Free NEC practice test · Article 620

Elevators and Escalators practice questions

A free NEC Article 620 practice test for the journeyman exam: 28 questions on Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts, each with the answer and the why behind it.

28 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 28 journeyman-exam practice questions cover NEC Article 620 across 28 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Duty ratings and overload protection for elevator/escalator/lift driving motors

NEC 620.61(B)

Elevators, dumbwaiters, and platform lifts run intermittent duty and use 430.33; escalators and moving walks run continuous duty and use 430.32 with Table 430.37.

Q1 NEC 620.61(B) Code lookup

An elevator's driving machine motor is being sized for overload protection. Which section establishes that this motor's duty is rated intermittent and permits it to be protected per 430.33?

  1. A 620.61(B)(3)
  2. B 620.61(B)(1)
  3. C 620.61(B)(4)
  4. D 620.61(B)(2)
Show answer & explanation

Correct: B — 620.61(B)(1)

620.61(B)(1) covers elevator, dumbwaiter, and motor-generator set driving motors, rating their duty as intermittent and allowing 430.33 protection. 620.61(B)(4) governs the same intermittent/430.33 scheme but only for platform lifts and stairway chairlifts, not elevators.

Disconnect location relative to the motor controller, by equipment type

NEC 620.51(C)

The disconnecting means must be within sight of the motor controller — except when the controller sits in the hoistway, which forces an outside-hoistway disconnect plus an additional lockable switch within sight of the controller.

Q2 NEC 620.51(C)

On an elevator without generator field control, the motor controller is installed inside the hoistway. Where must the disconnecting means required by 620.51(A) be located?

  1. A Outside the hoistway, accessible only to qualified persons
  2. B Within sight of the motor controller, inside the hoistway
  3. C Adjacent to the driving machine only, with no separate switch required
  4. D In the space where the controller is located, same as an escalator
Show answer & explanation

Correct: A — Outside the hoistway, accessible only to qualified persons

Per 620.51(C)(1), when the motor controller sits in the hoistway, the disconnect required by 620.51(A) must be located outside the hoistway and accessible to qualified persons only — an additional lockable switch is then required within sight of the controller. The 'within sight, inside the hoistway' option ignores this exception, and the escalator-style same-space rule belongs to 620.51(C)(3), not elevators.

Main power disconnect: single means and required type

NEC 620.51

Each elevator, escalator, moving walk, or lift needs one lockable-open, listed, enclosed fused switch or breaker disconnecting all ungrounded main supply conductors — never the required branch circuits.

Q3 NEC 620.51

What must be true about the disconnecting means for an elevator's main power supply conductors?

  1. A It must be a single means designed so no pole can be operated independently
  2. B A separate disconnect is required for each driving machine when multiple machines share one elevator
  3. C It must also disconnect the branch circuits required in 620.22 through 620.24
  4. D It may be any general-use switch as long as it is accessible
Show answer & explanation

Correct: A — It must be a single means designed so no pole can be operated independently

620.51 requires a single disconnecting means for all ungrounded main power conductors, designed so no pole operates independently. It explicitly must not disconnect the required branch circuits, and multiple driving machines still share one disconnect for the motors and control valve operating magnets, not separate ones.

GFCI receptacles in elevator/escalator spaces

NEC 620.6

Every 125-volt, 15- or 20-amp receptacle in an elevator, escalator, or lift space needs listed Class A GFCI protection — no exceptions by room type.

Q4 NEC 620.6

A 125-volt, 20-ampere receptacle is installed in an elevator machine room. What does 620.6(B) require?

  1. A Listed Class A ground-fault circuit-interrupter protection
  2. B No special protection because the room is normally locked and access-restricted
  3. C AFCI protection only, since it is not a wet location
  4. D Standard GFCI protection of any listed class
Show answer & explanation

Correct: A — Listed Class A ground-fault circuit-interrupter protection

620.6(B) requires listed Class A GFCI protection for all 125-volt, single-phase, 15- and 20-ampere receptacles in machine rooms, control spaces, machinery spaces, control rooms, and truss interiors. Restricted access does not remove the requirement, and the rule specifically calls for Class A, not just any GFCI class.

Minimum conductor sizes in traveling cables by circuit type

NEC 620.12(A)

Traveling cables set a different minimum wire size for each circuit type — 14 AWG for lighting, 24 AWG for communications, and 20 AWG for everything else, with limited paralleling allowed.

Q5 NEC 620.12(A)

In a traveling cable, what is the minimum conductor size permitted for a lighting circuit if a single conductor is used?

  1. A 24 AWG copper
  2. B 20 AWG copper
  3. C 16 AWG copper
  4. D 14 AWG copper
Show answer & explanation

Correct: D — 14 AWG copper

620.12(A)(1) sets 14 AWG copper as the minimum for lighting circuits in traveling cables, with 20 AWG or larger conductors allowed in parallel only if the combined ampacity equals at least that of 14 AWG copper. The 20 AWG and 24 AWG sizes are the minimums for other circuits and communications circuits, respectively, not lighting circuits run as a single conductor.

Wiring methods for elevator hoistways, cars, and counterweights

NEC 620.21(A)

Default to rigid raceway or MC/MI/AC cable everywhere in the hoistway system, but flexible conduit and cord are allowed in short 1.8 m (6 ft) runs at cars, counterweights, and machine rooms.

Q6 NEC 620.21(A)

Under 620.21, which wiring is exempt from the requirement to be installed in rigid conduit, EMT, rigid nonmetallic conduit, wireways, or Type MC, MI, or AC cable?

  1. A Conductors installed in the hoistway pit for general lighting
  2. B Conductors run in the control space serving the elevator controller
  3. C Fixed wiring inside the machine room between the disconnecting means and control panel
  4. D Traveling cables connecting the car or counterweight and hoistway wiring
Show answer & explanation

Correct: D — Traveling cables connecting the car or counterweight and hoistway wiring

620.21 explicitly excludes traveling cables connecting the car or counterweight and hoistway wiring from the raceway/cable requirement. Fixed wiring in the machine room, hoistway pit lighting conductors, and control-space conductors are all covered by the general rule unless one of the (A)–(C) exceptions applies.

Wiring methods for platform lifts and stairway chairlifts

NEC 620.21(C)

Runways and machinery spaces for platform lifts and stairway chairlifts allow FMC/LFMC, Class 2 cables, and short flexible cords, each with its own length and voltage limits.

Q7 NEC 620.21(C)

A platform lift installation needs flexible metal conduit run more than 1.8 m (6 ft) in the runway at metric designator 12 (trade size 3/8). What must be used instead?

  1. A Metric designator 12 or larger LFNC-B
  2. B Liquidtight flexible metal conduit at metric designator 12, run in a straight line to avoid the limit
  3. C Type CL3 cable run alongside the conduit
  4. D Standard FMC at metric designator 12, since the length cap only applies to LFMC
Show answer & explanation

Correct: A — Metric designator 12 or larger LFNC-B

Per 620.21(C)(1), metric designator 12 (trade size 3/8) FMC or LFMC is capped at 1.8 m (6 ft); to exceed that length, metric designator 12 or larger LFNC-B is permitted instead. The length cap applies to both FMC and LFMC equally, not just LFMC, and CL3 cable is not the wiring method addressed by this length exception.

What wiring is allowed inside hoistways and machine/control spaces

NEC 620.37(A)

Only wiring that's directly tied to the elevator or dumbwaiter itself — signals, car communication, fire detection, pit sump pumps, and its own heating/lighting/ventilating — is allowed inside the hoistway, machine room, control room, machinery space, or control space.

Q8 NEC 620.37(A)

Under 620.37(A), which of the following wiring uses is permitted inside an elevator hoistway?

  1. A A feeder supplying an unrelated tenant electrical panel
  2. B A branch circuit for a building fire alarm panel unrelated to the elevator
  3. C Fire detection system wiring for the elevator
  4. D General-purpose receptacle wiring for building maintenance tools
Show answer & explanation

Correct: C — Fire detection system wiring for the elevator

620.37(A) permits wiring for fire detection systems connected with the elevator. Wiring for unrelated building systems — a general building fire alarm panel, general-purpose receptacles, or a feeder to unrelated equipment — is not on the permitted list and doesn't belong in the hoistway per 620.37(A).

Motor branch-circuit short-circuit and ground-fault protection for elevators and escalators

NEC 620.61(D)

Elevator, escalator, and moving walk motors don't get their own short-circuit/ground-fault protection rules — 620.61(D) sends you straight to Article 430, Part IV.

Q9 NEC 620.61(D) Code lookup

An elevator machine room has a motor branch circuit feeding a single elevator drive motor. You need to size the short-circuit and ground-fault protective device for that branch circuit. Which section tells you where to find the applicable requirements?

  1. A 620.61(D)
  2. B 620.61(B)
  3. C 620.62
  4. D 620.61(C)
Show answer & explanation

Correct: A — 620.61(D)

620.61(D) directs short-circuit and ground-fault protection for the motor branch circuit to Article 430, Part IV. 620.61(B) governs overload protection (a different fault type) and 620.61(C) covers feeder-level protection, not the branch circuit to the motor.

Overcurrent protection for operating, control, and signaling circuits

NEC 620.61(A)

Elevator operating, control, and signaling circuits aren't protected like power feeders — Class 1 circuits follow 724.43 and 724.45, and Class 2 power-limited circuits follow Chapter 9's Notes to Tables 11(A) and 11(B).

Q10 NEC 620.61(A)

Per 620.61(A), overcurrent protection for an elevator's operating devices and control/signaling circuits is provided in accordance with which requirements?

  1. A Article 725 in its entirety
  2. B 724.43 and 724.45
  3. C Article 240, Part I general branch-circuit rules
  4. D 310.16 ampacity tables alone, with no separate overcurrent device
Show answer & explanation

Correct: B — 724.43 and 724.45

620.61(A) specifically names 724.43 and 724.45 (Class 1 circuit overcurrent rules) for operating devices and control/signaling circuits. Article 725 covers Class 2/3 circuits generally, but 620.61(A) instead sends Class 2 power-limited circuits to Chapter 9's table notes, not to Article 725's text. Standard Article 240 branch-circuit sizing doesn't apply to this small-wire control wiring.

Selective coordination of driving machine overcurrent devices

NEC 620.62

When multiple driving machine disconnects share a source, their overcurrent devices must be selectively coordinated with upstream devices, documented, and field-marked with a caution label.

Q11 NEC 620.62 Code lookup

A hospital elevator bank has three driving machine disconnecting means fed from the same service, each with its own overcurrent device. During design, the engineer must ensure that a fault on one elevator's branch circuit trips only that elevator's device without opening any upstream device shared with the other elevators. Which section requires this coordination to be engineered and documented?

  1. A 620.65
  2. B 620.61(D)
  3. C 620.61(C)
  4. D 620.62
Show answer & explanation

Correct: D — 620.62

620.62 is the section requiring selective coordination between overcurrent devices supplied by the same source when more than one driving machine disconnecting means is involved, including engineering selection and documentation. 620.61(C) and (D) only set short-circuit/ground-fault protection sizing for feeders and branch circuits, not coordination between devices; 620.65 only covers marking equipment once coordination has already been established.

Dedicated branch circuits for car lighting, ventilation, and HVAC

NEC 620.22

Elevator car lights and car air-conditioning/heating each need their own separate branch circuit, with the overcurrent device kept out of the hoistway unless no machine room exists outside it.

Q12 NEC 620.22

Per 620.22, how must an elevator car's lighting and its air-conditioning/heating units be circuited?

  1. A On separate, dedicated branch circuits
  2. B On the same circuit as long as it is GFCI protected
  3. C On the same branch circuit, since both serve the same car
  4. D On separate circuits only if the car exceeds a certain horsepower rating
Show answer & explanation

Correct: A — On separate, dedicated branch circuits

620.22(A) and 620.22(B) each independently require 'a separate branch circuit' — one for car lights/ventilation, one for car air-conditioning and heating. There is no allowance to combine them onto one circuit, with or without GFCI protection, and no horsepower exception is given in this section.

Sizing conductors for a single motor controller or power transformer

NEC 620.13(B)

Size conductors to a single controller or transformer at no less than its nameplate current rating plus any other connected loads.

Q13 NEC 620.13(B) Code lookup

An elevator machine room has a single motor controller feeding the drive machine, plus a small connected control-system load. When sizing the conductors that supply just this one motor controller, which section specifies the minimum ampacity required?

  1. A 620.13(A)
  2. B 620.12(B)
  3. C 620.13(B)
  4. D 620.13(D)
Show answer & explanation

Correct: C — 620.13(B)

620.13(B) directly addresses conductors supplying a single motor controller, requiring ampacity not less than the controller's nameplate current rating plus other connected loads. 620.13(A) covers a single motor (not its controller), and 620.13(D) applies only when more than one motor, controller, or transformer is fed by the same conductors.

Flame-retardant insulation requirements for elevator conductors

NEC 620.11

Every conductor in elevator raceways needs flame-retardant insulation, rated at least for the highest voltage present in that raceway or enclosure.

Q14 NEC 620.11

A raceway carries elevator conductors from several circuits at different voltages. Per 620.11(D), how must the insulation voltage rating of each conductor be determined?

  1. A Based on the average voltage of all circuits in the raceway
  2. B Based on the voltage of the lowest-rated conductor present, per manufacturer listing
  3. C Based on that conductor's own circuit voltage only
  4. D Based on the maximum nominal circuit voltage of any conductor within the same enclosure, cable, or raceway
Show answer & explanation

Correct: D — Based on the maximum nominal circuit voltage of any conductor within the same enclosure, cable, or raceway

620.11(D) requires every conductor's insulation to be rated for at least the maximum nominal circuit voltage present anywhere in the shared enclosure, cable, or raceway — not just its own circuit's voltage. Sizing to the conductor's own circuit voltage ignores higher-voltage neighbors sharing the raceway, and there's no NEC provision for averaging or matching the lowest-rated conductor.

Elevator disconnect: no remote operation, sprinklers may trip it open only

NEC 620.51(B)

The elevator disconnecting means can never be opened or closed from elsewhere in the building — sprinklers may trip it open before water hits, but restoration is always manual.

Q15 NEC 620.51(B)

Sprinklers are installed in an elevator machine room. Per 620.51(B), what is the elevator disconnecting means permitted to do because of this?

  1. A Automatically open the power supply before water is applied
  2. B Automatically cycle open and closed to test elevator response
  3. C Automatically close once the sprinkler flow stops
  4. D Be operated remotely from a fire command center
Show answer & explanation

Correct: A — Automatically open the power supply before water is applied

620.51(B) permits the disconnect to automatically open ahead of water application when sprinklers protect the machine room (or hoistway, control room, machinery space, control space). It never permits automatic closing, and remote operation from elsewhere in the premises is prohibited outright.

Bonding requirements for elevators, escalators, and lifts

NEC 620.82

Every elevator, escalator, moving walk, platform lift, and stairway chairlift bonds its metal parts back to the equipment grounding conductor per Article 250, Parts V and VII.

Q16 NEC 620.82

Under 620.82, which of the following must be bonded on an electric elevator?

  1. A Only the car's metal enclosure, not equipment in the machine room or hoistway
  2. B The frames of motors, elevator machines, and controllers, plus metal enclosures for electrical equipment in or on the car or in the hoistway
  3. C Only equipment physically mounted inside the hoistway, not equipment on the car itself
  4. D Only equipment operating above 600 volts
Show answer & explanation

Correct: B — The frames of motors, elevator machines, and controllers, plus metal enclosures for electrical equipment in or on the car or in the hoistway

620.82 requires bonding of motor frames, elevator machine frames, controller frames, and metal enclosures for all electrical equipment in or on the car or in the hoistway — it's not limited to one location or voltage class.

Voltage limits for elevator/escalator circuits

NEC 620.3

Elevator supply voltage caps at 300V unless the circuit type falls under a listed exception allowing up to 1000V.

Q17 NEC 620.3

Under Article 620, what is the maximum voltage between conductors for an elevator supply circuit unless a specific exception applies?

  1. A 1000 volts
  2. B 300 volts
  3. C 600 volts
  4. D 120 volts
Show answer & explanation

Correct: B — 300 volts

620.3 sets the general limit at 300 volts between conductors unless 620.3(A) through (C) permits a higher voltage. The 600-volt and 1000-volt figures are thresholds and allowances that appear only within the power-circuit and HVAC-circuit exceptions, not the baseline rule.

Applying feeder demand factors to reduce elevator feeder ampacity

NEC 620.14

A feeder supplying multiple elevators can be sized below the full-load ampacity of 620.13, but only by the exact demand factor Table 620.14 gives for that number of cars.

Q18 NEC 620.14 Code lookup

An elevator installation has multiple cars on a common feeder, and the calculated load per 620.13 would require a larger feeder than the designer wants to install. Which section allows the feeder conductors to be sized smaller than 620.13 requires, based on a demand factor table?

  1. A 620.12(A)(4)
  2. B 620.14
  3. C 620.15
  4. D 620.13(D)
Show answer & explanation

Correct: B — 620.14

620.14 is the section that permits feeder conductors of less ampacity than 620.13 requires, subject to Table 620.14's demand factors. 620.13(D) governs sizing conductors for multiple motors/controllers/transformers without any demand reduction, and 620.15 addresses motor controller rating, not feeder demand.

Branch circuits for hoistway pit lighting and receptacles

NEC 620.24

The hoistway pit needs its own dedicated lighting-and-receptacle branch circuit, a switch reachable from the pit door, and a 125-volt duplex receptacle — and the lighting can't ride the load side of a GFCI.

Q19 NEC 620.24

An electrician is wiring lighting and a receptacle for an elevator hoistway pit. Which arrangement violates 620.24(A)?

  1. A The required pit lighting is connected to the load side of a GFCI device
  2. B The pit lighting circuit is kept separate from the elevator machine circuit
  3. C The pit receptacle is on the same dedicated circuit as the pit lighting
  4. D A dedicated branch circuit feeds only the pit lighting and receptacle
Show answer & explanation

Correct: A — The required pit lighting is connected to the load side of a GFCI device

620.24(A) specifically prohibits connecting the required pit lighting to the load side of a ground-fault circuit interrupter. A separate branch circuit for the pit lighting and receptacle, even one shared between the two, is exactly what the section requires — it's only the GFCI load-side connection for lighting that's barred.

Branch circuits for machine room, control room, and truss interior lighting/receptacles

NEC 620.23

Lighting and receptacles in elevator machine rooms, control rooms, control spaces, and truss interiors must be on separate branch circuits, with lighting fed ahead of any GFCI.

Q20 NEC 620.23

An elevator machinery space has one branch circuit feeding both the lighting and the duplex receptacle. Does this comply with 620.23?

  1. A Yes, as long as the combined load stays under the circuit rating
  2. B Yes, because machinery spaces are exempt from the separate-circuit rule
  3. C No, but only because the space lacks a duplex receptacle in the first place
  4. D No, lighting and receptacles must be on separate branch circuits that supply no other loads
Show answer & explanation

Correct: D — No, lighting and receptacles must be on separate branch circuits that supply no other loads

620.23(A) requires the branch circuit supplying required lighting to be separate from the branch circuit supplying receptacles in machine rooms, control rooms/machinery spaces, control spaces, and truss interiors, and neither circuit may supply other loads. Combined loading staying under the circuit rating doesn't matter — the separation requirement is independent of load, and there's no exemption for machinery spaces.

Guarding elevator machine rooms and equipment access

NEC 620.71

Driving machines, generator sets, controllers, and disconnects normally live in a secured dedicated space, but controllers and certain driving machines have specific carve-outs.

Q21 NEC 620.71

A motor controller for an elevator is installed outside the dedicated machine room. Which condition satisfies 620.71(A)?

  1. A The enclosure is rated NEMA 4X and mounted at least 6 ft above the floor
  2. B The controller has a warning label instead of a locking enclosure
  3. C The controller is placed in any locked electrical closet, regardless of disconnect location
  4. D The enclosure has a lockable door and the disconnecting means is adjacent to or integral with the controller
Show answer & explanation

Correct: D — The enclosure has a lockable door and the disconnecting means is adjacent to or integral with the controller

620.71(A) permits controllers outside the dedicated space only if the enclosure has a door or removable panel capable of being locked closed AND the disconnecting means is adjacent to or an integral part of the controller. A locked closet alone, without the disconnect placement requirement, doesn't satisfy the rule, nor does an enclosure rating substitute for the locking and disconnect-location requirements.

Supporting and locating traveling cables in the hoistway

NEC 620.41

Traveling cables must be suspended by listed steel members or loop/tension supports within strict unsupported-length limits, and routed clear of anything that could damage them.

Q22 NEC 620.41

An elevator traveling cable is supported by looping it around a support. Per 620.41, what is the maximum unsupported length permitted for this method?

  1. A Up to 15 m (50 ft)
  2. B Any length, provided the cable has a steel supporting member
  3. C Up to 60 m (200 ft)
  4. D Less than 30 m (100 ft)
Show answer & explanation

Correct: D — Less than 30 m (100 ft)

620.41 permits looping cables around supports only for unsupported lengths less than 30 m (100 ft). The 60 m (200 ft) figure applies to the separate self-tightening tension support method, not looping, and looping does not require a steel supporting member (that's a distinct, third method).

Traveling cable type requirements

NEC 620.11(B)

Traveling cables linking an elevator or dumbwaiter car or counterweight to the hoistway wiring must be a listed elevator cable type per Table 400.4, or another type specifically approved for the job.

Q23 NEC 620.11(B)

Under 620.11(B), what type of cable is required for the flexible connection between an elevator car and the hoistway wiring?

  1. A Any Type S cord rated for hard or extra-hard usage
  2. B Type W cable suitable for portable power feeders
  3. C A listed elevator cable type from Table 400.4, or another approved type
  4. D Any flexible cord sized per the ampacity values in Table 400.5
Show answer & explanation

Correct: C — A listed elevator cable type from Table 400.4, or another approved type

620.11(B) requires traveling cables to be a listed elevator cable type from Table 400.4, or another type specifically approved for the application. Hard-usage cord, Type W portable power cable, and ampacity-based sizing under Table 400.5 are real provisions elsewhere in Article 400, but none satisfy the elevator-specific listing requirement in 620.11(B).

Wiring methods for escalators and moving walks

NEC 620.21(B)

Escalator and moving walk wellways allow flexible metal, liquidtight, and LFNC-B conduit, plus CL2/CL2R/CL2P cable and hard-service cords for removable control panels.

Q24 NEC 620.21(B)

An electrician runs metric designator 12 (trade size 3/8) liquidtight flexible metal conduit in an escalator wellway at a length of 2.4 m (8 ft). Is this compliant with 620.21(B)(1)?

  1. A No, because flexible conduit is never permitted in escalator wellways
  2. B Yes, because any liquidtight flexible conduit size is permitted in unlimited lengths
  3. C No, trade size 3/8 flexible or liquidtight flexible conduit is limited to 1.8 m (6 ft)
  4. D Yes, because flexible conduit in wellways has no length restriction
Show answer & explanation

Correct: C — No, trade size 3/8 flexible or liquidtight flexible conduit is limited to 1.8 m (6 ft)

Per 620.21(B)(1), flexible metal conduit or liquidtight flexible conduit of metric designator 12 (trade size 3/8) is limited to lengths not exceeding 1.8 m (6 ft). Only metric designator 12 or larger LFNC-B is permitted in lengths over 6 ft — not standard flexible metal or liquidtight flexible conduit generally, and flexible conduit is in fact permitted in wellways at all.

Working space around controllers and disconnects

NEC 620.5

Elevator and escalator equipment needs standard 110.26(A) working clearance unless it's flexible-connected, guarded, de-energized for service, or under 30V AC/60V DC.

Q25 NEC 620.5 Code lookup

An elevator machine room controller must be examined and adjusted periodically while the equipment is energized, and the technician wants to avoid the full 110.26(A) clear working space around it by relying on suitable guarding of live parts instead. Which section allows this specific exception to the working-space requirement?

  1. A 620.4
  2. B 620.5(B)
  3. C 620.5(D)
  4. D 620.5(C)
Show answer & explanation

Correct: B — 620.5(B)

620.5(B) permits skipping the 110.26(A) clearance when live parts over 30V ac rms are suitably guarded, isolated, or insulated so they can be serviced energized without removing that protection. 620.5(C) covers a different exception basis (equipment never needs to be serviced energized at all), and 620.5(D) applies only to low-voltage uninsulated parts, not guarded higher-voltage parts.

Sizing conductors supplying multiple motors/controllers/transformers

NEC 620.13(D)

For conductors feeding more than one motor, controller, or power transformer, ampacity must be at least the sum of all nameplate current ratings plus every other connected load.

Q26 NEC 620.13(D) Code lookup

A feeder is being sized to supply a group of hydraulic elevator pump motors, their controllers, and a step-down power transformer for cab lighting, all fed from the same set of conductors. Which section specifies how to size the ampacity of these feeder conductors when they supply more than one motor, motor controller, or power transformer together?

  1. A 620.14
  2. B 620.13(D)
  3. C 620.12
  4. D 620.13(A)
Show answer & explanation

Correct: B — 620.13(D)

620.13(D) governs conductors that supply more than one motor, motor controller, or power transformer, requiring ampacity not less than the sum of nameplate ratings plus other connected loads; 620.13(A) only addresses a feeder to a single motor, and 620.14 covers demand factors, not the base ampacity summation.

Sizing feeder/branch conductors for a single motor

NEC 620.13(A)

Conductors to a single elevator motor are sized from the duty-cycle percentages in Table 430.22(E), not a flat continuous-duty rule — and with generator field control, use the driving motor's nameplate current instead.

Q27 NEC 620.13(A) Code lookup

A single 40-amp nameplate elevator drive motor operates on intermittent duty. Which section provides the percentage of motor nameplate current (based on 430.22) to use when sizing the conductors that supply this single motor?

  1. A 620.13(D)
  2. B 620.13(B)
  3. C 620.12(A)(3)
  4. D 620.13(A)
Show answer & explanation

Correct: D — 620.13(A)

620.13(A) governs conductors supplying a single motor, requiring ampacity per the duty-cycle percentages in 430.22(A) and (E); 620.13(B) instead covers conductors to a single motor controller, 620.13(D) covers conductors serving more than one motor/controller/transformer, and 620.12(A)(3) addresses minimum sizing of traveling cable circuits, not feeder/branch conductor ampacity.

Disconnect for car light, receptacle, and ventilation circuits

NEC 620.53

One lockable disconnect must cut all ungrounded car light, receptacle, and ventilation power to an elevator car, numbered to match that car.

Q28 NEC 620.53 Code lookup

A traction elevator has a machine room with car lighting, a GFCI receptacle, and a 1 hp cab ventilation fan all fed from the same separate branch circuit. Which section covers the single disconnecting means required for these loads?

  1. A 620.53
  2. B 620.54
  3. C 620.51
  4. D 620.55
Show answer & explanation

Correct: A — 620.53

620.53 governs the single disconnecting means for car light, receptacle(s), and ventilation power-supply conductors, including the 430.109(C) listed/lockable option when a separate branch circuit under 2 hp ventilation supplies all three. 620.51 covers the main elevator power disconnect for the driving-machine motor, and 620.54 addresses heating/AC equipment disconnects, not car lighting/receptacle/ventilation circuits.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access