Free NEC practice test · Article 695

Fire Pumps practice questions

A free NEC Article 695 practice test for the journeyman exam: 14 questions on Fire Pumps, each with the answer and the why behind it.

14 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 14 journeyman-exam practice questions cover NEC Article 695 across 14 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Control wiring must not be able to stop the pump from starting

NEC 695.14

External control wiring can fail in almost any way, but that failure must never be able to block the fire pump from starting.

Q1 NEC 695.14

An external control circuit that extends outside the fire pump room loses power entirely. Per 695.14(A), what is the required design outcome?

  1. A The fire pump controller must still be able to start the pump by other means
  2. B The transfer switch must lock out automatic operation as a safety precaution
  3. C The controller must shut the pump down until the circuit is repaired
  4. D The pump must switch to manual-only operation until an electrician resets the controller
Show answer & explanation

Correct: A — The fire pump controller must still be able to start the pump by other means

695.14(A) requires that loss of power, breakage, disconnection, or shorting of external control conductors not prevent the controller from starting the pump by other internal or external means. Shutting the pump down or locking out automatic features would be exactly the failure mode the rule prohibits.

Disconnecting means and overcurrent device selection for fire pump sources

NEC 695.4(B)

Fire pump overcurrent devices must be sized to carry locked-rotor current indefinitely, and each source gets its own dedicated, lockable, marked disconnect.

Q2 NEC 695.4(B)

For an individual power source feeding a fire pump, how must the overcurrent protective device be rated per 695.4(B)(2)(a)?

  1. A To trip at 125% of the sum of all motor full-load currents, per standard motor branch-circuit protection
  2. B To carry the full-load current of the largest motor only, since accessory loads are separately protected
  3. C To trip instantaneously above the locked-rotor current to protect the motor windings
  4. D To carry indefinitely the locked-rotor current of the largest fire pump motor plus the full-load current of all other pump motors and accessory equipment
Show answer & explanation

Correct: D — To carry indefinitely the locked-rotor current of the largest fire pump motor plus the full-load current of all other pump motors and accessory equipment

695.4(B)(2)(a)(1) requires the OCPD to carry indefinitely the sum of the largest fire pump motor's locked-rotor current and the full-load current of all other pump motors and accessory equipment — the device must never open during starting or running. The 125%-of-FLC option describes ordinary motor branch-circuit sizing, not fire pump sizing, and an instantaneous trip above locked-rotor current would shut the pump down exactly when it's needed.

Arranging and transferring power between fire pump sources

NEC 695.3(E)

Multiple fire pump power sources must be arranged so one fire can't take out both, and switching between them happens inside the pump room on a listed transfer switch.

Q3 NEC 695.3(E)

Where does the NEC require transfer of power to a fire pump controller between an individual source and an alternate source to occur?

  1. A Within the fire pump room
  2. B At the utility transformer vault
  3. C At the service entrance switchgear
  4. D At the nearest accessible outdoor disconnect
Show answer & explanation

Correct: A — Within the fire pump room

695.3(F) requires transfer of power between the individual source and an alternate source to take place within the pump room. Locating it at the service switchgear, an outdoor disconnect, or the utility vault would put the transfer point outside the protected pump room, defeating the intent of keeping the switching function in the space designed to survive the fire.

Feeder sources for multibuilding campus-style fire pump installs

NEC 695.3(C)

A campus-style complex can power a fire pump from feeders instead of the usual 695.3(A) sources, but only with AHJ approval, a qualifying feeder arrangement, and mandatory selective coordination.

Q4 NEC 695.3(C)

A fire pump is part of a multibuilding campus-style complex, and the power sources required by 695.3(A) are not practicable. Under what condition can feeder sources be used instead?

  1. A If approved by the authority having jurisdiction and installed per 695.3(C)(1) and (C)(3), or (C)(2) and (C)(3)
  2. B If two feeders are installed, regardless of whether they share a utility service
  3. C Automatically, since campus-style complexes are exempt from 695.3(A)
  4. D If approved by the serving utility company alone
Show answer & explanation

Correct: A — If approved by the authority having jurisdiction and installed per 695.3(C)(1) and (C)(3), or (C)(2) and (C)(3)

695.3(C) permits feeder sources in a campus-style complex only with AHJ approval and only when installed per (C)(1) and (C)(3), or (C)(2) and (C)(3). Utility-only sign-off isn't sufficient, and two feeders sharing one utility service don't satisfy 695.3(C)(1)'s separate-services requirement — there's no automatic exemption.

Wiring methods for engine and generator fire pump control circuits

NEC 695.14(D)

Diesel controller wiring must be stranded and sized per the manufacturer, electric fire pump control wiring must run in a specified raceway or listed cable, and generator control conductors need their own independent, monitored, fire-protected path.

Q5 NEC 695.14(D)

Which wiring method is NOT permitted for electric motor–driven fire pump control wiring under 695.14(E)?

  1. A Electrical nonmetallic tubing (ENT)
  2. B Liquidtight flexible metal conduit
  3. C Electrical metallic tubing (EMT)
  4. D Type MI cable
Show answer & explanation

Correct: A — Electrical nonmetallic tubing (ENT)

695.14(E) lists rigid metal conduit, IMC, liquidtight flexible metal conduit, EMT, liquidtight flexible nonmetallic conduit, listed Type MC cable with impervious covering, and Type MI cable. ENT is not on that list, while EMT, MI cable, and liquidtight flexible metal conduit are all explicitly permitted.

No overload or ground-fault protection on fire pump power circuits

NEC 695.6(C)

Fire pump power circuits get short-circuit protection only — never overload or ground-fault protection — because a running pump matters more than a protected conductor.

Q6 NEC 695.6(C)

What type of overcurrent protection is permitted on fire pump branch-circuit and feeder conductors?

  1. A Short-circuit protection only
  2. B Overload protection only
  3. C Ground-fault protection of equipment only
  4. D Both overload and short-circuit protection
Show answer & explanation

Correct: A — Short-circuit protection only

695.6(C) states that fire pump power circuits shall not have automatic overload protection, and conductors are protected against short circuit only (except transformer primary protection under 695.5(C)(2)). Overload-only and combined overload/short-circuit protection would shut the pump down under a sustained overload, and GFPE is separately prohibited under 695.6(G).

Choosing a reliable power source for electric fire pump motors

NEC 695.3

A fire pump's power source must reliably carry the combined locked-rotor and accessory load indefinitely, and only a utility service connection, an on-site power production facility, or a dedicated feeder off that service qualify.

Q7 NEC 695.3

Which of the following is a required characteristic of any individual power source used to supply an electric motor-driven fire pump under 695.3(A)?

  1. A It must be capable of carrying the combined locked-rotor and accessory load indefinitely
  2. B It must supply only the fire pump motor and no other connected equipment
  3. C It must be located within the same switchgear section as the service disconnect for coordination
  4. D It must be a dedicated transformer rated at utilization voltage only
Show answer & explanation

Correct: A — It must be capable of carrying the combined locked-rotor and accessory load indefinitely

695.3(A) requires the source to be reliable and capable of carrying the sum of the locked-rotor current of the fire pump and pressure maintenance pump motors, plus full-load current of accessory equipment, indefinitely. Locating the source within the same switchgear section as the service disconnect is actually prohibited by 695.3(A)(1), which requires the connection be located ahead of and separate from the service disconnecting means.

Listed electrical circuit protective systems and junction box requirements

NEC 695.6(H)

Junction boxes and terminations on fire pump controller wiring have their own listing, mounting, and sealing rules separate from the controller itself.

Q8 NEC 695.6(H)

A junction box feeds a fire pump controller through a listed electrical circuit protective system. Where must this junction box be located relative to the fire-rated wall it passes through?

  1. A At least 300 mm (12 in.) beyond the fire-rated wall, ahead of the controller
  2. B Inside the fire pump room only, regardless of distance from the wall
  3. C At least 300 mm (12 in.) beyond the controller enclosure itself
  4. D Immediately adjacent to the fire-rated wall, on either side
Show answer & explanation

Correct: A — At least 300 mm (12 in.) beyond the fire-rated wall, ahead of the controller

695.6(H)(1) requires the junction box a minimum of 300 mm (12 in.) beyond the fire-rated ceiling, wall, or floor bounding the fire zone, installed ahead of the controller. Placing it immediately adjacent to the wall or measuring from the controller enclosure instead of the fire barrier misreads where the distance is measured from.

Wiring methods from controller to pump motor

NEC 695.6(D)

Controller-to-motor wiring on fire pumps must be a rigid, moisture-sealed method — RMC, IMC, EMT, liquidtight flex, or jacketed MC/MI cable — with wet-location fittings and listed connectors only, no twist-ons.

Q9 NEC 695.6(D)

Which wiring method is NOT permitted between a fire pump controller and the pump motor?

  1. A Type MC cable with an impervious covering
  2. B Intermediate metal conduit
  3. C Electrical nonmetallic tubing (ENT)
  4. D Liquidtight flexible metal conduit
Show answer & explanation

Correct: C — Electrical nonmetallic tubing (ENT)

695.6(D)(1) lists RMC, IMC, EMT, liquidtight flexible metal conduit, LFNC-B, jacketed Type MC, and Type MI as the only permitted methods. ENT isn't on that list — it lacks the physical robustness the section requires for this critical wiring run.

Fire pump article scope and listed equipment requirement

NEC 695.1

Article 695 covers power sources and dedicated switching/control equipment for fire pump drivers, not the pump system's internal wiring or performance testing — and controllers, transfer switches, and motors must be listed for fire pump service.

Q10 NEC 695.1

Which installation is specifically excluded from the coverage of Article 695?

  1. A Interconnecting circuits to the fire pump power source
  2. B Switching equipment dedicated to a fire pump driver
  3. C The internal wiring of fire pump system components and its acceptance testing
  4. D Control equipment dedicated to a fire pump driver
Show answer & explanation

Correct: C — The internal wiring of fire pump system components and its acceptance testing

695.1(B)(1) excludes the performance, maintenance, and acceptance testing of the fire pump system and the internal wiring of its components. The dedicated switching, control equipment, and interconnecting circuits to the power source are exactly what 695.1(A) says the article covers.

Routing service/feeder/generator supply conductors to the fire pump room

NEC 695.6(A)

Service conductors must stay outside the building where possible, while feeder or generator supply conductors routed inside must be independently run and fire-protected for 2 hours.

Q11 NEC 695.6(A)

Under 695.6(A)(1), how must fire pump service conductors normally be routed relative to the building?

  1. A Independently routed from all other feeders inside the building
  2. B Through a 2-hour fire-rated raceway inside the building
  3. C Physically outside the building, installed as service-entrance conductors
  4. D Encased in 2 in. of concrete wherever they run
Show answer & explanation

Correct: C — Physically outside the building, installed as service-entrance conductors

695.6(A)(1) requires service conductors to be physically routed outside the building and installed per 230.6, 230.9, and Article 230 Parts III and IV. The 2-hour fire protection methods and independent routing requirement apply to feeder/generator conductors under 695.6(A)(2), not to service conductors.

Sizing and protecting transformers for fire pump voltage conversion

NEC 695.5

A fire pump transformer must be sized at 125% of the pump motor loads plus 100% of accessory load, and it can never have secondary overcurrent protection.

Q12 NEC 695.5

A transformer installed under 695.5(A) and (B) to convert service voltage for a fire pump controller is discovered also feeding a small office lighting panel. What is the issue?

  1. A This is allowed as long as the lighting load is less than 20% of the transformer rating
  2. B This is allowed only if the fire pump motor is under 25 hp
  3. C This is allowed as long as the office panel has its own secondary overcurrent device
  4. D This is a violation — only transformers under 695.5(C) may supply loads not directly associated with the fire pump system
Show answer & explanation

Correct: D — This is a violation — only transformers under 695.5(C) may supply loads not directly associated with the fire pump system

Per 695.5, only transformers covered under 695.5(C) are permitted to supply loads not directly associated with the fire pump system. A transformer installed under 695.5(A) and (B) must be dedicated to the fire pump system, so feeding an unrelated lighting panel from it is not permitted regardless of load percentage or added protection.

Voltage drop limits during fire pump motor starting and running

NEC 695.7

Fire pump voltage can sag up to 15% at starting and 5% while running at 115% load, unless a demonstrated generator start allows the starting limit to be skipped.

Q13 NEC 695.7

Under 695.7(A), what is the maximum permitted voltage drop at the fire pump controller line terminals during motor starting conditions?

  1. A 15 percent below controller-rated voltage
  2. B 5 percent below controller-rated voltage
  3. C 10 percent below controller-rated voltage
  4. D 20 percent below controller-rated voltage
Show answer & explanation

Correct: A — 15 percent below controller-rated voltage

695.7(A) caps starting voltage drop at 15 percent below controller-rated voltage. The 5 percent figure is the separate running-condition limit from 695.7(D), and 10 percent and 20 percent do not appear in this section.

Sizing fire pump supply conductors

NEC 695.6(B)

Conductors feeding only the fire pump motor size per 430.22; conductors that also feed pressure maintenance pumps or accessories must sum 125% of the motor loads plus 100% of the accessory load.

Q14 NEC 695.6(B)

A conductor supplies only a fire pump motor, with no pressure maintenance pump or accessory equipment on the same conductor. Which rule governs its minimum ampacity?

  1. A The 695.6(B)(1) combined-load formula
  2. B Table 310.16 alone, with no additional sizing factor
  3. C 215.2 feeder sizing requirements
  4. D 430.22
Show answer & explanation

Correct: D — 430.22

695.6(B)(2) directs motor-only fire pump conductors to 430.22. The combined-load formula in 695.6(B)(1) only applies when a pressure maintenance pump or accessory equipment shares the conductor with the fire pump motor.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access