Free NEC practice test · Article 600

Electric Signs practice questions

A free NEC Article 600 practice test for the journeyman exam: 24 questions on Electric Signs and Outline Lighting, each with the answer and the why behind it.

24 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 24 journeyman-exam practice questions cover NEC Article 600 across 24 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Disconnect location rules: at sign, in sight, or remote

NEC 600.6(A)

Every sign disconnect must open all ungrounded conductors and sit at the sign's entry point, within sight of the sign or controller, or remote with a label at the sign pointing to it.

Q1 NEC 600.6(A)

A sign disconnecting means is mounted where it is not within sight of every section of the sign that could be energized. What does the NEC require?

  1. A No additional requirement applies as long as the disconnect is externally operable
  2. B A second disconnect must be added within sight of the sign
  3. C The disconnect must be lockable in the open position and the sign must carry a marking showing the disconnect's location
  4. D The disconnect must instead be relocated to the point of entry to the sign enclosure
Show answer & explanation

Correct: C — The disconnect must be lockable in the open position and the sign must carry a marking showing the disconnect's location

Under 600.6(A)(2), when the disconnect is out of the line of sight from any section able to be energized, it must be lockable per 110.25 and the sign must carry a permanent field-applied marking identifying the disconnect's location. Relocating to the point of entry or adding a second disconnect are not the code's remedy — marking and lockability are.

Raceway types and fill for neon secondary circuits over 1000V

NEC 600.32(A)

Neon secondary conductors over 1000V need a raceway from the approved list, one conductor per raceway, metric designator 16 (trade size 1/2) minimum, and metal building parts can never serve as the return or grounding path.

Q2 NEC 600.32(A)

An electrician is installing rigid metal conduit for a neon secondary circuit operating above 1000 volts. How many current-carrying conductors may be pulled into that single conduit?

  1. A Two, provided one is the return conductor
  2. B Two, if they are the same size
  3. C One
  4. D Three, matching standard branch-circuit conduit fill
Show answer & explanation

Correct: C — One

Per 600.32(A)(2), conduit or tubing for neon secondary circuits over 1000V shall contain only one conductor. This is a special rule distinct from ordinary conduit fill tables that allow multiple conductors, and it applies regardless of conductor size or function.

Bonding sign metal parts together and to the EGC

NEC 600.7(B)(1)

All metal parts of a sign or outline lighting system must be bonded together and to the equipment grounding conductor — never through the building's metal parts.

Q3 NEC 600.7(B)(1)

An electrician wants to bond two adjacent sign sections by connecting each to the metal wall girt they're mounted on. Is this acceptable under 600.7?

  1. A Yes, as long as the girt is continuous metal between the sections
  2. B Yes, if the girt is also bonded to the service equipment grounding conductor
  3. C No, metal building parts cannot be used as the bonding means for sign metal parts
  4. D No, because girts are never permitted to carry any current under any circumstance
Show answer & explanation

Correct: C — No, metal building parts cannot be used as the bonding means for sign metal parts

600.7(B)(3) specifically prohibits using metal building parts as a bonding means for sign or outline lighting metal parts or equipment, regardless of the girt's continuity or its own bonding status. A dedicated bonding conductor per 600.7(B)(1) and (B)(7) is required instead.

Branch circuit ampere ratings for neon vs. other signs

NEC 600.5(C)

Neon tubing branch circuits max out at 30 A; every other sign or outline lighting circuit maxes out at 20 A, and both count as continuous loads.

Q4 NEC 600.5(C)

What is the maximum ampere rating permitted for a branch circuit supplying a neon tubing installation?

  1. A 50 amperes
  2. B 30 amperes
  3. C 25 amperes
  4. D 20 amperes
Show answer & explanation

Correct: B — 30 amperes

Per 600.5(C)(1), branch circuits supplying neon tubing installations shall not be rated in excess of 30 amperes. The 20 A figure is the limit for all other signs and outline lighting systems under 600.5(C)(2), not neon.

Equipment grounding conductor rules for sign metal parts

NEC 600.7(A)

Metal sign parts, outline lighting, and skeleton tubing must bond to a 250.118 equipment grounding conductor sized per 250.122 — building steel can never fill that role.

Q5 NEC 600.7(A)

An electrician is installing a sign against a steel-framed building and plans to bond the sign's metal parts to the building's structural steel instead of running an equipment grounding conductor. Is this acceptable under 600.7?

  1. A No, unless the sign is cord-and-plug connected
  2. B No, metal parts of a building are not permitted as an equipment grounding conductor or secondary return conductor
  3. C Yes, structural steel is always a listed grounding electrode
  4. D Yes, but only if the steel is continuous from the service equipment
Show answer & explanation

Correct: B — No, metal parts of a building are not permitted as an equipment grounding conductor or secondary return conductor

600.7(A)(5) specifically prohibits using metal building parts as a secondary return conductor or equipment grounding conductor for signs. The sign must instead connect to a proper 250.118 equipment grounding conductor per 600.7(A)(1); building steel continuity doesn't change this, and the cord-and-plug exception in 600.7(A)(1) is unrelated to this rule.

Sign mounting height, pedestrian protection, and combustible clearance

NEC 600.9

Signs need 14 ft of vehicle clearance (or damage protection), physical protection for exposed neon near pedestrians, and a 2-in. gap from combustible material near incandescent or HID lamps.

Q6 NEC 600.9

A business owner wants to mount an illuminated sign above a driveway where delivery trucks pass. What is the minimum mounting height to avoid needing extra physical protection?

  1. A 3.0 m (10 ft)
  2. B 3.7 m (12 ft)
  3. C 5.5 m (18 ft)
  4. D 4.3 m (14 ft)
Show answer & explanation

Correct: D — 4.3 m (14 ft)

Per 600.9(A), sign or outline lighting equipment must be at least 4.3 m (14 ft) above vehicle-accessible areas unless protected from physical damage. 10 ft and 12 ft are below that threshold and would require added protection; 18 ft exceeds the requirement unnecessarily.

Where sign supply wiring must terminate: boxes, enclosures, poles

NEC 600.5(D)

Sign supply wiring must terminate in the sign itself, an outline lighting enclosure, a suitable box, a conduit body, or a panelboard — never left open.

Q7 NEC 600.5(D)

Per 600.5(D)(1), where is a wiring method supplying a sign permitted to terminate?

  1. A A sign, an outline lighting system enclosure, a suitable box, a conduit body, or a panelboard
  2. B Only inside the sign itself, per manufacturer instructions
  3. C A suitable box only, with the sign enclosure treated as a separate disconnect location
  4. D Any weatherproof junction box mounted within 6 ft of the sign
Show answer & explanation

Correct: A — A sign, an outline lighting system enclosure, a suitable box, a conduit body, or a panelboard

600.5(D)(1) lists five acceptable termination points: a sign, an outline lighting system enclosure, a suitable box, a conduit body, or a panelboard. Limiting termination to only the sign itself, to any nearby weatherproof box, or excluding the sign enclosure all narrow the rule incorrectly.

Selecting Class 2 sign cable by installation location

NEC 600.33(A)

Class 2 sign secondary wiring must be listed cable sized at least 18 AWG, with the cable type driven by where it runs — general space, plenum/riser, wet, or sunlight.

Q8 NEC 600.33(A)

A Class 2 sign secondary conductor runs through a vertical riser shaft connecting several floors. Which cable designation satisfies this location?

  1. A CL2P
  2. B CL2R
  3. C Any CL2 general-use cable regardless of riser marking
  4. D PLTC without sunlight-resistant marking
Show answer & explanation

Correct: B — CL2R

Per 600.33(A)(2), vertical shafts and risers require CL2R or CL3R. CL2P is the plenum/environmental air space designation, not the riser designation, so it doesn't satisfy this specific location requirement. General-use CL2 cable is for 600.33(A)(1) locations and is not automatically suitable for a riser unless it carries the riser rating.

Installing, protecting, and grounding Class 2 sign wiring

NEC 600.33(B)

Secondary sign wiring must be neatly supported every 6 ft, spliced only in listed enclosures, shielded from physical damage, and grounded per 600.7.

Q9 NEC 600.33(B)

An electrician splices secondary sign wiring conductors inside a wall cavity. Per 600.33(B)(2), what is required?

  1. A The connection must be relocated outside the wall entirely
  2. B The connection must be wrapped in listed insulating tape only, no box required
  3. C The connection may be buried in the wall without access as long as it is soldered
  4. D The connection must be enclosed in a listed box
Show answer & explanation

Correct: D — The connection must be enclosed in a listed box

600.33(B)(2) requires connections made in a wall to be enclosed in a listed box, in addition to using listed insulating devices and remaining accessible after installation. Tape alone isn't sufficient inside a wall, relocating outside the wall isn't required by this rule, and burying an inaccessible splice violates the accessibility requirement.

Class 2 power source listing, grounding, and wiring requirements

NEC 600.24

A Class 2 sign power source must be listed for sign use, have its metal parts bonded to equipment ground, and split its wiring rules at the transformer: Chapter 3 on the supply side, Class 2 rules on the load side.

Q10 NEC 600.24 Code lookup

An electric sign uses a listed Class 2 power source to feed low-voltage LED modules. The installer wants to confirm the power source's metal enclosure is bonded correctly — which section requires that the metal parts of the Class 2 power supply be connected to the equipment grounding conductor?

  1. A 600.23(B)
  2. B 600.24(A)
  3. C 600.24(B)
  4. D 600.24(C)
Show answer & explanation

Correct: C — 600.24(B)

600.24(B) is the specific rule requiring metal parts of a Class 2 power supply/source to be connected to the equipment grounding conductor. 600.24(A) only covers listing requirements, and 600.23(B) governs ground-fault protection for Class 1 transformer/electronic power supply secondary circuits, not Class 2 bonding.

Electrode enclosure, receptacle, and bushing listing by location

NEC 600.42(H)

Every neon electrode part — enclosure, receptacle, bushing — must be listed, and enclosures used in damp or wet locations need a listing specific to that exposure.

Q11 NEC 600.42(H)

An electrode enclosure for a neon sign is listed, labeled, and identified only for dry locations. Where can it be installed?

  1. A In any location, since all electrode enclosures must be listed anyway
  2. B In wet locations if a listed cap is also used
  3. C In dry or damp locations, but not wet
  4. D In dry locations only
Show answer & explanation

Correct: D — In dry locations only

Per 600.42(H)(2), enclosures installed in damp and wet locations must be specifically listed, labeled, and identified for those locations. A dry-location-only listing does not extend to damp or wet use, and adding a listed cap under 600.42(G) addresses sealing a penetration, not the enclosure's location rating.

Spacing, insulators, and raceway clearance for high-voltage secondary conductors

NEC 600.32(E)

Neon secondary conductors need at least 38 mm of air spacing from everything but insulators, listed insulators/bushings above 1000 volts, and 65 mm of insulation past any raceway end.

Q12 NEC 600.32(E)

A neon sign installer is running secondary conductors across a ceiling cavity, supported by listed insulators. What minimum spacing must be maintained from other objects, aside from the insulators themselves?

  1. A 65 mm (2 1/2 in.)
  2. B 38 mm (1 1/2 in.)
  3. C No minimum spacing is required as long as listed insulators are used
  4. D 150 mm (6 in.)
Show answer & explanation

Correct: B — 38 mm (1 1/2 in.)

600.32(E) requires secondary conductors to be separated from each other and from all objects other than insulators or neon tubing by not less than 38 mm. The 65 mm figure is a different requirement — that's the minimum insulation extension beyond a raceway under 600.32(G) — and spacing is required regardless of insulator use.

GTO cable rating, physical protection, and bend limits

NEC 600.32(B)

Secondary sign conductors must be listed GTO cable rated 5, 10, or 15 kV, at least 18 AWG, protected from physical damage, and installed without sharp bends.

Q13 NEC 600.32(B) Code lookup

You're wiring a neon sign secondary circuit rated over 1000 volts and need to select GTO cable. Which section specifies the required voltage rating options, minimum conductor size, and minimum insulation temperature rating for this cable?

  1. A 600.32(E)
  2. B 600.32(B)
  3. C 600.32(A)(3)
  4. D 600.32(C)
Show answer & explanation

Correct: B — 600.32(B)

600.32(B) is the section titled Insulation and Size — it lists the 5, 10, or 15 kV ratings, the 18 AWG minimum, and the 105°C minimum temperature rating for GTO cable. 600.32(A)(3) instead covers size requirements for the general secondary-circuit wiring methods of 600.32(A), not the GTO cable's own insulation/size spec, and 600.32(C) and 600.32(E) address installation protection and spacing, not conductor rating or size.

Maximum lamp wattage marking for incandescent lampholders

NEC 600.4(C)

Incandescent lampholders in signs and outline lighting must carry a permanent maximum-wattage marking, letters at least 6 mm (1/4 in.) tall, visible during relamping.

Q14 NEC 600.4(C)

Under 600.4(C), what information must be marked at an incandescent lampholder used in a sign or outline lighting system?

  1. A The voltage rating of the branch circuit supplying the sign
  2. B The manufacturer's UL listing number
  3. C The maximum allowable lamp wattage per lampholder
  4. D The date the sign was installed
Show answer & explanation

Correct: C — The maximum allowable lamp wattage per lampholder

600.4(C) requires the marking to state the maximum allowable lamp wattage per lampholder. A listing number, install date, and circuit voltage are not what this specific marking requirement calls for.

Neon secondary wiring, 1000V or less

NEC 600.31(A)

Neon secondary conductors rated 1000V or less use any Chapter 3 wiring method, but must be listed, insulated, at least 18 AWG, protected from damage, and bushed through metal openings.

Q15 NEC 600.31(A)

For a neon secondary circuit rated 1000 volts or less, which wiring method is permitted?

  1. A Only a dedicated neon-rated raceway listed specifically for sign secondary circuits
  2. B Only rigid metal conduit, to ensure adequate physical protection
  3. C Open wiring on insulators only, as required for high-voltage neon secondaries
  4. D Any wiring method included in Chapter 3 that is suitable for the conditions
Show answer & explanation

Correct: D — Any wiring method included in Chapter 3 that is suitable for the conditions

600.31(A) permits any Chapter 3 wiring method suitable for the conditions of installation — there's no restriction to a special neon-only method, open wiring, or a single conduit type. Those more restrictive options are confusions with higher-voltage neon secondary rules elsewhere in Article 600.

Neon tubing design load, support, spacing, and protection

NEC 600.41(A)

Neon tubing must never overload its transformer, must be supported within 6 in. of each electrode, kept 1/4 in. off any surface, and guarded if accessible to the public.

Q16 NEC 600.41(A)

Per 600.41(C), what is the minimum spacing required between neon tubing and the nearest surface other than its support?

  1. A 13 mm (1/2 in.)
  2. B 6 mm (1/4 in.)
  3. C 25 mm (1 in.)
  4. D 38 mm (1 1/2 in.)
Show answer & explanation

Correct: B — 6 mm (1/4 in.)

600.41(C) sets the minimum air space at 6 mm (1/4 in.) between the tubing and any nearby surface, excluding the support itself. The larger spacings are common clearance figures used elsewhere in the Code but aren't the neon tubing spacing value.

Portable and mobile sign support, cords, and GFCI protection

NEC 600.10

Portable and mobile signs must be tool-free movable, cord-and-plug connected, GFCI-protected, and use cord types and lengths matched to wet/damp versus dry locations.

Q17 NEC 600.10

Where must the GFCI protection required for a cord-and-plug portable sign be located?

  1. A Integral to the attachment plug, or in the cord within 300 mm (12 in.) of the plug
  2. B At the panelboard supplying the circuit
  3. C At the disconnecting means for the sign
  4. D Anywhere on the branch circuit ahead of the sign's receptacle outlet
Show answer & explanation

Correct: A — Integral to the attachment plug, or in the cord within 300 mm (12 in.) of the plug

600.10(C)(2) requires the manufacturer-provided GFCI to be integral to the attachment plug or located in the power-supply cord within 300 mm (12 in.) of the plug. A GFCI elsewhere on the circuit, at the disconnect, or at the panelboard does not meet this specific placement requirement, even though 210.8 GFCI protection may also apply elsewhere.

Installing power supplies in attics, soffits, and suspended ceilings

NEC 600.21(E)

Sign ballasts and power supplies in attics/soffits need a code-size access door, a walkway to each unit, and switched lighting; above suspended ceilings the enclosure must be independently supported and hard-wired, never cord-connected.

Q18 NEC 600.21(E)

A sign transformer is installed in an attic space. Which of the following is required by 600.21(E)?

  1. A A second lighting outlet located at least 3 m (10 ft) from the equipment
  2. B A passageway at least 900 mm (3 ft) wide and 600 mm (2 ft) high
  3. C A point of control located at the equipment only, not at the entry
  4. D A permanent walkway at least 300 mm (12 in.) wide extending to the component
Show answer & explanation

Correct: D — A permanent walkway at least 300 mm (12 in.) wide extending to the component

600.21(E) requires a permanent walkway at least 300 mm (12 in.) wide extending from the point of entry to each component. The passageway dimensions are reversed in the second distractor — it's 900 mm (3 ft) high by 600 mm (2 ft) wide, not the other way around. Only one lighting outlet is required, not two, and the point of control must be at the usual point of entry, not only at the equipment.

Siting ballasts, transformers, and power supplies: access and wet locations

NEC 600.21(A)

Sign power sources must be enclosed, accessible, fastened in place, mounted as close to the lamps or tubing as practical, and weatherproof or protected if used outdoors.

Q19 NEC 600.21(A)

An electronic power supply for a sign is mounted inside the sign cabinet but buried behind permanently fixed panels with no way to reach it for service. Which requirement does this violate?

  1. A The accessibility requirement of 600.21(A)
  2. B The wet location requirement of 600.21(C)
  3. C The self-contained enclosure requirement of 600.21
  4. D The proximity-to-load requirement of 600.21(B)
Show answer & explanation

Correct: A — The accessibility requirement of 600.21(A)

600.21(A) requires ballasts, transformers, electronic power supplies, and Class 2 power sources to be located where accessible and securely fastened in place. Burying one behind fixed panels blocks access, which is separate from the enclosure rule in 600.21, the proximity rule in 600.21(B), or the wet-location rule in 600.21(C), none of which are at issue here.

PV sign equipment listing and field wiring requirements

NEC 600.34(B)

PV-powered sign equipment must be listed for PV use, and external wiring must be listed for PV applications, closely routed, secured every 3 ft, and protected from damage.

Q20 NEC 600.34(B)

Which requirement applies to wiring routed external to a PV-powered sign's body under 600.34(B)?

  1. A It must be run in rigid metal conduit for its entire length
  2. B It must be secured at intervals not exceeding 1.5 m (5 ft)
  3. C It may be routed away from the sign body if labeled for outdoor use
  4. D It must be secured at intervals not exceeding 0.91 m (3 ft)
Show answer & explanation

Correct: D — It must be secured at intervals not exceeding 0.91 m (3 ft)

600.34(B)(3) requires external PV sign wiring to be as short as possible and secured at intervals not exceeding 0.91 m (3 ft). There's no rigid-conduit mandate in this section, the wiring must closely follow the sign body per 600.34(B)(2) rather than being routed away from it, and 1.5 m (5 ft) is not the specified interval.

PV sign grounding, disconnects, and battery compartment access

NEC 600.34(D)

A PV powered sign must meet Article 690's grounding and disconnect rules on top of the normal sign rules, and its battery compartment must require a tool to open.

Q21 NEC 600.34(D)

Besides 600.7, what must the grounding of a photovoltaic powered sign comply with?

  1. A Article 690, Part V
  2. B Article 690, Part III
  3. C No additional article — 600.7 alone governs
  4. D Article 250 in place of 600.7
Show answer & explanation

Correct: A — Article 690, Part V

600.34(D) requires PV sign grounding to comply with Article 690, Part V, in addition to 600.7. Article 690, Part III covers disconnecting means, not grounding, and is the cross-reference used for 600.34(E) instead. Skipping the Article 690 reference and relying on 600.7 alone would miss the PV-specific grounding provisions.

Retrofit kit listing, damaged-part repair, and marking

NEC 600.35(A)

A sign retrofit kit must be listed and labeled, every unreplaced part must be inspected and any damage fixed to preserve the sign's location rating, and the finished sign must be marked per 600.4(B).

Q22 NEC 600.35(A)

A retrofit kit replaces a sign's LED modules and driver, but the original housing is left untouched. Under 600.35(B), what must happen to the housing?

  1. A No action is needed since the kit's listing covers the whole sign assembly
  2. B Inspection is only required if the housing is more than 10 years old
  3. C Inspection is only required if the sign is installed in a wet location
  4. D It must still be inspected for damage even though it wasn't replaced
Show answer & explanation

Correct: D — It must still be inspected for damage even though it wasn't replaced

600.35(B) requires all parts not replaced by the kit to be inspected for damage, with no exception based on the kit's listing scope, the sign's location rating, or the age of the part.

Routing secondary sign wiring by voltage class (≤1000V, >1000V, Class 2)

NEC 600.12

Field-installed secondary wiring for signs splits into three paths by voltage and power source: 1000V or less follows 600.31, over 1000V follows 600.32, and Class 2 output follows 600.33 with a choice of Chapter 3 methods or listed Class 2 cable.

Q23 NEC 600.12

An electrician is field-wiring the secondary circuit of a neon sign transformer rated at 1200 volts. Which NEC section applies?

  1. A 600.32
  2. B 600.24
  3. C 600.31
  4. D 600.33
Show answer & explanation

Correct: A — 600.32

Per 600.12(B), neon secondary circuit wiring over 1000 volts must comply with 600.32. The 600.31 path applies only at 1000 volts or less under 600.12(A). 600.24 and 600.33 apply to Class 2 output systems under 600.12(C), not to a 1200-volt neon secondary.

Bonding signs and outline lighting installed in fountains

NEC 600.7(B)(8)

Metal parts of a sign or outline lighting mounted inside a fountain must bond to the recirculating system's equipment grounding conductor, as close to the fountain as practicable.

Q24 NEC 600.7(B)(8)

Outline lighting is installed inside a decorative fountain. Per 600.7(B)(8), all metal parts of the outline lighting must be bonded to what?

  1. A A dedicated ground rod driven near the fountain
  2. B The equipment grounding conductor of the nearest exterior receptacle circuit
  3. C The equipment grounding conductor of the branch circuit for the fountain's recirculating system
  4. D The grounded (neutral) conductor of the fountain circuit
Show answer & explanation

Correct: C — The equipment grounding conductor of the branch circuit for the fountain's recirculating system

600.7(B)(8) requires bonding to the equipment grounding conductor of the branch circuit that feeds the fountain recirculating system. A separate ground rod, the neutral conductor, and an unrelated receptacle's equipment grounding conductor are not acceptable bonding points.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access