Free NEC practice test · Article 425

Industrial Process Heating practice questions

A free NEC Article 425 practice test for the journeyman exam: 16 questions on Fixed Resistance and Electrode Industrial Process Heating Equipment, each with the answer and the why behind it.

16 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 16 journeyman-exam practice questions cover NEC Article 425 across 16 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Disconnecting means for industrial process heaters — general requirements

NEC 425.19

One disconnect (or a grouped, identified set) must kill the heater, its motor controllers, and supplementary overcurrent devices simultaneously, sized at 125% of total load, lockable open, and of indicating type.

Q1 NEC 425.19

Fixed industrial process heating equipment is supplied from two separate branch circuits. Per 425.19, what must be done with the disconnecting means?

  1. A The disconnects must be grouped and identified as multiple disconnecting means
  2. B The disconnects must each be rated at 100% of their individual circuit load
  3. C Only one of the two disconnects needs to be lockable in the open position
  4. D Each disconnect can be located anywhere as long as it is within sight of the equipment
Show answer & explanation

Correct: A — The disconnects must be grouped and identified as multiple disconnecting means

425.19 requires that where heating equipment is supplied by more than one source, feeder, or branch circuit, the disconnecting means shall be grouped and identified as having multiple disconnecting means. The lockable-in-open-position requirement applies to all such disconnects, not just one, and the rating rule is 125% of total load, not 100% of an individual circuit.

Sizing conductors feeding and serving subdivided heater loads

NEC 425.22(D)

Conductors for subdivided industrial heater circuits are sized at 125% of load, dropping to 100% only if the heater is 50 kW or more, marked with a minimum conductor size, and cycled by a temperature-actuated device.

Q2 NEC 425.22(D)

Under what condition can the ampacity of field-wired conductors between a fixed industrial process heater and its supplementary overcurrent protective devices be as low as 100% of the subdivided circuit load?

  1. A The heater is rated 50 kW or more and the installation is inspected by the AHJ
  2. B The heater is marked with a minimum conductor size, regardless of kW rating
  3. C The heater is rated 50 kW or more, marked with a minimum conductor size, wired no smaller than that mark, and cyclically controlled by a temperature-actuated device
  4. D The conductors are protected by the supplementary overcurrent devices in accordance with 240.4
Show answer & explanation

Correct: C — The heater is rated 50 kW or more, marked with a minimum conductor size, wired no smaller than that mark, and cyclically controlled by a temperature-actuated device

425.22(E) permits 100% sizing only when all three conditions are met together: the heater is rated 50 kW or more, it's marked with a minimum conductor size, the conductors used are not smaller than that marked size, and a temperature-actuated device controls cyclic operation. Being marked with a minimum size alone, without the 50 kW threshold, is not enough. AHJ inspection and 240.4 protection are separate requirements, not the basis for the 100% allowance.

Disconnect location when heater has supplementary overcurrent protection

NEC 425.19(A)

One disconnect can cover both the motor controller and the heater, but the rule for combining them branches at 18 hp.

Q3 NEC 425.19(A)

A fixed industrial process heater has supplementary overcurrent protection using fuses. Where must the disconnecting means be located relative to those fuses?

  1. A On the load side of the fuses only
  2. B Anywhere in the same room as the heater
  3. C Within sight, on either the supply or load side
  4. D Within sight and on the supply side of the fuses
Show answer & explanation

Correct: D — Within sight and on the supply side of the fuses

425.19(A) requires the disconnect to be within sight from the supplementary overcurrent protective device(s), and on the supply side if fuses are used. The load-side-only and same-room options ignore that specific supply-side requirement, and 'either side' misses that fuses force supply-side placement.

Using a unit switch as the disconnecting means

NEC 425.19(C)

A unit switch with a marked "off" position that opens all ungrounded conductors can serve as a fixed heater's disconnecting means, with a readily accessible branch-circuit switch or breaker as the other.

Q4 NEC 425.19(C) Code lookup

A fixed electric heater's factory-installed unit switch has a marked "off" position and opens all ungrounded conductors. Which section allows this unit switch to serve as the disconnecting means required for the heater, provided the branch-circuit switch or breaker is also readily accessible for servicing?

  1. A 425.19(B)
  2. B 425.19(A)
  3. C 425.21
  4. D 425.19(C)
Show answer & explanation

Correct: D — 425.19(C)

425.19(C) specifically permits a unit switch with a marked "off" position that opens all ungrounded conductors to serve as the disconnecting means, so long as the branch-circuit switch or breaker is readily accessible as the other disconnect. 425.19(A) and (B) instead set the disconnect requirements based on whether the heater has supplementary overcurrent protection, not the unit-switch allowance, and 425.21 only addresses marking switches/breakers as indicating, not the unit-switch substitution itself.

Duct heater identification and airflow requirements

NEC 425.59

Duct heaters need even airflow across their face and must be identified for both standard installation and any elevated inlet air temperature.

Q5 NEC 425.59 Code lookup

A duct heater is being installed 2 ft downstream from the outlet of an air-moving unit, with an elbow just upstream of the heater. To prevent uneven heating and possible nuisance trips of limit controls, the installer wants to add turning vanes on the inlet side of the duct heater per the manufacturer's instructions. Which section covers this requirement?

  1. A 425.59
  2. B 425.64
  3. C 425.60
  4. D 425.58
Show answer & explanation

Correct: A — 425.59

425.59 requires means (such as turning vanes, pressure plates, or similar devices) to ensure uniform airflow over the face of a duct heater, especially near obstructions like elbows or air-mover outlets. 425.58 only addresses labeling the heater as suitable for duct installation, not airflow distribution, and 425.60 concerns elevated inlet air temperature ratings, not airflow uniformity.

Identification & required markings for electrode boilers

NEC 425.81

An electrode-type boiler must be identified as suitable for the installation and permanently marked with manufacturer, ratings, supply data, and a servicing warning.

Q6 NEC 425.81

Which of the following is NOT one of the items 425.86 requires to be marked on an electrode-type boiler?

  1. A The marking "Electrode-Type Process Heating Boiler"
  2. B The manufacturer's name
  3. C The rating in volts, amperes, and kilowatts
  4. D The installation date and inspector's initials
Show answer & explanation

Correct: D — The installation date and inspector's initials

425.86 lists five required markings: manufacturer's name, volt/ampere/kilowatt rating, electrical supply characteristics, the "Electrode-Type Process Heating Boiler" label, and the disconnect-before-servicing warning. An installation date and inspector's initials are not among them.

Access and working space for industrial process heating equipment

NEC 425.10

Fixed industrial process heating equipment must stay accessible, with 110.26/110.34 working space in front of it — unless special permission allows less in a qualified-persons-only industrial setting.

Q7 NEC 425.10 Code lookup

An industrial process heating enclosure is mounted above a work platform. The enclosure is 24 in. wide. Which section specifies the minimum required width of the working space in front of it?

  1. A 425.10(C)
  2. B 425.10(B)
  3. C 425.19(A)(1)
  4. D 425.13
Show answer & explanation

Correct: A — 425.10(C)

425.10(C) sets the specific working-space width rule for enclosures located above grade, a floor, or a work platform (width of enclosure or 30 in., whichever is greater). 425.10(B) instead points to the general 110.26/110.34 clearances used when the enclosure isn't elevated on a platform.

Branch circuit rating and continuous-load sizing for process heaters

NEC 425.4

Individual branch circuits can match any rating of fixed industrial process heating equipment, but heaters and their motors count as continuous loads for sizing.

Q8 NEC 425.4

Under 425.4(B), how should a motor that drives a fan on a fixed industrial process heater be classified for branch-circuit load purposes?

  1. A As a continuous load, regardless of how long it actually runs
  2. B As a noncontinuous load because it is incidental to the heater
  3. C As a continuous load only if it runs 3 hours or more at a time
  4. D As a continuous load only when it is the sole motor on the circuit
Show answer & explanation

Correct: A — As a continuous load, regardless of how long it actually runs

425.4(B) states that fixed industrial process heating equipment and motors shall be considered continuous loads — this is a blanket classification, not one conditioned on the general 3-hour continuous-load definition used elsewhere in the Code.

Disconnect location when heater has no supplementary overcurrent protection

NEC 425.19(B)

With no supplementary OCPD, the branch-circuit switch or breaker can serve as the disconnect only if the heater has no motor or a motor of 18 hp or less; over 18 hp, a dedicated lockable disconnect is required.

Q9 NEC 425.19(B)

Fixed industrial process heating equipment has no supplementary overcurrent protection and a motor rated 15 hp. Which statement about the disconnecting means is correct?

  1. A No lockable-open capability is required because the motor is under 18 hp
  2. B The branch-circuit switch or circuit breaker can serve as the disconnect if it's within sight from the heater and lockable open per 110.25
  3. C A separate disconnect must be located within sight from the motor controller regardless of horsepower
  4. D The branch-circuit switch must be within sight of both the heater and the motor controller
Show answer & explanation

Correct: B — The branch-circuit switch or circuit breaker can serve as the disconnect if it's within sight from the heater and lockable open per 110.25

Under 425.19(B)(1), for a motor not over 18 hp, the branch-circuit switch or circuit breaker can serve as the disconnecting means if it's within sight from the heater and capable of being locked open per 110.25 — it does not need to be within sight of the motor controller. The 'must be within sight of the motor controller regardless of horsepower' option describes the over-18-hp rule in 425.19(B)(2), and the lockable-open requirement applies in both cases.

Sizing and subdividing resistance heating element loads

NEC 425.22(B)

Resistance heating elements in fixed industrial process equipment max out at 60 A protection, and above 48 A they must be split into subdivided loads of 48 A or less — unless the enclosed/ASME exception bumps that to 120 A circuits protected at 150 A.

Q10 NEC 425.22(B)

Fixed industrial process heating equipment uses resistance-type heating elements rated at 60 amperes total, with no enclosure or ASME vessel involved. Per 425.22(B), what must be done?

  1. A Nothing extra — 60 A is within the general protection limit and subdivision isn't required below 48 A anyway
  2. B The elements can be subdivided into circuits up to 120 A since the total exceeds 48 A
  3. C The equipment must be protected at 150 amperes since it exceeds 48 A
  4. D The elements must be subdivided so no subdivided load exceeds 48 amperes
Show answer & explanation

Correct: D — The elements must be subdivided so no subdivided load exceeds 48 amperes

Under 425.22(B), equipment rated more than 48 A must have its resistance elements subdivided into loads not exceeding 48 A each. The 120 A/150 A allowance only applies when the elements are integral to the process surface, in a listed enclosure, or in an ASME-rated vessel — none of which apply here, so 60 A total without those conditions doesn't qualify for the higher subdivision limit.

Scope of industrial process heating equipment

NEC 425.1

Article 425 covers only fixed industrial process heating equipment using electric resistance or electrode technology — boilers, duct heaters, strip heaters, immersion heaters, and process air heaters.

Q11 NEC 425.1

Under 425.1, Article 425 applies to which type of industrial process heating equipment?

  1. A Fixed equipment using gas-fired heating technology
  2. B Portable equipment using electric resistance heating technology
  3. C Fixed equipment using electric resistance or electrode heating technology
  4. D Fixed equipment using any electrical heating or cooling technology
Show answer & explanation

Correct: C — Fixed equipment using electric resistance or electrode heating technology

425.1 limits the article to fixed industrial process heating equipment employing electric resistance or electrode heating technology. Portable equipment is outside this scope, gas-fired heating isn't electric heating at all, and the article does not cover cooling equipment.

Requirements for supplementary overcurrent protective devices

NEC 425.22(C)

Supplementary OCPDs for subdivided fixed resistance heater loads must be factory-supplied with the heater, accessible, and rated for branch-circuit use.

Q12 NEC 425.22(C)

A fixed electric resistance heater has its load subdivided per 425.22(B). What must be true of the supplementary overcurrent protective device for each subdivided load?

  1. A It must be factory installed in or on the heater, or supplied for that use as a separate assembly by the heater manufacturer
  2. B It must be rated for supplementary protection only, not branch-circuit protection
  3. C It must be part of the building's main service equipment
  4. D It must be a field-installed fuse holder added by the installing electrician
Show answer & explanation

Correct: A — It must be factory installed in or on the heater, or supplied for that use as a separate assembly by the heater manufacturer

425.22(C)(1) requires the device be factory installed within or on the heater enclosure, or supplied for use with the heater as a separate assembly by the heater manufacturer. It also must be suitable for branch-circuit protection per 240.10, not merely supplementary-rated, and a field-added fuse holder or reliance on service equipment doesn't satisfy the requirement.

Conductor sizing for boiler heater circuits and 50kW exception

NEC 425.72(F)

Boiler heater conductors are normally sized at 125% of load, but heaters rated 50 kW or more can drop to 100% if the heater is marked with a minimum conductor size and cyclic operation is temperature- or pressure-controlled.

Q13 NEC 425.72(F)

A boiler heater rated 60 kW is marked with a minimum conductor size, and its field-wired conductors to the supplementary overcurrent protective devices meet that marked size. Which additional condition must be satisfied to size those conductors at 100% of the subdivided load instead of 125%?

  1. A A temperature- or pressure-actuated device must control the cyclic operation of the equipment
  2. B A separate disconnecting means must be installed for each subdivided circuit
  3. C The heater must be de-rated to below 50 kW before the exception applies
  4. D The conductors must be increased one wire size above the marked minimum
Show answer & explanation

Correct: A — A temperature- or pressure-actuated device must control the cyclic operation of the equipment

Per 425.72(F), the 100% sizing exception for heaters rated 50 kW or more requires all three conditions: marked minimum conductor size, conductors not smaller than that marked size, and cyclic operation controlled by a temperature- or pressure-actuated device. Oversizing conductors beyond the marked minimum, de-rating the heater, or adding extra disconnects are not among the listed conditions.

Sizing heating-element overcurrent protection by vessel type

NEC 425.72(A)

ASME-stamped boiler vessels get a 150 A / 120 A subdivision ceiling; non-ASME vessels get a much tighter 60 A / 48 A ceiling.

Q14 NEC 425.72(A)

Why does a boiler with resistance-type immersion heating elements get a 150 A overcurrent protection ceiling instead of the 60 A ceiling?

  1. A The elements are individually subdivided into 48 A loads
  2. B The boiler's total load exceeds 120 amperes
  3. C The boiler is rated for use in a commercial occupancy
  4. D The elements are contained in an ASME-rated and stamped vessel
Show answer & explanation

Correct: D — The elements are contained in an ASME-rated and stamped vessel

Per 425.72(A), the higher 150 A ceiling applies specifically because the heating elements are contained in an ASME-rated and stamped vessel. Occupancy type doesn't factor into this rule. Subdividing into 48 A loads is the non-ASME threshold from 425.72(B), not what unlocks the higher ceiling. Being rated more than 120 A actually triggers subdivision, not a higher allowance.

Supplementary overcurrent devices for subdivided boiler loads

NEC 425.72(C)

Supplementary OCPDs for subdivided boiler loads must come from the boiler manufacturer and be accessible, and cartridge fuses let one disconnect serve all the subdivided circuits.

Q15 NEC 425.72(C) Code lookup

A boiler manufacturer ships resistance-type immersion heating elements with subdivided loads, each protected by a supplementary overcurrent device that is mounted inside the boiler's own enclosure as a factory-installed assembly. Which section specifies that these supplementary overcurrent protective devices must be factory-installed within or on the boiler enclosure (or supplied as a separate assembly by the manufacturer) and accessible, though not necessarily readily accessible?

  1. A 425.72(A)
  2. B 425.72(C)
  3. C 425.72(D)
  4. D 425.72(E)
Show answer & explanation

Correct: B — 425.72(C)

425.72(C) is the specific rule requiring the supplementary OCPDs to be factory-installed on/within the boiler enclosure or supplied as a separate manufacturer assembly, and to be accessible but not necessarily readily accessible. 425.72(A) only sets the threshold for when subdivision is required for ASME-rated vessels, not the installation/accessibility rule for the devices themselves.

Overtemperature and overpressure limit controls

NEC 425.73

Liquid-phase boilers need a temperature limit control and vapor-phase boilers need a pressure limit control, each wired to cut power to the heating elements independent of the regular thermostat.

Q16 NEC 425.73

A resistance-type boiler is designed so the heat transfer fluid remains liquid at all times during normal operation. Which limit control does the NEC require?

  1. A No separate limit control, since the regulating thermostat already covers it
  2. B A temperature-sensitive limiting means
  3. C A pressure-sensitive limiting means
  4. D A combination pressure-and-temperature relief valve only
Show answer & explanation

Correct: B — A temperature-sensitive limiting means

Per 425.73, a boiler with no change in state of the heat transfer medium (stays liquid) must have a temperature-sensitive limiting means. Pressure-sensitive limiting means applies instead to vapor-phase boilers under 425.74, and the limit control must be separate from the normal regulating thermostat, not replaced by it.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access