Free NEC practice test · Article 610

Cranes and Hoists practice questions

A free NEC Article 610 practice test for the journeyman exam: 15 questions on Cranes and Hoists, each with the answer and the why behind it.

15 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 15 journeyman-exam practice questions cover NEC Article 610 across 15 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Support spacing for runway and bridge contact conductors

NEC 610.21(C)

Runway conductors need insulating supports every 20 ft (up to 40 ft if spacing widens proportionately) with 6 in. separation; bridge conductors need saddles every 50 ft on spans over 80 ft with 2½ in. separation; rigid conductors follow the 80x-height rule capped at 15 ft.

Q1 NEC 610.21(C)

A designer needs to space insulating supports for main contact conductors along a crane runway beyond the normal maximum. What must also happen if the interval is increased to 12 m (40 ft)?

  1. A No other change is required since 40 ft is always allowed
  2. B Insulating saddles must be added at 15 m intervals instead
  3. C The conductors must be changed to the rigid type
  4. D The conductor separation must be increased proportionately
Show answer & explanation

Correct: D — The conductor separation must be increased proportionately

610.21(C) allows increasing the support interval up to 12 m (40 ft) only if the separation between conductors is increased proportionately. The insulating saddle interval and rigid-conductor rules belong to 610.21(D) and 610.21(E), not this provision, and the increase is conditional, not automatic.

Branch-Circuit Fuse/Breaker Rating for Crane Motors

NEC 610.42(A)

Crane, hoist, and monorail hoist motor branch circuits are protected only by fuses or inverse-time breakers rated per Table 430.52(C)(1), and motors sharing one motion are summed as a single motor.

Q2 NEC 610.42(A) Code lookup

A crane installation has two motors operating the same bridge motion. Their nameplate current ratings must be summed and treated as a single motor when sizing the branch-circuit fuses or inverse-time circuit breakers per Table 430.52(C)(1). Which section states this combined-rating requirement and sets the fuse/breaker rating rule for crane, hoist, and monorail hoist motor branch circuits?

  1. A 610.42(B)(1)
  2. B 610.42(A)
  3. C 610.43(C)
  4. D 610.41(A)
Show answer & explanation

Correct: B — 610.42(A)

610.42(A) is the branch-circuit fuse/circuit breaker rating rule, which is based on Table 430.52(C)(1) and includes the rule to sum nameplate currents when two or more motors operate a single motion. 610.42(B)(1) instead addresses feeder taps supplying multiple motors, and 610.43(C) governs overload protection for multimotor branch circuits, not short-circuit/ground-fault sizing.

Ampacity and minimum size of crane/hoist conductors

NEC 610.14(A)

Crane and hoist conductor ampacity comes from Table 610.14(A), and no external conductor may go below 16 AWG except two narrow exceptions for control and electronic circuits.

Q3 NEC 610.14(A) Code lookup

A crane installation uses short-time rated hoist motors, and the electrician needs to size the insulated copper conductors feeding them based on ambient temperature and duty cycle. Which section provides the ampacity table for these conductors?

  1. A 610.14(C)
  2. B 610.14(B)
  3. C 610.14(D)
  4. D 610.14(A)
Show answer & explanation

Correct: D — 610.14(A)

610.14(A) hosts Table 610.14(A), the ampacity table for insulated copper conductors used with short-time rated crane and hoist motors. 610.14(B) only covers sizing the separate conductors between controller and resistor using a rating factor, not the base ampacity table itself.

Conductor types: heat exposure, bare contact conductors, and flexible cords

NEC 610.13

Crane and hoist conductors default to Table 310.4(1), but heat exposure calls for flame-resistant covering, runway contact conductors can be bare metal, and flexible runs need listed cord, cable, or festoon cable.

Q4 NEC 610.13

A crane installation routes conductors close to a bank of resistors that generate significant heat. What does 610.13(A) require?

  1. A The conductors must be replaced with bare contact conductors per 610.13(B)
  2. B The conductors must have a flame-resistant outer covering or flame-resistant tape, individually or as a group
  3. C The conductors must be derated to 50% of their Table 310.4(1) ampacity
  4. D The conductors must be run in rigid metal conduit for the entire heated section
Show answer & explanation

Correct: B — The conductors must have a flame-resistant outer covering or flame-resistant tape, individually or as a group

610.13(A) requires a flame-resistant outer covering, or flame-resistant tape applied individually or as a group, for conductors exposed to external heat or connected to resistors. Conduit, derating, and switching to bare contact conductors are not the rule this section states.

Flexible connections to motors, pendants, and moving parts

NEC 610.11(C)

Flexible motor and pendant connections need flexible stranded conductors in an approved flexible wiring method, and moving-part connections need festoon cable or suitable cord with strain relief.

Q5 NEC 610.11(C)

Under 610.11(C), which wiring method is NOT listed as approved for flexible connections to a crane motor?

  1. A Multiconductor cable
  2. B Rigid metal conduit
  3. C Liquidtight flexible metal conduit
  4. D Liquidtight flexible nonmetallic conduit
Show answer & explanation

Correct: B — Rigid metal conduit

610.11(C) permits flexible metal conduit, liquidtight flexible metal conduit, liquidtight flexible nonmetallic conduit, multiconductor cable, or an approved nonmetallic flexible raceway. Rigid metal conduit is a fixed raceway and cannot provide the flexibility this section requires.

Overcurrent protection sizing for crane control circuits

NEC 610.53

Crane control conductors are protected at up to 300% of their ampacity, but transformer taps drop that to 200% and hazard-of-opening circuits can skip dedicated protection entirely.

Q6 NEC 610.53

Under 610.53, control circuit conductors on a crane are considered protected against overcurrent when the protective device is rated or set at not more than what percentage of the conductor ampacity, absent any exception?

  1. A 300 percent
  2. B 125 percent
  3. C 200 percent
  4. D 400 percent
Show answer & explanation

Correct: A — 300 percent

610.53 sets the general control-circuit protection allowance at not more than 300 percent of conductor ampacity. 200 percent is the tighter limit that applies specifically to transformer-tap secondaries under 610.53(A), not the general rule. 125 percent is a common continuous-load multiplier from other NEC contexts, not this section.

Disconnecting means for cranes and monorail hoists

NEC 610.32

Cranes and monorail hoists need a lockable disconnect in the power supply leads, sized to at least 50% of combined motor short-time rating or 75% of any single motion's motors.

Q7 NEC 610.32

Under 610.33, which statement correctly describes how the two sizing thresholds for the disconnecting means relate to each other?

  1. A Both the 50% combined and 75% single-motion thresholds must be met; the larger required rating governs
  2. B Only the 50% combined threshold applies; the single-motion rule is advisory
  3. C Either threshold may be used at the designer's discretion, whichever gives a smaller device
  4. D Only the 75% single-motion threshold applies; the combined rating rule is advisory
Show answer & explanation

Correct: A — Both the 50% combined and 75% single-motion thresholds must be met; the larger required rating governs

610.33 sets two independent minimums: not less than 50% of the combined short-time rating of all motors, and not less than 75% of the short-time rating for any single motion. Both are mandatory floors, so the disconnect must satisfy whichever produces the higher required ampere rating.

When one controller can run more than one motor

NEC 610.51

Every motor needs its own controller unless the motors share one motion together, or one controller switches between motors that never run at the same time.

Q8 NEC 610.51

Per 610.51, what is required for each motor on a crane or hoist unless an exception applies?

  1. A An individual disconnecting means only, controller optional
  2. B An individual controller
  3. C A shared controller sized for the combined horsepower of all motors on the machine
  4. D A controller rated at 125% of the motor's full-load current
Show answer & explanation

Correct: B — An individual controller

610.51 requires each motor to have an individual controller unless 610.51(A) or (B) permits otherwise. A combined-horsepower shared controller and a disconnect-only setup are not what the base rule requires, and a 125%-rated controller conflates controller rating with overcurrent sizing, which isn't the topic of this section.

Using the crane track/rail itself as a circuit conductor

NEC 610.21(F)

A crane, monorail, or tram rail may carry one phase of a 3-phase ac supply only if every condition in 610.21(F) is met — insulated other phases, an insulating transformer, 300 volts max, and bonding to the equipment grounding conductor at the transformer.

Q9 NEC 610.21(F)

Under what circumstance may a crane runway rail be used as a current-carrying conductor for one phase of a 3-phase ac supply?

  1. A Anytime the crane's controller is listed for rail-fed power
  2. B Only on dc-powered cranes, since ac systems can't use rails as conductors
  3. C Only when every condition of 610.21(F) is satisfied, including an insulating transformer and a 300-volt maximum
  4. D Only if the rail is electrically isolated from the building structure
Show answer & explanation

Correct: C — Only when every condition of 610.21(F) is satisfied, including an insulating transformer and a 300-volt maximum

610.21(F) permits this only when all four numbered conditions are met together. The rule applies to ac systems specifically, and isolating the rail from the structure isn't required — the fittings that suspend or attach the rail to a building are explicitly permitted to ground it.

Wiring method for crane and hoist conductors

NEC 610.11

Crane and hoist conductors must be enclosed in raceway or Type AC/MC/MI cable, except bare contact conductors and short exposed runs at resistors or collectors.

Q10 NEC 610.11

Which of the following is NOT one of the wiring methods permitted by 610.11 for enclosing crane and hoist conductors?

  1. A Type NM cable
  2. B Type MI cable
  3. C Type AC cable with an insulated equipment grounding conductor
  4. D Type MC cable
Show answer & explanation

Correct: A — Type NM cable

610.11 lists raceway, Type AC cable with an insulated equipment grounding conductor, Type MC cable, or Type MI cable as the permitted enclosure methods. Type NM cable is not one of the listed options, so it does not comply.

Calculating motor load for single/multiple motors and cranes

NEC 610.14(E)

One motor uses 100% of its nameplate FLA; multiple motors on a crane use largest motor at 100% plus the next largest at 50%; multiple cranes stack those sums and apply a demand factor from Table 610.14(E)(3).

Q11 NEC 610.14(E)

When determining the minimum ampacity of power supply conductors for a single motor on a crane, what nameplate percentage applies?

  1. A 50 percent of the motor nameplate full-load ampere rating
  2. B 80 percent of the motor nameplate full-load ampere rating
  3. C 100 percent of the motor nameplate full-load ampere rating
  4. D 125 percent of the motor nameplate full-load ampere rating
Show answer & explanation

Correct: C — 100 percent of the motor nameplate full-load ampere rating

610.14(E)(1) requires 100 percent of the single motor's nameplate full-load ampere rating. The 125 percent figure is a common motor-branch-circuit factor from Article 430, not the crane single-motor rule in this concept, and the 50 percent figure only applies to the next-largest motor when multiple motors share a crane per 610.14(E)(2).

Overload Protection Methods for Crane Motors

NEC 610.43(A)

Crane and hoist motors can be protected from overload three ways: a properly rated branch-circuit device, overload relays in each ungrounded conductor, or winding-temperature sensors.

Q12 NEC 610.43(A) Code lookup

A single-motor crane hoist branch circuit uses only the branch-circuit overcurrent device (sized per 610.42) to guard against sustained overload, with no separate overload relays or thermal sensors installed. Which section sets the condition under which this is acceptable as the motor's overload protection?

  1. A 610.43(C)
  2. B 610.43(A)
  3. C 610.43(D)
  4. D 610.42(A)
Show answer & explanation

Correct: B — 610.43(A)

610.43(A)(1) states a single motor is considered protected where the branch-circuit overcurrent device meets the rating requirements of 610.42 — that's the overload-protection rule, not 610.42(A) itself, which only sets the fuse/breaker rating. 610.43(C) and 610.43(D) address multimotor and hoist-specific overload schemes, not the single-motor case.

Terminating raceways and cables at exposed wiring

NEC 610.12

Where a raceway or cable ends and conductors run exposed, use a box with a separately bushed hole per conductor, or — at unenclosed crane/hoist controls — a bushing alone on rigid metal conduit, IMC, or EMT.

Q13 NEC 610.12

A crane installation transitions from EMT to exposed conductors feeding a luminaire outlet. Which termination method satisfies 610.12?

  1. A A terminal fitting with taps, since luminaire circuits are exempted
  2. B A box with a single common bushed opening for all conductors
  3. C A box or terminal fitting with a separately bushed hole for each conductor, without taps or splices
  4. D A bushing alone, since EMT qualifies under 610.12(B)
Show answer & explanation

Correct: C — A box or terminal fitting with a separately bushed hole for each conductor, without taps or splices

610.12(A) requires a separately bushed hole for each conductor and explicitly bars use at luminaire outlets for the bushing-alone method under 610.12(B) — a luminaire outlet still needs the box with individually bushed holes, and it can't contain taps or splices. A single shared bushed opening does not meet the 'separately bushed hole for each conductor' requirement.

Disconnecting means for runway contact conductors

NEC 610.31

Runway contact conductors need their own lockable, simultaneous-break disconnect, sized per 610.14(E)/(F), placed in view of the conductors unless an electrolytic cell line exception applies.

Q14 NEC 610.31

Which requirement applies to the disconnecting means installed between runway contact conductors and the power supply?

  1. A It only needs to be accessible from an elevated maintenance platform
  2. B It may switch ungrounded conductors independently as long as each has its own lock
  3. C It is only required when the runway exceeds a stated horsepower rating
  4. D It must open all ungrounded conductors simultaneously
Show answer & explanation

Correct: D — It must open all ungrounded conductors simultaneously

610.31 requires the disconnecting means to open all ungrounded conductors simultaneously. Switching conductors independently, requiring elevated-only access, or gating the requirement on horsepower are not what the section allows — the disconnect must be readily accessible from ground or floor level for every runway installation covered.

Tap Conductor Protection for Crane Branch Circuits

NEC 610.42(B)

Tap conductors feeding multiple crane motors on one branch circuit need at least one-third the branch circuit's ampacity, and load-side control circuit taps follow 430.72.

Q15 NEC 610.42(B)

Two motors on a crane are connected to the same branch circuit. What is the minimum required ampacity of the tap conductor to each individual motor?

  1. A One-third the full-load current of the largest motor
  2. B One-third the ampacity of the branch circuit
  3. C The same ampacity as the branch circuit conductors
  4. D One-half the ampacity of the branch circuit
Show answer & explanation

Correct: B — One-third the ampacity of the branch circuit

Under 610.42(B)(1), each tap conductor to an individual motor on a shared branch circuit must have an ampacity not less than one-third that of the branch circuit — not one-half, not matched to the branch circuit conductors, and not based on the largest motor's full-load current.