonding jumper (unless a listed low-voltage system not requiring grounding is used) — not a standard equipment grounding conductor sized from Table 250.66, and not a bare conductor.

Wet-niche luminaire cord grounding and bonding

NEC 680.23(B)(3)

A wet-niche luminaire's cord needs its own integral copper EGC to a grounding terminal, potted terminations, and a tool-required locking bond to the forming shell.

Q22 NEC 680.23(B)(3)

A wet-niche luminaire is supplied by a flexible cord with 12 AWG copper supply conductors. What is the minimum acceptable size for the cord's equipment grounding conductor?

  1. A 10 AWG to allow for pool-water corrosion derating
  2. B 16 AWG regardless of supply conductor size
  3. C 12 AWG, matching the supply conductors
  4. D 18 AWG, since EGCs may run smaller than supply conductors
Show answer & explanation

Correct: C — 12 AWG, matching the supply conductors

Per 680.23(B)(3), the equipment grounding conductor shall not be smaller than the supply conductors and not smaller than 16 AWG. With 12 AWG supply conductors, the EGC must be at least 12 AWG — the 16 AWG floor only controls when supply conductors are smaller than that.

Bonding fixed metal parts (fences, piping, awnings) near pool

NEC 680.26(B)(7)

Fixed metal within 5 ft horizontally or 12 ft vertically of the pool must be bonded, unless a permanent barrier blocks contact.

Q23 NEC 680.26(B)(7)

A metal fence sits 4 ft from the inside wall of a pool, with no barrier separating it. What does 680.26(B)(7) require?

  1. A The fence only needs bonding if it is taller than 12 ft
  2. B The fence is exempt because fences are not listed as fixed metal parts
  3. C The fence needs bonding only if it is within 3 ft of the pool
  4. D The fence must be bonded because it is within the 5 ft horizontal zone
Show answer & explanation

Correct: D — The fence must be bonded because it is within the 5 ft horizontal zone

680.26(B)(7) requires bonding of fixed metal parts, explicitly including metal fences, located no more than 1.5 m (5 ft) horizontally from the pool's inside walls. At 4 ft, the fence is inside that zone, so it must be bonded unless a permanent barrier prevents contact.

Bonding misc. pool-structure metal, fittings & light shells

NEC 680.26(B)(5)

Nearly every metal part touching a pool must be bonded — reinforcing steel, light forming shells, and fittings — with only narrow, size-limited exceptions.

Q24 NEC 680.26(B)(5) Code lookup

A pool deck has a stainless-steel ladder escutcheon and a metal skimmer faceplate attached to the pool structure. Which section requires these metal fittings to be bonded?

  1. A 680.26(B)(3)
  2. B 680.26(B)(6)
  3. C 680.26(B)(5)
  4. D 680.26(B)(7)
Show answer & explanation

Correct: C — 680.26(B)(5)

680.26(B)(5) covers metal fittings within or attached to the pool structure, such as ladder escutcheons and skimmer faceplates. 680.26(B)(3) governs metallic components of the shell itself (e.g., reinforcing steel), and 680.26(B)(6)/(B)(7) address electrical equipment and fixed metal parts near the pool, not fittings on the structure.

Bonding pool water directly when no bonded parts touch it

NEC 680.26(C)

If no bonded pool part touches the water, install a corrosion-resistant conductive surface with at least 9 in.2 of water contact, bonded like any other 680.26(B) part.

Q25 NEC 680.26(C)

A vinyl-liner pool has no metal ladder, light, or fitting touching the water. What does 680.26(C) require in this case?

  1. A A GFCI-protected receptacle installed within reach of the pool
  2. B A corrosion-resistant conductive surface with at least 9 in.2 of water contact, bonded per 680.26(B)
  3. C A second equipotential bonding grid embedded beneath the pool shell
  4. D A double-insulated underwater luminaire so that bonding is not required
Show answer & explanation

Correct: B — A corrosion-resistant conductive surface with at least 9 in.2 of water contact, bonded per 680.26(B)

680.26(C) requires that where no bonded part touches the pool water, an approved corrosion-resistant conductive surface exposing at least 9 in.2 (5800 mm2) to the water be provided and bonded per 680.26(B). Adding another bonding grid, a nearby GFCI receptacle, or a double-insulated luminaire don't create the required electrical contact with the water itself.

Cord-and-Plug Connections for Fixed Pool Equipment

NEC 680.8

Fixed pool equipment can be cord-and-plug connected for easy service, but only within a 3 ft cord, a 12 AWG minimum grounding conductor, and a bonded metal frame.

Q26 NEC 680.8

A contractor wants to cord-and-plug connect a fixed pool pump on a permanently installed pool using a 5 ft flexible cord. Is this compliant with 680.8(A)?

  1. A No, because cord-and-plug connections are never permitted on permanently installed pools
  2. B No, because for other than storable pools the cord cannot exceed 900 mm (3 ft)
  3. C Yes, because 5 ft is within typical flexible cord lengths used elsewhere in the NEC
  4. D Yes, because 680.8(A) only limits cord length for storable pools
Show answer & explanation

Correct: B — No, because for other than storable pools the cord cannot exceed 900 mm (3 ft)

680.8(A) limits the flexible cord to 900 mm (3 ft) for other than storable pools — the opposite of the claim that the limit only applies to storable pools. A 5 ft cord exceeds that limit, and cord-and-plug connection itself is allowed under 680.8, just with this length restriction.

Wiring and Equipment in Corrosive Environments

NEC 680.14

Pool-area corrosive environments require conduit and equipment resistant to that corrosion — aluminum conduit and tubing are never allowed.

Q27 NEC 680.14

An electrician is selecting a raceway for a run across a pool deck, an area classified as a corrosive environment under 680.14. Which material is NOT permitted?

  1. A Rigid polyvinyl chloride conduit
  2. B Reinforced thermosetting resin conduit
  3. C Aluminum conduit
  4. D Rigid metal conduit
Show answer & explanation

Correct: C — Aluminum conduit

680.14(A) explicitly bans aluminum conduit and tubing in corrosive environments. Rigid PVC, rigid metal conduit, and RTRC are all named as suitable wiring methods in 680.14 and 680.14(A).

Deck-area heating equipment setbacks

NEC 680.27(C)(1)

Any comfort heater within 20 ft of a pool wall must clear a 5 ft horizontal no-go zone, and radiant heating cable can never be buried in a pool deck.

Q28 NEC 680.27(C)(1)

A contractor wants to install embedded radiant heating cable under the concrete deck surrounding a pool to keep the deck warm in winter. Per 680.27(C)(3), is this permitted?

  1. A Yes, if it is GFCI protected
  2. B No, radiant heating cable embedded in or below the deck is never permitted
  3. C Yes, if the cable is rated for wet locations
  4. D Yes, if it is installed more than 5 ft from the pool wall
Show answer & explanation

Correct: B — No, radiant heating cable embedded in or below the deck is never permitted

680.27(C)(3) prohibits radiant heating cables embedded in or below a pool deck outright — there is no wet-rating, distance, or GFCI-protection exception that makes it acceptable. The other options describe protections that apply to other equipment types under 680.27(C), not a path to permitting embedded deck cable.

Dry-niche luminaire construction and junction box

NEC 680.23(C)(1)

A dry-niche luminaire needs drainage and a grounding conductor per conduit entry, and its junction box — if used at all — skips the elevation rule when the luminaire is listed for that purpose.

Q29 NEC 680.23(C)(1)

Per 680.23(C)(1), what must a dry-niche luminaire's construction provide for at each conduit entry?

  1. A A low-water cutoff switch
  2. B A means for accommodating one equipment grounding conductor
  3. C A bonding jumper sized to the pool's perimeter surface
  4. D A double-insulated barrier rated for submersion
Show answer & explanation

Correct: B — A means for accommodating one equipment grounding conductor

680.23(C)(1) requires a dry-niche luminaire to have means for accommodating one equipment grounding conductor for each conduit entry, unless it's a listed low-voltage luminaire not requiring grounding. The other options are not construction requirements found in this section.

Electrically operated pool cover motors and GFCI

NEC 680.27(B)(1)

Pool cover motors need 5 ft of separation from the pool (or a barrier), below-grade motors must be totally enclosed, and the motor circuit needs GFCI protection unless it's a low-voltage listed system.

Q30 NEC 680.27(B)(1)

An electrically operated pool cover motor is installed 3 ft from the inside wall of the pool, with no wall, cover, or barrier separating it from the water. Which statement is correct?

  1. A This is permitted because 3 ft satisfies the minimum clearance for standard 120V motors
  2. B This is permitted as long as the motor is GFCI-protected, regardless of distance
  3. C This violates 680.27(B)(1) unless the motor is part of a listed low-voltage system fed by a compliant transformer or power supply
  4. D This is permitted only if the motor is installed below grade in a totally enclosed housing
Show answer & explanation

Correct: C — This violates 680.27(B)(1) unless the motor is part of a listed low-voltage system fed by a compliant transformer or power supply

680.27(B)(1) requires motors, controllers, and wiring to be at least 5 ft from the inside pool wall unless separated by a permanent barrier. The only exception that allows closer placement without a barrier is a listed system at or below the low-voltage contact limit, supplied by a listed transformer or power supply complying with 680.23(A)(2). GFCI protection and below-grade enclosure are separate requirements under 680.27(B)(2) and 680.27(B)(1) respectively, and neither substitutes for the clearance rule.

Equipment Rooms, Vaults, and Pits: Drainage and Receptacles

NEC 680.12

Pool equipment spaces need drainage that keeps water from pooling, plus GFCI protection on every receptacle inside — at least one dedicated GFCI receptacle is required in equipment rooms.

Q31 NEC 680.12

Which receptacle requirement applies specifically and only to a pool equipment room, not to a vault or pit?

  1. A At least one GFCI-protected 125-volt, 15- or 20-ampere receptacle on a general-purpose branch circuit
  2. B A minimum of two receptacles per room
  3. C Receptacles rated at least 30 amperes
  4. D GFCI protection on all receptacles rated 150 volts or less to ground
Show answer & explanation

Correct: A — At least one GFCI-protected 125-volt, 15- or 20-ampere receptacle on a general-purpose branch circuit

680.12(B) requires at least one GFCI-protected 125-volt, 15- or 20-ampere general-purpose receptacle specifically 'within an equipment room' — vaults and pits aren't included in that specific mandate. The GFCI-for-all-receptacles rule, by contrast, applies to equipment rooms, vaults, and pits alike. There's no stated minimum count of two, and no 30-ampere minimum rating.

Why pools need equipotential bonding

NEC 680.26(A)

Equipotential bonding exists to equalize voltage across the pool and deck so a person in contact with both never feels a shock — not to provide a ground-fault path.

Q32 NEC 680.26(A)

A residential in-ground pool has no pump, no lighting, and no other electrical equipment connected to it. Is equipotential bonding under 680.26 required?

  1. A Yes, because the bonding requirement applies with or without associated electrical equipment
  2. B No, because bonding only applies when pool-related electrical equipment is present
  3. C No, because voltage gradients cannot occur without an electrical source at the pool
  4. D Yes, but only if the pool is within 20 ft of a dwelling unit
Show answer & explanation

Correct: A — Yes, because the bonding requirement applies with or without associated electrical equipment

680.26(A) states that equipotential bonding to reduce voltage gradients is required for pools with or without associated electrical equipment. The idea that bonding is only triggered by electrical equipment, or that gradients can't occur without an electrical source, misunderstands the purpose — the pool and perimeter surfaces themselves create the gradient risk.

Cord-and-plug-connected fountain equipment: GFCI, cord type, sealing, terminations

NEC 680.56

Every cord-and-plug fountain load needs GFCI protection, an extra-hard-usage "W" cord, potted watertight terminations, and a permanent connection unless it's fixed equipment outside the water.

Q33 NEC 680.56

Under 680.56(A), what electrical equipment associated with a fountain must be GFCI protected?

  1. A Only equipment rated over 15 amperes
  2. B Only equipment that is submerged in the water-containing part of the fountain
  3. C Only equipment supplied by a feeder rather than a branch circuit
  4. D All electrical equipment, including power-supply cords
Show answer & explanation

Correct: D — All electrical equipment, including power-supply cords

680.56(A) states that all electrical equipment, including power-supply cords, shall be GFCI protected — there's no carve-out based on amperage, feeder vs. branch circuit, or whether the equipment is submerged. Those distinctions are common confusions with GFCI rules elsewhere in Article 680, but 680.56(A) is written without qualification.

Scope of fountain rules and equipment location setback

NEC 680.50

Permanently installed fountains always follow Part I and Part V, and equipment over the low-voltage contact limit must sit 5 ft back from the fountain walls unless a permanent barrier separates it.

Q34 NEC 680.50

Per 680.50(B), equipment rated above the low-voltage contact limit may be located closer than 5 ft to a fountain's inside walls only if:

  1. A It is listed for wet locations
  2. B It is mounted at least 4 ft above grade
  3. C It is separated from the fountain by a solid fence, wall, or other permanent barrier
  4. D It is GFCI-protected
Show answer & explanation

Correct: C — It is separated from the fountain by a solid fence, wall, or other permanent barrier

680.50(B) allows the 5 ft (1.5 m) horizontal setback to be waived only when a solid fence, wall, or other permanent barrier separates the equipment from the fountain. GFCI protection, mounting height, and wet-location listing are separate considerations elsewhere in Article 680 and don't substitute for the physical barrier this section requires.

Submersible equipment installation: overheat protection, wiring, servicing, stability

NEC 680.51(D)

Submersible fountain equipment needs a low-water cutoff, corrosion-resistant wetted metal, a 10 ft cord limit, easy removal for service, and secure stability.

Q35 NEC 680.51(D)

A submersible fountain pump is designed to be cooled by the surrounding water. Per 680.51(D), what must protect it from damage if it is exposed or the water level drops?

  1. A A GFCI circuit breaker at the panelboard
  2. B A low-water cutoff or other approved means of overheat protection
  3. C An equipment bonding jumper sized to the branch-circuit conductors
  4. D A disconnecting means within sight of the fountain
Show answer & explanation

Correct: B — A low-water cutoff or other approved means of overheat protection

680.51(D) specifically requires a low-water cutoff or other approved means to prevent overheating when equipment that depends on submersion loses that submersion. GFCI protection, bonding jumpers, and disconnect location are all real 680 requirements elsewhere in the article, but none address the overheating hazard from loss of water contact.

Grounding and Bonding Conductors and Terminals

NEC 680.7

In pool-area corrosive or wet locations, EGCs must be insulated copper sized per Table 250.122 (12 AWG minimum), and terminals must be copper, copper alloy, or stainless steel and listed for direct burial.

Q36 NEC 680.7

Table 250.122 calculations show that a 20 A pool pump branch circuit only requires a 14 AWG equipment grounding conductor. What is the minimum EGC size actually permitted under 680.7(A)?

  1. A 12 AWG, regardless of the Table 250.122 result
  2. B 10 AWG in all pool installations
  3. C Bare 14 AWG copper is acceptable if run in conduit
  4. D 14 AWG, matching the Table 250.122 result
Show answer & explanation

Correct: A — 12 AWG, regardless of the Table 250.122 result

680.7(A) sets 12 AWG insulated copper as the floor for feeder and branch-circuit EGCs in pool corrosive/wet locations, even when Table 250.122 alone would permit a smaller conductor. 10 AWG is not the stated minimum, and bare conductors don't meet the insulated-copper requirement.

Bonding hydromassage tub metal parts

NEC 680.74(A)

Everything metal near a hydromassage tub that could become energized gets tied together with an 8 AWG solid copper bonding jumper — but this bond stays local and never runs to a panel or electrode.

Q37 NEC 680.74(A)

Where must the equipotential bonding jumper for a hydromassage tub be terminated?

  1. A To the panelboard supplying the tub's branch circuit
  2. B Only within the area of the hydromassage tub, connecting the required metal parts together
  3. C To the service equipment enclosure
  4. D To the nearest grounding electrode
Show answer & explanation

Correct: B — Only within the area of the hydromassage tub, connecting the required metal parts together

Per 680.74(B), the bonding jumper is for equipotential bonding in the area of the hydromassage bathtub and is not required to be extended or attached to any remote panelboard, service equipment, or electrode. The grounding electrode, service equipment, and panelboard options all describe extending the bond to a remote point, which the section explicitly says is not required.

Immersion pool clearance from luminaires, fans, and switches

NEC 680.35(E)

Storable and portable immersion pools need 10 ft diagonal clearance from overhead lighting and paddle fans, and 5 ft horizontal clearance from switches, with narrow exceptions for the pool's own equipment.

Q38 NEC 680.35(E)

A ceiling-suspended paddle fan operating at 120 volts is near a storable immersion pool. How is the required clearance measured?

  1. A 3 m (10 ft) diagonally from the nearest point on the fan to the nearest point on the pool's top rim
  2. B 1.5 m (5 ft) diagonally from the nearest point on the fan to the water surface
  3. C 3 m (10 ft) vertically above the pool's top rim
  4. D 3 m (10 ft) horizontally from the pool's edge
Show answer & explanation

Correct: A — 3 m (10 ft) diagonally from the nearest point on the fan to the nearest point on the pool's top rim

680.35(E) requires 3 m (10 ft) measured diagonally between the nearest point on the fan and the nearest point on the pool's top rim, since the fan operates above the low-voltage contact limit. A flat horizontal or vertical-only measurement, or the 1.5 m (5 ft) figure (which applies to switches under 680.35(F)), would misapply the rule.

Permanently installed immersion pools: applicable rules and bonding exceptions

NEC 680.45

Immersion pools follow Parts I, II, and IV of Article 680 (treated like a spa/hot tub for Part IV) and use Chapter 3 wiring methods, with two carve-outs from equipotential bonding.

Q39 NEC 680.45

A permanently installed immersion pool has no permanently connected electrical equipment and is installed entirely above the finished floor. What does 680.45 say about equipotential bonding?

  1. A Equipotential bonding is required unless the pool is a spa listed for outdoor use
  2. B The equipotential bonding requirements of 680.26(B) do not apply
  3. C Equipotential bonding is required only if the pool is indoors
  4. D Equipotential bonding is still required because the pool is permanently installed
Show answer & explanation

Correct: B — The equipotential bonding requirements of 680.26(B) do not apply

680.45 waives 680.26(B) equipotential bonding specifically when the immersion pool has no permanently installed or connected electrical equipment and is located entirely on or above the finished floor. Being permanently installed as a pool type doesn't override this exception, and the rule isn't conditioned on indoor/outdoor location or spa listing.

Heater requirements for permanently installed immersion pools

NEC 680.45(C)

Whether a heater is permanently installed or cord-connected, it must be listed for pool/spa use, grounded, and GFCI protected on 150-volt-or-less-to-ground circuits.

Q40 NEC 680.45(C)

A cord-connected, storable heater used with a permanently installed immersion pool must have what type of ground-fault protection?

  1. A GFPE (ground-fault protection of equipment) only
  2. B No GFCI required if the cord is under 6 ft
  3. C Class A GFCI protection
  4. D Standard GFCI protection only when rated above 250 volts
Show answer & explanation

Correct: C — Class A GFCI protection

680.45(C)(2) specifically requires Class A GFCI protection for storable/portable heaters supplied at 150 volts or less to ground. GFPE is not the applicable protection type here, cord length doesn't exempt the GFCI requirement, and the requirement applies regardless of the voltage/ampere tier described.

Receptacle requirements for immersion pool equipment

NEC 680.35(G)

Any 250V/50A-or-less receptacle within 20 ft of a storable or portable immersion pool that feeds pool equipment must meet the same GFCI and location rules as storable pools.

Q41 NEC 680.35(G)

A 240-volt, 30-ampere receptacle is mounted 15 ft from the inside wall of a portable cold-plunge immersion pool and feeds the plunge's heater. Under 680.35(G), what must this receptacle comply with?

  1. A No additional requirement beyond standard 250-volt receptacle installation rules
  2. B 680.32 and 680.34
  3. C 680.34 only — GFCI protection is not required
  4. D 680.32 only — placement is not restricted
Show answer & explanation

Correct: B — 680.32 and 680.34

680.35(G) requires a receptacle rated 250V, 50A or less within 6.0 m (20 ft) of an immersion pool, and used to power pool equipment, to meet both 680.32 and 680.34 together — GFCI protection and location requirements, not just one of them.

Maintenance Disconnecting Means for Pool Equipment

NEC 680.13

Pool equipment needs a readily accessible disconnect within sight, kept at least 5 ft from the water's edge unless a permanent barrier provides that reach path.

Q42 NEC 680.13

Under 680.13, which piece of pool-related equipment is NOT required to have a maintenance disconnecting means?

  1. A Underwater pool lighting
  2. B An air blower for a spa
  3. C A pool circulation pump
  4. D A pool heater
Show answer & explanation

Correct: A — Underwater pool lighting

680.13 requires a maintenance disconnecting means for all pool utilization equipment except lighting. Pumps, heaters, and blowers are utilization equipment covered by the rule; lighting is specifically excluded, per 680.13.

No-niche luminaires

NEC 680.23(D)

A no-niche luminaire follows the same construction and installation rules as a wet-niche luminaire, except any forming-shell connection goes to the mounting bracket instead.

Q43 NEC 680.23(D)

A no-niche luminaire has no forming shell. Per 680.23(D), where the code specifies a connection to a forming shell, the connection shall instead be made to what?

  1. A The pool's bonding grid directly
  2. B The mounting bracket
  3. C The wet-niche housing
  4. D A dry-niche enclosure
Show answer & explanation

Correct: B — The mounting bracket

680.23(D) states that where connection to a forming shell is specified, the connection shall be to the mounting bracket instead, since a no-niche luminaire has no forming shell. The wet-niche housing, direct bonding-grid connection, and dry-niche enclosure aren't the substitution point this rule identifies.

Overhead Conductor and Communications Cable Clearances

NEC 680.9

Overhead power conductors near pools follow Table 680.9(A) clearances measured from maximum water level, while communications and CATV cables just need 3.0 m (10 ft).

Q44 NEC 680.9 Code lookup

A residential pool installer is running open overhead conductors (not in a raceway) across the yard near an in-ground swimming pool. Which section provides the minimum clearance requirements (via a table) for these conductors above the pool?

  1. A 680.9(A)
  2. B 680.9(C)
  3. C 680.11(A)
  4. D 680.9(B)
Show answer & explanation

Correct: A — 680.9(A)

680.9(A) sends open overhead power conductors to Table 680.9(A) for minimum clearances. 680.9(B) only covers communications/coax cables, and 680.9(C) applies specifically to network-powered broadband conductors, not general power conductors.

Transformer/GFCI enclosure construction and placement

NEC 680.24(B)(1)

A transformer or GFCI enclosure feeding a no-niche luminaire must be listed for the purpose, sealed and bonded, and kept at least 4 in. above deck/8 in. above water and 4 ft from the pool wall unless a barrier separates it.

Q45 NEC 680.24(B)(1)

A pool's maximum water level would put an 8 in. clearance line lower than a 4 in.-above-deck clearance line for a nearby transformer enclosure. Per 680.24(B)(2)(a), which elevation governs?

  1. A The average of the two elevations
  2. B The 8 in.-above-water elevation, since water clearance always controls
  3. C Either may be used at the installer's discretion
  4. D The 4 in.-above-deck elevation, since it is the greater of the two
Show answer & explanation

Correct: D — The 4 in.-above-deck elevation, since it is the greater of the two

680.24(B)(2)(a) requires the enclosure to be located at whichever elevation is greater between 4 in. above deck/ground level and 8 in. above max pool water level — not a fixed preference for water clearance, discretion, or an average.

Pool junction box construction and placement

NEC 680.24(A)(1)

A pool junction box feeding a no-niche luminaire must be listed for the job, corrosion-resistant, and set back 4 in. above grade / 8 in. above water and 4 ft from the pool wall — unless it's a potted flush deck box on low-voltage.

Q46 NEC 680.24(A)(1)

A junction box connects directly to the forming shell of a no-niche pool luminaire operating above the low-voltage contact limit. Which placement satisfies 680.24(A)(2)?

  1. A 4.5 ft from the pool wall and 5 in. above the pool deck
  2. B Flush-mounted in the deck with potting compound, 5 ft from the pool wall
  3. C 3 ft from the pool wall, with no fence or barrier present
  4. D 6 in. above the maximum pool water level
Show answer & explanation

Correct: A — 4.5 ft from the pool wall and 5 in. above the pool deck

680.24(A)(2)(a) and (b) require at least 4 in. above deck/grade or 8 in. above max water level (whichever is greater), plus at least 4 ft horizontal clearance from the pool wall unless a permanent barrier separates the box. The 4.5 ft / 5 in. option clears both the vertical and horizontal minimums. The 3 ft option fails the 4 ft horizontal rule, the 6 in. above water option falls short of the 8 in. minimum, and the flush deck box option is only permitted at or below the low-voltage contact limit, not above it.

Pool lift scope and equipment listing requirements

NEC 680.81

Electrically powered pool lifts must be listed, labeled, and identified for pool/spa use, unless they fall under one of three low-voltage exceptions.

Q47 NEC 680.81

An electrically powered pool lift is installed at a residential pool. Under what condition can it be installed WITHOUT being listed, labeled, and identified for swimming pool and spa use?

  1. A The lift is installed by a licensed electrician
  2. B The lift is used only during pool parties and stored otherwise
  3. C The lift is bonded to the pool's equipotential bonding grid
  4. D The lift's battery is removed for charging at another location and is rated at or below the low-voltage contact limit
Show answer & explanation

Correct: D — The lift's battery is removed for charging at another location and is rated at or below the low-voltage contact limit

Per 680.81, listing/labeling isn't required when the battery is removed for offsite charging and is rated at or below the low-voltage contact limit. Who installs it, how often it's used, and bonding to the equipotential grid don't affect the listing requirement.

GFCI/SPGFCI protection for luminaires 5-10 ft from pool

NEC 680.22(B)(4)

Luminaires and paddle fans 5-10 ft from a pool need GFCI or SPGFCI protection unless mounted at least 5 ft above the water and rigidly attached to the structure.

Q48 NEC 680.22(B)(4)

A new lighting outlet is planned 7 ft horizontally from the inside wall of a pool, mounted only 4 ft above the maximum water level. What does 680.22(B)(4) require?

  1. A Only bonding of the fixture is required, not GFCI protection
  2. B GFCI or SPGFCI protection, since the height clearance is not met
  3. C The fixture must simply be relocated beyond 10 ft to comply
  4. D No protection is required because it is outside the 5 ft zone
Show answer & explanation

Correct: B — GFCI or SPGFCI protection, since the height clearance is not met

Under 680.22(B)(4), fixtures in the 5-10 ft zone need GFCI or SPGFCI protection unless they are at least 5 ft above the max water level and rigidly attached. At only 4 ft above water, the height exception isn't met, so protection is required. Relocating beyond 10 ft isn't necessary — protection within the zone is sufficient, and bonding alone does not substitute for GFCI/SPGFCI protection.

Cord-and-plug and low-voltage luminaire exceptions near pools

NEC 680.22(B)(6)

Low-voltage luminaires and fire features under the contact limit can sit within 5 ft of a pool wall, but cord-and-plug luminaires within 16 ft of the water still must follow 680.8.

Q49 NEC 680.22(B)(6) Code lookup

A pool builder wants to install small listed low-voltage LED accent luminaires directly into the pool wall's vertical surface, only 3 ft from the inside wall of the pool. The luminaires do not require grounding, are within the low-voltage contact limit, and are fed from a listed transformer meeting 680.23(A)(2). Which section permits mounting these luminaires closer than the usual clearance from the pool wall?

  1. A 680.22(B)(1)
  2. B 680.22(B)(5)
  3. C 680.22(B)(6)
  4. D 680.22(B)(2)
Show answer & explanation

Correct: C — 680.22(B)(6)

680.22(B)(6) is the specific exception permitting listed low-voltage luminaires meeting the stated conditions to be located less than 5 ft from the inside pool wall. 680.22(B)(1) sets the general outdoor clearance requirement this exception relaxes, and 680.22(B)(5) addresses cord-and-plug-connected luminaires within 16 ft of the water surface, not the 5 ft wall clearance.

GFCI/SPGFCI protection for all pool-area receptacles

NEC 680.22(A)(4)

Every 125–250V, 60A-or-less receptacle within 20 ft of a pool's inside walls needs GFCI or SPGFCI protection, no matter how far that is from the actual spacing minimum.

Q50 NEC 680.22(A)(4)

A 125-volt, 20-ampere receptacle is installed 18 ft from the inside wall of a pool. What protection does 680.22(A)(4) require?

  1. A GFCI protection complying with 680.5(B), or SPGFCI protection complying with 680.5(C)
  2. B No protection is required because it's outside the 6 ft minimum spacing distance
  3. C Protection is only required if the receptacle supplies pool equipment directly
  4. D SPGFCI protection only — GFCI protection is not an acceptable alternative
Show answer & explanation

Correct: A — GFCI protection complying with 680.5(B), or SPGFCI protection complying with 680.5(C)

680.22(A)(4) requires GFCI or SPGFCI protection for any 125–250 volt, 60 A or less receptacle within 6.0 m (20 ft) of a pool's inside walls — 18 ft falls inside that zone. The 6 ft distance is a separate placement minimum, not the protection trigger, and the rule explicitly allows either GFCI per 680.5(B) or SPGFCI per 680.5(C) — it doesn't limit protection to SPGFCI only or to receptacles feeding pool equipment.

Pool Water Heaters and Heat Pumps/Chillers

NEC 680.10

Resistive pool water heaters must be split into 48 A max loads protected at 60 A max, with conductors and OCPD at 125% of nameplate; heat pumps and chillers just need to be listed and sized to nameplate.

Q51 NEC 680.10

An electric pool water heater uses resistive heating elements. Per 680.10(A), how must the heating elements be arranged?

  1. A Wired as a single load protected at 125% of nameplate rating
  2. B Listed and sized directly to the nameplate rating
  3. C Subdivided into loads not exceeding 60 amperes each
  4. D Subdivided into loads not exceeding 48 amperes each
Show answer & explanation

Correct: D — Subdivided into loads not exceeding 48 amperes each

680.10(A) requires resistive heating elements to be subdivided into loads not exceeding 48 amperes, protected at not over 60 amperes. The 60-ampere figure is the overcurrent protection cap, not the load-subdivision limit, and 'listed and sized to nameplate' describes heat pumps/chillers under 680.10(B), not resistive heaters.

Bonding methods and equipotential bonding exceptions for spas

NEC 680.42(B)

Metal-to-metal frame bonding is always allowed, and a listed self-contained outdoor spa can skip perimeter equipotential bonding if it meets all four listed conditions, including a 28 in. rim height.

Q52 NEC 680.42(B)

Under 680.42(B), which condition is required for a self-contained aboveground spa to be exempt from perimeter equipotential bonding?

  1. A The spa must be listed for indoor use only
  2. B The spa's top rim must be at least 710 mm (28 in.) above perimeter surfaces within 760 mm (30 in.)
  3. C The spa must be installed below grade to isolate it from perimeter surfaces
  4. D The spa must be bonded using a copper grid buried beneath the perimeter surface
Show answer & explanation

Correct: B — The spa's top rim must be at least 710 mm (28 in.) above perimeter surfaces within 760 mm (30 in.)

680.42(B) requires the top rim be at least 710 mm (28 in.) above all perimeter surfaces within 760 mm (30 in.) horizontally. The buried bonding grid describes 680.26(B)(2), which this exception avoids. The spa must NOT be indoor-only rated, and it must be located on or above grade, not below grade.

GFCI/SPGFCI protection for storable pool equipment and nearby receptacles

NEC 680.32

All equipment used with a storable pool, plus any 125–250V receptacle 60A or less within 20 ft of its walls, must have GFCI or SPGFCI protection.

Q53 NEC 680.32

Under 680.32, which receptacles located within 6.0 m (20 ft) of a storable pool's inside walls must have GFCI or SPGFCI protection?

  1. A Only receptacles that directly supply the pool's recirculating pump
  2. B Only receptacles rated higher than 60 amperes
  3. C Any receptacle rated 125 through 250 volts, 60 amperes or less
  4. D Only 125-volt, 15- and 20-ampere general-purpose receptacles
Show answer & explanation

Correct: C — Any receptacle rated 125 through 250 volts, 60 amperes or less

680.32 requires GFCI/SPGFCI protection for any 125-through-250-volt receptacle rated 60 amperes or less within 20 ft of a storable pool's walls — not just 15/20 A general-purpose outlets, not just a pump-dedicated receptacle, and not receptacles above 60 A, which fall outside this rule's scope.

Underwater luminaire construction options for storable pools

NEC 680.33

A storable pool underwater luminaire must be a listed cord-and-plug assembly built either within the low-voltage contact limit with a transformer, or over that limit but 150 V or less with an integral GFCI that has open-neutral protection.

Q54 NEC 680.33

A storable pool underwater luminaire assembly operates within the low-voltage contact limit. Which component is required as part of the listed assembly?

  1. A A GFCI with open-neutral conductor protection integral to the assembly
  2. B A luminaire lamp permanently connected to a GFCI
  3. C Exposed metal parts bonded to the equipment grounding conductor
  4. D A transformer or power supply meeting 680.23(A)(2) with a primary rating not over 150 V
Show answer & explanation

Correct: D — A transformer or power supply meeting 680.23(A)(2) with a primary rating not over 150 V

Per 680.33(A), a within-low-voltage-contact-limit assembly requires a transformer or power supply per 680.23(A)(2) rated not over 150 V primary, along with no exposed metal parts and an impact-resistant polymeric lens, body, and transformer enclosure. The integral GFCI with open-neutral protection and permanently connected lamp are features of the 680.33(B) assembly (over the low-voltage contact limit), not this one, and exposed metal parts are prohibited under both options.

Bonding therapeutic tub metal parts

NEC 680.62(B)

Everything metal in, on, or within 5 ft of a therapeutic tub must be bonded together, using solid copper 8 AWG or larger if a jumper is used.

Q55 NEC 680.62(B)

Which of the following is NOT required to be bonded under the therapeutic tub bonding rules?

  1. A An electrical control unrelated to the tub located within 5 ft of it
  2. B A towel bar not connected to metal framing
  3. C Metal piping within 5 ft of the tub's inside walls with no permanent barrier
  4. D Metal pump motor parts of the tub's water circulating system
Show answer & explanation

Correct: B — A towel bar not connected to metal framing

680.62(B) exempts small conductive surfaces unlikely to become energized, such as towel bars and mirror frames not connected to metal framing. Pump motor parts, nearby unbarriered metal piping, and unrelated electrical devices/controls within 5 ft are all specifically required to be bonded.

GFCI protection for therapeutic tubs

NEC 680.62(A)

Therapeutic tub outlets need GFCI protection unless the unit has built-in GFCI protection, or the unit is 3-phase, over 250V, or has a heater load over 50 A.

Q56 NEC 680.62(A)

A field-assembled therapeutic tub's supply outlet is being installed in a healthcare facility. Per 680.62(A), what protection does the outlet require by default?

  1. A No special protection, since it is field-assembled rather than self-contained
  2. B GFCI protection only if the tub is rated single phase and 250 volts or less
  3. C AFCI protection
  4. D GFCI protection
Show answer & explanation

Correct: D — GFCI protection

680.62(A) requires GFCI protection for the outlet supplying a self-contained, packaged, or field-assembled therapeutic tub, with no distinction based on assembly type. The voltage/phase condition in the last option describes when the requirement can be waived under 680.62(A)(2), not a precondition for it to apply. AFCI is not the protection type specified here.

Underwater audio speaker installation

NEC 680.27(A)(1)

Underwater speakers must sit in a corrosion-resistant metal forming shell with a locking screen, fed by approved conduit, and bonded with an 8 AWG copper conductor.

Q57 NEC 680.27(A)(1)

An underwater pool speaker is fed with liquidtight flexible nonmetallic conduit (LFNC) from the forming shell to the junction box. What additional component does 680.27(A)(2) require inside that conduit?

  1. A An 8 AWG insulated solid or stranded copper bonding jumper
  2. B A separate ground rod bonded at the shell
  3. C No additional conductor, since LFNC is self-bonding
  4. D A 12 AWG equipment grounding conductor
Show answer & explanation

Correct: A — An 8 AWG insulated solid or stranded copper bonding jumper

Per 680.27(A)(2), when LFNC, rigid PVC, or RTRC is used, an 8 AWG insulated solid or stranded copper bonding jumper must be installed in the conduit and terminated at the forming shell and junction box. A 12 AWG equipment grounding conductor and a ground rod don't meet this specific bonding jumper requirement, and nonmetallic conduit is never self-bonding.

Equipment grounding conductor for underwater luminaire circuits

NEC 680.23(F)(2)

The equipment grounding conductor to an underwater luminaire must be insulated copper, unspliced, and at least 12 AWG — sized up per 250.122 if the load demands it.

Q58 NEC 680.23(F)(2)

A wet-niche underwater luminaire circuit uses a 14 AWG equipment grounding conductor sized per the standard 250.122 table for the circuit's overcurrent device. Is this compliant?

  1. A Yes, because underwater luminaire circuits are exempt from minimum EGC size rules
  2. B Yes, because 250.122 sizing always governs equipment grounding conductors
  3. C No, because underwater luminaire EGCs must always be aluminum
  4. D No, because 680.23(F)(2) sets 12 AWG as the minimum regardless of what 250.122 would allow
Show answer & explanation

Correct: D — No, because 680.23(F)(2) sets 12 AWG as the minimum regardless of what 250.122 would allow

680.23(F)(2) sizes the EGC per 250.122 but sets a hard floor of 12 AWG — a smaller conductor is not allowed even if the standard table would permit it. The EGC must also be copper, not aluminum, ruling out that distractor.

Raceway-sharing limits for GFCI/transformer output conductors

NEC 680.23(F)(3)

Conductors feeding an underwater luminaire from a GFCI or the isolating transformer can't share a raceway or box with other conductors unless those other conductors are also GFCI-protected, are the required EGCs/bonding jumpers, or are supply conductors to a feed-through GFCI.

Q59 NEC 680.23(F)(3)

Load-side conductors from a pool luminaire's GFCI are run in the same raceway as another branch circuit's conductors. Under what condition is this permitted per 680.23(F)(3)?

  1. A The other circuit is also for pool equipment
  2. B The other conductors are rated for a higher voltage
  3. C The other conductors are also GFCI protected
  4. D The raceway is metallic and bonded
Show answer & explanation

Correct: C — The other conductors are also GFCI protected

680.23(F)(3)(1) permits sharing only when the other conductors are themselves GFCI protected. A higher voltage rating, a bonded metallic raceway, or the other circuit also serving pool equipment are not among the listed exceptions in 680.23(F)(3).

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access