A 30 hp motor is fed through a listed VFD. The drive is listed and marked "Suitable for Output Motor Conductor Protection," and the installer wants to size the branch-circuit short-circuit and ground-fault protective device using the drive's rated input current instead of the motor's full-load current. Which section allows this alternative sizing method and specifies the table to use?
- A 430.131
- B 430.122(B)
- C 430.130(A)
- D 430.124(A)
Show answer & explanation
Correct: C — 430.130(A)
430.130(A)(1) permits sizing the branch-circuit short-circuit and ground-fault protective device from Table 430.52(C)(1) using the power conversion equipment's rated input current when it is listed and marked "Suitable for Output Motor Conductor Protection." 430.122(B) covers output conductor sizing, not protective device sizing, so it doesn't answer this ask.