Free NEC practice test · Article 240

Overcurrent Protection practice questions

A free NEC Article 240 practice test for the journeyman exam: 41 questions on Overcurrent Protection, each with the answer and the why behind it.

41 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 41 journeyman-exam practice questions cover NEC Article 240 across 41 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Arc energy reduction for 1200A+ fuses: documentation, method, and testing

NEC 240.67

Fuses rated 1200 A or higher need a clearing time of 0.07 seconds or less (or an approved reduction method), documentation of fuse location and settings, and on-site performance testing.

Q1 NEC 240.67

An installation includes fuses rated 1200 amperes. Which requirement set applies under 240.67?

  1. A GFCI protection on the feeder supplying the fuses
  2. B Documentation, a method to reduce clearing time, and performance testing
  3. C Only a written short-circuit study, since fuses are already current limiting
  4. D Arc-fault circuit interrupter protection at the panelboard
Show answer & explanation

Correct: B — Documentation, a method to reduce clearing time, and performance testing

Per 240.67, fuses rated 1200 amperes or higher trigger all three subsections: (A) documentation, (B) a method to reduce clearing time, and (C) performance testing. Being current-limiting doesn't exempt a fuse from these rules, and GFCI/AFCI protection is unrelated to arc energy reduction.

Adjustable-trip circuit breaker rating rules (unrestricted, restricted, remote access)

NEC 240.6(B)

An adjustable-trip breaker's ampere rating is its maximum possible setting, unless the adjusting means has restricted local access or approved remote access — then the rating is the actual dial-in setting.

Q2 NEC 240.6(B)

An adjustable-trip circuit breaker's adjusting means is located behind a bolted equipment enclosure door. How is the breaker's ampere rating determined?

  1. A By the manufacturer's nameplate frame size regardless of setting
  2. B By the average of the minimum and maximum settings
  3. C By the maximum setting possible on the adjusting means
  4. D By the actual adjusted current (long-time pickup) setting
Show answer & explanation

Correct: D — By the actual adjusted current (long-time pickup) setting

Per 240.6(C), a breaker with restricted access to the adjusting means — including behind bolted equipment enclosure doors — is permitted an ampere rating equal to the actual adjusted current setting. The maximum-setting rule only applies when access isn't restricted, per 240.6(B).

Branch-circuit protection methods for flexible cord and fixture wire

NEC 240.5(B)

Flexible cord is protected by its listing (appliance, luminaire, or extension cord set), not by the branch-circuit breaker size; fixture wire is protected by size-to-ampacity tap rules.

Q3 NEC 240.5(B)

An electrician wants to know how the flexible cord on a portable, listed luminaire is protected when it's plugged into a 20-ampere branch circuit. What governs?

  1. A The cord must be sized so its ampacity matches the 20-ampere branch-circuit breaker
  2. B The cord needs its own supplementary overcurrent device rated at or below its ampacity
  3. C The cord is considered protected when used within the luminaire's listing requirements
  4. D The cord must be run no more than 50 ft from the luminaire to the outlet
Show answer & explanation

Correct: C — The cord is considered protected when used within the luminaire's listing requirements

Per 240.5(B)(1), flexible cord approved for and used with a specific listed appliance or luminaire is considered protected when applied within that listing's requirements — no matching to the branch-circuit breaker size, no separate length limit, and no supplementary device is required by this rule. The 50 ft length limit is a fixture-wire tap rule under 240.5(B)(2), not a cord rule.

Arc energy reduction for high-trip-setting breakers

NEC 240.87(B)

Circuit breakers with a trip setting of 1200 A or higher need a listed way to cut clearing time below the arcing current, plus documentation and on-site performance testing.

Q4 NEC 240.87(B)

A circuit breaker's highest continuous current trip setting can be adjusted to 1200 amperes. Under 240.87, what does this trigger?

  1. A A requirement to derate the breaker to 80% of its trip setting
  2. B A requirement to document breaker location and provide an arc energy reduction method, with performance testing
  3. C A requirement to install ground-fault protection of equipment regardless of the method used
  4. D An automatic exemption from selective coordination requirements
Show answer & explanation

Correct: B — A requirement to document breaker location and provide an arc energy reduction method, with performance testing

240.87 applies whenever the highest continuous trip setting the breaker is rated for or adjustable to is 1200 A or higher, requiring documentation (240.87(A)), a clearing-time reduction method (240.87(B)), and performance testing (240.87(C)). Ground-fault protection of equipment and selective coordination are separate, unrelated requirements, and there is no 80% derating rule tied to this section.

Circuit breakers as OC devices: multiwire and multi-phase exceptions

NEC 240.15(B)

A circuit breaker must open all ungrounded conductors together, unless handle-tied single-pole breakers qualify under one of four named exceptions.

Q5 NEC 240.15(B)

Under the general rule of 240.15(B), how must a circuit breaker protect the ungrounded conductors of a circuit?

  1. A It must open all ungrounded conductors automatically but not manually
  2. B It must open only the conductor that experiences the overcurrent condition
  3. C It must open all conductors, including the grounded neutral, automatically only
  4. D It must open all ungrounded conductors of the circuit, both manually and automatically
Show answer & explanation

Correct: D — It must open all ungrounded conductors of the circuit, both manually and automatically

240.15(B) requires circuit breakers to open all ungrounded conductors of the circuit both manually and automatically, unless one of the exceptions in 240.15(B)(1) through (B)(4) applies. Opening only the faulted conductor, or only automatically, doesn't meet this default requirement.

Feeder taps: 10-ft and 25-ft tap rules

NEC 240.21(B)

A feeder tap can skip overcurrent protection at the tap point only if its length, enclosure, and ampacity meet the strict 10-ft or 25-ft rules in 240.21(B)(1) or (B)(2).

Q6 NEC 240.21(B)

A tap conductor 8 ft long is run from a feeder, leaves the enclosure where the tap is made, and continues to a panelboard. Under 240.21(B)(1), what minimum ampacity must it have relative to the feeder overcurrent device?

  1. A Not less than one-half of the feeder overcurrent device rating
  2. B Not less than one-third of the feeder overcurrent device rating
  3. C Equal to the full feeder overcurrent device rating
  4. D Not less than one-tenth of the feeder overcurrent device rating
Show answer & explanation

Correct: D — Not less than one-tenth of the feeder overcurrent device rating

Per 240.21(B)(1)(4), when a 10-ft tap conductor leaves the enclosure or vault where the tap is made, its ampacity must be not less than one-tenth of the feeder overcurrent device rating. The one-third figure is the threshold for the 25-ft tap rule in 240.21(B)(2), not the 10-ft rule.

Feeder tap supplying a transformer (primary + secondary ≤ 25 ft)

NEC 240.21(B)(3)

A tap can feed a transformer without full feeder protection if primary and secondary conductors are each sized off one-third the feeder OCPD (adjusted by turns ratio) and the combined tap length stays under 25 ft in raceway.

Q7 NEC 240.21(B)(3)

Under 240.21(B)(3), which requirement applies to the secondary conductors of the transformer at the end of the tap?

  1. A They may terminate without overcurrent protection if the primary is protected
  2. B They must be protected at the same rating as the feeder overcurrent device
  3. C They must terminate in a single circuit breaker or set of fuses limiting load current to the conductor ampacity
  4. D They must terminate in an individual breaker for each connected load
Show answer & explanation

Correct: C — They must terminate in a single circuit breaker or set of fuses limiting load current to the conductor ampacity

240.21(B)(3)(5) requires the secondary conductors to terminate in a single circuit breaker or set of fuses that limits the load current to not more than the conductor ampacity permitted by 310.14. Terminating without protection, requiring per-load breakers, or matching the feeder OCPD rating are not what this section specifies.

Ground-fault protection of equipment for large services

NEC 240.13

A 1000A+ solidly grounded wye service disconnect over 150V to ground needs ground-fault protection of equipment per 230.95, with three narrow exceptions.

Q8 NEC 240.13

A building has a single main disconnecting means rated 1200 amperes, fed from a solidly grounded 277/480V wye service. Per 240.13, what is required?

  1. A Ground-fault protection of equipment in accordance with 230.95
  2. B No ground-fault protection, since 240.13 only applies to feeders, not service disconnects
  3. C Ground-fault protection only if the system exceeds 1000 volts phase-to-phase
  4. D Ground-fault protection only if the disconnect is rated 2000 amperes or more
Show answer & explanation

Correct: A — Ground-fault protection of equipment in accordance with 230.95

240.13 requires ground-fault protection of equipment per 230.95 for each building or structure main disconnect rated 1000 amperes or more on a solidly grounded wye system over 150V to ground but not exceeding 1000V phase-to-phase — a 1200A, 480Y/277V disconnect fits squarely in that trigger. The 2000A threshold is wrong (1000A is the actual cutoff), the system already qualifies since 480V phase-to-phase is under the 1000V ceiling, and the rule explicitly names building/structure disconnecting means, not just feeders.

Next-size-up rule for devices 800A or less

NEC 240.4(B)

You can round up to the next standard breaker or fuse size above the conductor's ampacity, but only if the load isn't a multi-outlet cord-and-plug branch circuit, no in-between standard size exists, and the result stays at or under 800 A.

Q9 NEC 240.4(B)

Under 240.4(B), which scenario disqualifies a conductor from being protected by the next higher standard overcurrent device rating?

  1. A The overcurrent device is a fuse rather than a circuit breaker
  2. B The next higher standard rating is 400 amperes
  3. C The conductor is part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads
  4. D The conductor ampacity falls between two standard device ratings
Show answer & explanation

Correct: C — The conductor is part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads

240.4(B)(1) excludes conductors in a branch circuit feeding more than one receptacle for cord-and-plug portable loads — those require an exact ampacity match. A gap between standard ratings is actually what allows rounding up, a rating of 400 A is well under the 800 A cap, and the rule applies to both breakers and fuses.

Overcurrent device accessibility and mounting height

NEC 240.24(A)

Circuit breakers and fused switches must be readily accessible with the operating handle's grip center no higher than 6 ft 7 in. above the floor or platform, unless a listed exception applies.

Q10 NEC 240.24(A)

Per 240.24(A), where is the maximum mounting height for a circuit breaker's operating handle measured to and from?

  1. A The top of the enclosure, from the floor or working platform
  2. B The bottom of the enclosure, from the finished ceiling
  3. C The center of the grip in its lowest position, from the floor or working platform
  4. D The center of the grip of the operating handle in its highest position, from the floor or working platform
Show answer & explanation

Correct: D — The center of the grip of the operating handle in its highest position, from the floor or working platform

240.24(A) measures to the center of the grip of the operating handle when in its highest position, not the enclosure edges, and not the handle's lowest position. That point cannot exceed 2.0 m (6 ft 7 in.) above the floor or working platform.

Prohibited locations: physical damage, ignitible material, bathrooms, stairs

NEC 240.24(C)

Overcurrent devices can't go where they'd get physically damaged, near easily ignitible material like closets, in bathrooms, or over stairway steps.

Q11 NEC 240.24(C)

An electrician wants to install a panelboard inside a dwelling unit's clothes closet. Is this permitted?

  1. A No, because 240.24(D) prohibits overcurrent devices near easily ignitible material such as clothes closets
  2. B Yes, as long as the panelboard has a locking cover
  3. C No, but only if the closet is smaller than a habitable room
  4. D Yes, because clothes closets are only restricted for luminaires, not overcurrent devices
Show answer & explanation

Correct: A — No, because 240.24(D) prohibits overcurrent devices near easily ignitible material such as clothes closets

240.24(D) specifically names clothes closets as the kind of easily ignitible material location where overcurrent protective devices cannot be installed. There's no exception for a locking cover, no size threshold, and the restriction is not limited to luminaires.

What overcurrent equipment can and cannot be reconditioned

NEC 240.2

Molded-case circuit breakers, GFCIs, and ground-fault protection equipment can never be reconditioned — only low-voltage power circuit breakers and protective relays can, and only if listed as reconditioned.

Q12 NEC 240.2

Which piece of overcurrent equipment is permitted to be reconditioned under 240.2(B)?

  1. A Ground-fault circuit interrupter
  2. B Low-voltage power circuit breaker
  3. C Molded-case circuit breaker
  4. D Low-voltage nonrenewable fuse
Show answer & explanation

Correct: B — Low-voltage power circuit breaker

240.2(B) permits reconditioning of low-voltage power circuit breakers (and electromechanical protective relays with current transformers), provided the equipment is listed as reconditioned per 110.21(A)(2). Molded-case circuit breakers, GFCIs, and low-voltage nonrenewable fuses are all barred from reconditioning under 240.2(A).

Small conductor overcurrent limits (14-18 AWG) by material and rating

NEC 240.4(D)

For 18-10 AWG, overcurrent protection is capped at a fixed amp value by wire size and material — you can't just apply the ampacity tables.

Q13 NEC 240.4(D)

Under 240.4(D), what is the maximum overcurrent protection permitted for 14 AWG copper conductors, before any ampacity correction factors are even considered?

  1. A 20 amperes
  2. B 15 amperes
  3. C 30 amperes
  4. D 25 amperes
Show answer & explanation

Correct: B — 15 amperes

240.4(D)(4) sets 14 AWG copper at a flat 15 A maximum. 20 A is the 12 AWG copper limit and 30 A is the 10 AWG copper limit — mixing up adjacent wire sizes is the common error. 25 A applies to 10 AWG aluminum/copper-clad aluminum, not copper of any size in this table.

Transformer secondary conductors: 10-ft and 25-ft length rules

NEC 240.21(C)(2)

Short unprotected secondary taps skip normal overcurrent protection only if length, ampacity, enclosure, and (for 25 ft) supervision conditions are all met.

Q14 NEC 240.21(C)(2)

A contractor wants to run unprotected transformer secondary conductors 20 ft (6 m) to a switchboard in a commercial office building. Is this permitted under 240.21(C)?

  1. A Yes, under the 25-ft industrial tap rule
  2. B No, because the 25-ft tap rule applies only to industrial installations, and 20 ft exceeds the 10-ft general rule
  3. C Yes, under the 10-ft general rule since 20 ft is under 25 ft
  4. D Yes, as long as the conductors are enclosed in a raceway
Show answer & explanation

Correct: B — No, because the 25-ft tap rule applies only to industrial installations, and 20 ft exceeds the 10-ft general rule

A commercial office building is not an industrial installation, so the 7.5 m (25 ft) tap in 240.21(C)(3) is unavailable. The general tap in 240.21(C)(2) caps out at 3 m (10 ft), and 20 ft exceeds that limit regardless of raceway enclosure. Neither exception applies here.

Required markings on cartridge fuses

NEC 240.60(C)

Every cartridge fuse must show ampere rating, voltage rating, manufacturer name, current-limiting status where applicable, and interrupting rating unless it's 10,000 A.

Q15 NEC 240.60(C)

A cartridge fuse has an interrupting rating of 10,000 amperes. Per 240.60(C), is this rating required to be marked on the fuse?

  1. A Yes, because interrupting rating is always required on every fuse without exception
  2. B Yes, but only if the fuse is current-limiting
  3. C No, because 10,000 amperes is the rating exempted from marking
  4. D No, because interrupting rating is never a required marking
Show answer & explanation

Correct: C — No, because 10,000 amperes is the rating exempted from marking

Under 240.60(C), the interrupting rating must be marked only where it is other than 10,000 amperes — so a 10,000 A rating is exempt. It's incorrect that marking is always required regardless of rating, and incorrect that interrupting rating is never required, since it is required whenever the rating differs from 10,000 A. Current-limiting status is a separate, independent marking requirement.

Circuit breaker interrupting rating and voltage marking

NEC 240.83(C)

A breaker's nameplate must show its interrupting rating (unless it's 5000A) and a voltage rating at least equal to the system's nominal voltage.

Q16 NEC 240.83(C) Code lookup

An inspector is checking a panelboard and wants to confirm that each circuit breaker with an interrupting rating above 5000A has that rating actually marked on it. Which section covers this marking requirement?

  1. A 240.83(C)
  2. B 240.83(A)
  3. C 240.86(B)
  4. D 240.89
Show answer & explanation

Correct: A — 240.83(C)

240.83(C) requires the interrupting rating to be marked on any breaker rated above 5000A, with an exception for supplementary protection devices. 240.83(A) only addresses that markings be durable and visible, not what must be marked, and 240.86(B) deals with tested series-rated combinations, not individual breaker marking.

Series-rated circuit breaker combinations

NEC 240.86

A breaker can lean on an upstream device's interrupting rating only if the pair is tested-and-marked or engineer-approved, and motor contribution stays under 1% of the downstream breaker's rating.

Q17 NEC 240.86

A panelboard has a breaker whose marked interrupting rating is lower than the available fault current at that point, but it is backed by a higher-rated device upstream. Under 240.86, what must be true for this to be code-compliant?

  1. A The breaker must be replaced with one individually rated for the full available fault current in all cases
  2. B Any breaker may be used as long as the upstream device rating exceeds the available fault current
  3. C The combination must be a tested combination marked on the equipment, or selected under engineering supervision per 240.86(A) or (B), and meet 240.86(C)
  4. D The combination is acceptable only if approved by the local AHJ inspector on-site, with no engineering or testing required
Show answer & explanation

Correct: C — The combination must be a tested combination marked on the equipment, or selected under engineering supervision per 240.86(A) or (B), and meet 240.86(C)

240.86 requires the combination to satisfy 240.86(A) (engineered and PE-stamped) or 240.86(B) (tested and marked), and 240.86(C) (motor contribution limit) in all cases. Simply having a higher-rated upstream device isn't sufficient by itself, individual full-rating isn't the only option since series ratings exist as an alternative, and AHJ sign-off alone doesn't substitute for the documented engineering or testing required.

Applying straight- vs slash-rated breakers to system voltage

NEC 240.85

A straight-rated breaker (like 480V) needs every conductor-to-conductor voltage under its rating; a slash-rated breaker (like 480Y/277V) needs both the conductor-to-ground AND conductor-to-conductor voltages to fit, and only on solidly grounded systems.

Q18 NEC 240.85

An electrician wants to install a 480Y/277V slash-rated circuit breaker. Which system is this breaker suitable for?

  1. A A solidly grounded wye system
  2. B An ungrounded 3-phase delta system
  3. C Any 3-phase system regardless of grounding method
  4. D A corner-grounded delta system using a breaker without a 1φ–3φ marking
Show answer & explanation

Correct: A — A solidly grounded wye system

Per 240.85, slash-rated breakers are only permitted on solidly grounded circuits, checking both conductor-to-ground and conductor-to-conductor voltages. Ungrounded and corner-grounded delta systems don't meet the solidly grounded requirement, and any-system application ignores the grounding condition entirely.

Basic rule: conductors protected per their ampacity

NEC 240.4

The overcurrent device protecting a conductor must match that conductor's ampacity from 310.14, unless 240.4(A) through (H) says otherwise.

Q19 NEC 240.4

Under the general rule of 240.4, how must a fixed conductor's overcurrent protection be sized?

  1. A At the next size up from the conductor's ampacity in every case
  2. B At the conductor's ampacity as specified in 310.14, unless 240.4(A) through (H) applies
  3. C At the rating of the connected load only, ignoring conductor ampacity
  4. D At the ampacity of the smallest conductor in the raceway regardless of exceptions
Show answer & explanation

Correct: B — At the conductor's ampacity as specified in 310.14, unless 240.4(A) through (H) applies

240.4 states conductors are protected in accordance with their ampacities per 310.14 unless otherwise permitted or required by 240.4(A) through (H). The 'always round up' and 'always use smallest conductor' options describe specific exception scenarios (like tap rules or small conductor rules), not the general rule itself, and sizing to load alone ignores the ampacity basis entirely.

Conductor protection basics and the >800A exception

NEC 240.91

Conductors follow the standard 240.4 sizing rule unless the overcurrent device is rated over 800 A, where 95% ampacity plus listed equipment can replace a full match.

Q20 NEC 240.91

Which condition triggers the alternative conductor protection method in 240.91(B) instead of the general rule in 240.4?

  1. A The overcurrent device is rated over 800 amperes
  2. B The feeder length exceeds 100 feet
  3. C The conductors are aluminum instead of copper
  4. D The installation is outdoors rather than indoors
Show answer & explanation

Correct: A — The overcurrent device is rated over 800 amperes

Per 240.91, conductors follow 240.4 (the general rule) unless the overcurrent device is rated over 800 amperes, in which case 240.91(B) applies instead. Conductor material, location, and feeder length don't determine which subsection applies.

Edison-base fuses: replacement-only use

NEC 240.51

Edison-base plug fuses are capped at 125V/30A and can only go into existing installations as replacements — new work requires Type S.

Q21 NEC 240.51

An electrician finds a blown Edison-base plug fuse in an older dwelling panel with no signs of tampering or overfusing. What does 240.51(B) permit?

  1. A Replacing it with an Edison-base fuse rated higher than 30 amperes
  2. B Leaving the circuit unfused until the panel is upgraded
  3. C Replacing it only with a Type S fuse and adapter
  4. D Replacing it with another Edison-base fuse of the correct rating
Show answer & explanation

Correct: D — Replacing it with another Edison-base fuse of the correct rating

Per 240.51(B), Edison-base fuses are permitted for replacements in existing installations where there's no evidence of overfusing or tampering. There's no requirement to convert to Type S at that point, and 240.51(A) caps Edison-base classification at 30 amperes and below.

High-bay manufacturing building tap (over 25 ft)

NEC 240.21(B)(4)

In a high-bay manufacturing building over 35 ft tall, a tap can run up to 25 ft horizontally (100 ft total) if it's made at least 30 ft up and meets all nine conditions of 240.21(B)(4).

Q22 NEC 240.21(B)(4)

An electrician wants to use the high-bay manufacturing building tap rule in 240.21(B)(4) for a feeder tap. Which condition must the building itself meet?

  1. A The building must be a high-bay manufacturing building over 35 ft high at the walls
  2. B The building must be a high-bay manufacturing building over 25 ft high at the walls
  3. C The building must have a footprint over 30,000 square feet
  4. D The building must be classified as an industrial occupancy with 3-phase service only
Show answer & explanation

Correct: A — The building must be a high-bay manufacturing building over 35 ft high at the walls

240.21(B)(4) applies only to high-bay manufacturing buildings over 11 m (35 ft) high at the walls. The 25 ft figure describes the tap's horizontal length limit, not the building height, and there's no footprint or 3-phase service requirement in this rule.

Outside taps of unlimited length

NEC 240.21(B)(5)

A tap run entirely outside the building has no length limit at all, as long as it's protected from damage and lands on one disconnect sized to the tap's ampacity.

Q23 NEC 240.21(B)(5)

Tap conductors run entirely outside a building, except at the point of load termination, are protected from physical damage and terminate at a single circuit breaker sized to their ampacity. Under 240.21(B)(5), what governs the maximum length of these tap conductors?

  1. A There is no length limit as long as all listed conditions are met
  2. B 10 ft, the same as the general tap rule
  3. C 100 ft, and only in industrial occupancies with qualified maintenance
  4. D 25 ft, matching the 25-ft outside feeder tap allowance
Show answer & explanation

Correct: A — There is no length limit as long as all listed conditions are met

240.21(B)(5) removes the length restriction entirely for taps located outside a building, provided the four conditions (physical protection, single sized overcurrent device, device placement, and accessible disconnect location) are satisfied. The 10-ft, 25-ft, and 100-ft figures belong to other tap rules, not this unlimited-length exception.

No overcurrent device in series with a grounded conductor

NEC 240.22

You can't put a fuse or single-pole breaker in the grounded (neutral) conductor — it can open the neutral while the hot stays live.

Q24 NEC 240.22 Code lookup

A designer wants to protect a grounded neutral conductor with a single-pole breaker that only opens the ungrounded conductor, leaving the neutral pole permanently connected. Which section prohibits placing an overcurrent device in series with a grounded conductor unless it opens all conductors simultaneously?

  1. A 240.24(A)
  2. B 240.21(A)
  3. C 240.22
  4. D 240.21(D)
Show answer & explanation

Correct: C — 240.22

240.22 specifically bars an overcurrent device from being connected in series with a grounded conductor unless it opens all conductors together, with no independent pole operation. 240.21(D) instead governs where service conductor overcurrent protection is located, not the grounded-conductor series restriction, so it doesn't answer this question.

General rule: overcurrent protection at the supply point

NEC 240.21

Overcurrent protection goes where the conductor gets its supply — every exception in 240.21(A)-(H) is a narrow carve-out from that default.

Q25 NEC 240.21

Per 240.21, where must overcurrent protection generally be located for each ungrounded circuit conductor?

  1. A At the point where the conductor receives its supply
  2. B At the load end of the conductor, nearest the equipment served
  3. C At the midpoint of the conductor run when the run exceeds 25 ft
  4. D Wherever is most convenient during installation, as long as it's accessible
Show answer & explanation

Correct: A — At the point where the conductor receives its supply

240.21 states the general rule: overcurrent protection is located at the point where the conductor receives its supply, except as permitted by 240.21(A) through (H). Locating it at the load end, at a midpoint, or wherever is convenient are not the code default — those patterns only exist because a specific tap-rule exception allows them.

Occupant access to overcurrent devices (multi-occupancy buildings)

NEC 240.24(B)

Every occupant must have ready access to their own overcurrent devices, unless building management provides continuous supervision — then service, feeder, and certain branch-circuit devices can be locked away from tenants.

Q26 NEC 240.24(B)

Under what condition can a multiple-occupancy building restrict service and feeder overcurrent device access to authorized management personnel only?

  1. A The building has a fire alarm system with 24-hour monitoring
  2. B The devices are located in a locked electrical room on each floor
  3. C Each occupancy has its own separately metered service
  4. D Electric service and electrical maintenance are provided by building management under continuous supervision
Show answer & explanation

Correct: D — Electric service and electrical maintenance are provided by building management under continuous supervision

240.24(B)(1) requires that electric service and electrical maintenance be provided by building management and be under continuous building management supervision before service or feeder overcurrent devices supplying multiple occupancies can be restricted to authorized personnel. A locked room or separate metering alone doesn't satisfy this — the continuous-supervision condition is what matters.

Outside feeder taps without overcurrent protection at the tap

NEC 240.92(D)

An outdoor tap can skip overcurrent protection at the tap point only if it stays outside, is physically protected, and lands on a max-six-device disconnect sized to its ampacity.

Q27 NEC 240.92(D) Code lookup

A set of outdoor feeder conductors runs from a utility transformer secondary across a yard to a building disconnect, with no overcurrent device installed at the point where the conductors originate at the transformer. The conductors are protected from physical damage, and the six-breaker group at the building disconnect limits the load to the conductor ampacity. Which section lists the conditions that must all be met to permit this tap without overcurrent protection at the connection point?

  1. A 240.92(E)
  2. B 240.92(D)
  3. C 240.92(B)
  4. D 240.92(C)
Show answer & explanation

Correct: B — 240.92(D)

240.92(D) is the outside-feeder-tap rule that lists the five conditions (physical protection, six-device limit, outdoor routing, integral disconnect location, readily accessible disconnect) permitting unprotected taps or connections made outdoors, including at a transformer secondary. 240.92(B) covers taps made from a feeder run indoors under the 10-ft/25-ft/outside-building tap rules, not a transformer secondary connection outdoors, and 240.92(C) governs separately derived system secondary conductors rather than outside taps.

General requirements for plug fuses and fuseholders

NEC 240.50

Plug fuses are limited to 125 V circuits (or 150 V line-to-neutral on a grounded system), must be hexagonal at 15 A and under, and the screw shell always lands on the load side.

Q28 NEC 240.50

A plug fuse is being installed on a system with a grounded neutral point. What is the maximum permitted line-to-neutral voltage?

  1. A 125 volts
  2. B 208 volts
  3. C 150 volts
  4. D 277 volts
Show answer & explanation

Correct: C — 150 volts

Per 240.50(A)(2), plug fuses are permitted on systems with a grounded neutral point where the line-to-neutral voltage does not exceed 150 volts. The 125-volt figure is the separate limit for line-to-line voltage under 240.50(A)(1), not the line-to-neutral allowance on a grounded system. 208 and 277 volts both exceed the permitted line-to-neutral maximum.

Unprotected secondary conductors from separately derived transformers

NEC 240.92(C)

A transformer secondary conductor can skip overcurrent protection at the connection only if it meets all three tests: fault protection, overload protection, and physical protection.

Q29 NEC 240.92(C)

An electrician wants to land separately derived transformer secondary conductors on a panel without overcurrent protection at the tap. Which of these, by itself, satisfies 240.92(C)?

  1. A The secondary conductors are 30 m (100 ft) or less with primary OCPD at no more than 150% of reflected secondary ampacity
  2. B The secondary conductors are enclosed in an approved raceway
  3. C The conductors terminate in a single overcurrent device sized to the conductor ampacity
  4. D None of these alone — short-circuit/ground-fault protection, overload protection, and physical protection must all be satisfied together
Show answer & explanation

Correct: D — None of these alone — short-circuit/ground-fault protection, overload protection, and physical protection must all be satisfied together

240.92(C) requires the conditions of 240.92(C)(1), (C)(2), and (C)(3) to all be met — short-circuit/ground-fault protection, overload protection, and physical protection. Raceway enclosure alone only satisfies (C)(3); the 30 m/150% method alone only satisfies part of (C)(1); a single terminating device alone only satisfies (C)(2). None of them individually is sufficient.

Standard ampere ratings for fuses and fixed-trip breakers

NEC 240.6(A)

Overcurrent devices are sized to the standard ratings in Table 240.6(A), rounding up to the next standard size unless a specific exception applies.

Q30 NEC 240.6(A)

Which of the following is one of the additional standard fuse ampere ratings listed outside Table 240.6(A)?

  1. A 601 amps
  2. B 1000 amps
  3. C 500 amps
  4. D 50 amps
Show answer & explanation

Correct: A — 601 amps

240.6(A) states that additional standard ampere ratings for fuses shall be 1, 3, 6, and 601 amps. 500, 50, and 1000 amps are not part of that supplemental list (500 and 50 fall within the main Table 240.6(A) progression, and 1000 is not called out at all here).

Tap conductors: where else their OC protection is governed

NEC 240.4(E)

240.4(E) doesn't set tap rules itself — it's a signpost pointing to six other sections where tap conductor overcurrent protection actually lives.

Q31 NEC 240.4(E) Code lookup

A single motor is fed by tap conductors sized per the motor tap rules, run to a disconnect ahead of the branch-circuit short-circuit protective device. Which NEC section lists this as a permitted method of protecting tap conductors against overcurrent?

  1. A 240.4(D)
  2. B 240.4(F)
  3. C 240.4(E)
  4. D 240.5(B)(2)
Show answer & explanation

Correct: C — 240.4(E)

240.4(E) is the list of permitted alternative overcurrent-protection schemes for tap conductors, including the single-motor tap rule (referring out to 430.53(D)); 240.4(F) instead covers transformer secondary conductors, a different tap scenario entirely.

Type S adapter and fuseholder design safeguards

NEC 240.54

Type S adapters screw into an Edison base but lock in permanently and only accept Type S fuses, so a homeowner can't oversize a fuse or bridge it.

Q32 NEC 240.54

An electrician installs a Type S adapter into an existing Edison-base fuseholder to upgrade it. Which statement about the adapter is correct?

  1. A It accepts any standard Edison-base fuse after installation
  2. B It can be unscrewed later if the homeowner wants the Edison base back
  3. C Once inserted, it cannot be removed from the fuseholder
  4. D It must be reinstalled every time the fuse blows
Show answer & explanation

Correct: C — Once inserted, it cannot be removed from the fuseholder

Per 240.54(C), Type S adapters are designed so that once inserted in a fuseholder, they cannot be removed. This prevents reverting to an Edison base that would accept oversized fuses. It does not become removable, and per 240.54(B) it restricts the holder to Type S fuses only, not standard Edison-base fuses.

Transformer secondary conductor protection (untapped feeder to xfmr)

NEC 240.21(C)

Secondary conductors can run without overcurrent protection at the transformer only if they qualify under one of the six specific exceptions in 240.21(C)(1)–(6).

Q33 NEC 240.21(C)

An installer wants to size transformer secondary conductors using the 240.4(B) next-standard-size-up rule instead of matching a specific secondary conductor exception. Is this permitted?

  1. A No, because transformer secondary conductors always require overcurrent protection at the secondary
  2. B Yes, but only for secondary conductors 25 ft (7.5 m) or less
  3. C Yes, 240.4(B) applies to all feeder and secondary conductors alike
  4. D No, 240.21(C) specifically prohibits using 240.4(B) for transformer secondary conductors
Show answer & explanation

Correct: D — No, 240.21(C) specifically prohibits using 240.4(B) for transformer secondary conductors

240.21(C) states plainly that 240.4(B) shall not be permitted for transformer secondary conductors, so the next-size-up rounding allowance can't substitute for meeting one of the (C)(1) through (C)(6) exceptions. The 25 ft length figure is a condition found in one of those specific exceptions, not a blanket allowance, and secondary conductors are not always required to have protection at the secondary — that's the entire point of the 240.21(C) exception family.

Secondary conductors from a feeder-tapped transformer

NEC 240.21(C)(5)

A transformer secondary tap up to 25 ft skips the primary tap rules entirely if it meets its own three conditions: the 1/3 ampacity rule, a single terminating OCPD, and physical protection.

Q34 NEC 240.21(C)(5)

An electrician wants to run secondary conductors from a transformer without protecting them at the secondary, under 240.21(C)(6). Which of these is NOT one of the required conditions?

  1. A The conductors must also satisfy the primary tap conditions in 240.21(B)(3)
  2. B The conductors terminate in a single circuit breaker or set of fuses limiting load current to the conductor's ampacity
  3. C The conductors do not exceed 7.5 m (25 ft) in length
  4. D The conductors are enclosed in an approved raceway or otherwise protected from physical damage
Show answer & explanation

Correct: A — The conductors must also satisfy the primary tap conditions in 240.21(B)(3)

240.21(C)(6) is a standalone rule with its own three conditions: the ampacity/voltage-ratio requirement, single-OCPD termination, and physical protection. It does not require also meeting 240.21(B)(3) — that cross-reference to the primary tap rule belongs to the separate allowance in 240.21(C)(5), not (C)(6).

Renewable fuses and fuse reducers — replacement-only rules

NEC 240.60(D)

Renewable Class H fuses are replacement-only in existing installations with no sign of overfusing or tampering, and fuse reducers must be listed.

Q35 NEC 240.60(D) Code lookup

An electrician is servicing a panel in an older building and finds a Class H renewable-element cartridge fuse that has blown. There's no sign the circuit was ever overfused or tampered with. Which section covers whether this type of fuse can be reinstalled as a replacement?

  1. A 240.54(D)
  2. B 240.51(B)
  3. C 240.60(B)
  4. D 240.60(D)
Show answer & explanation

Correct: D — 240.60(D)

240.60(D) is the specific rule permitting renewable-type Class H cartridge fuses only as replacements in existing installations with no evidence of overfusing or tampering. 240.51(B) is the parallel replacement-only rule but it governs Edison-base plug fuses, not cartridge fuses.

Cartridge fuse voltage classification and 300-volt type usage

NEC 240.61

Cartridge fuses are voltage-classified, not just amp-rated — a 300-volt type fuse can't be used on a circuit exceeding 300 volts between conductors.

Q36 NEC 240.61 Code lookup

A single-phase line-to-neutral load is fed from a 3-phase, 4-wire, solidly grounded neutral service, and the line-to-neutral voltage measures 277 volts. An electrician wants to confirm cartridge fuses rated for 300 volts are permitted on this circuit. Which section addresses this specific usage of 300-volt type cartridge fuses?

  1. A 240.61
  2. B 240.60(B)
  3. C 240.60(A)
  4. D 240.50(A)
Show answer & explanation

Correct: C — 240.60(A)

240.60(A) is the maximum-voltage rule that specifically permits 300-volt type cartridge fuses on line-to-neutral circuits from a solidly grounded 3-phase, 4-wire source not exceeding 300 volts. 240.61 only classifies fuses by voltage/amperage range in general, not this specific usage; 240.50(A) is the analogous maximum-voltage rule for plug fuses, not cartridge fuses.

Fuseholder noninterchangeability by class and current-limiting type

NEC 240.60(B)

Cartridge fuseholders must physically block a fuse rated for lower current or higher voltage, and must block non-current-limiting fuses from current-limiting slots.

Q37 NEC 240.60(B) Code lookup

A supply house sells cartridge fuseholders that physically prevent a lower-voltage-rated fuse position from accepting a higher-voltage fuse, and separately reject non-current-limiting fuses where current-limiting types are required. Which section establishes this noninterchangeability requirement for 0-6000-ampere cartridge fuseholders?

  1. A 240.60(D)
  2. B 240.60(B)
  3. C 240.60(A)
  4. D 240.61
Show answer & explanation

Correct: B — 240.60(B)

240.60(B) is the noninterchangeability rule for 0-6000-ampere cartridge fuseholders, covering both class/voltage rejection and current-limiting-only fuseholders. 240.60(A) only sets the 300-volt maximum voltage marking rule, and 240.61 merely classifies fuses by ampere/voltage/interrupting rating rather than requiring physical fuseholder rejection.

Ampere rating marking: durability, visibility, and location

NEC 240.83(A)

Every circuit breaker's ampere rating must stay durably visible after installation, and breakers 100 A/1000 V or less must have that rating molded or stamped into the handle or escutcheon.

Q38 NEC 240.83(A)

A 90-ampere, 480-volt circuit breaker has its ampere rating printed only on an adhesive label stuck to the handle. Does this comply with 240.83(B)?

  1. A No, because 240.83(B) only applies to breakers rated over 100 A
  2. B Yes, because any visible marking on the handle satisfies the requirement regardless of method
  3. C Yes, because 480-volt breakers are exempt from the handle-marking requirement
  4. D No, because breakers rated 100 A or less and 1000 V or less must have the rating molded, stamped, or etched into the handle or escutcheon
Show answer & explanation

Correct: D — No, because breakers rated 100 A or less and 1000 V or less must have the rating molded, stamped, or etched into the handle or escutcheon

Under 240.83(B), breakers rated 100 A or less and 1000 V or less must have the ampere rating molded, stamped, etched, or similarly marked into the handle or escutcheon area. This 90 A, 480 V breaker falls within that threshold, so an adhesive label alone does not comply. The rule applies at or below the 100 A / 1000 V threshold, not above it, and there is no voltage-based exemption at 480 V.

Circuit breaker on/off position indication

NEC 240.81

A breaker must clearly show open ("off") or closed ("on"), and if the handle moves up/down, "up" must mean "on."

Q39 NEC 240.81 Code lookup

A journeyman is installing a panel where the breaker handles operate straight up and down instead of side to side. Which section states that in this vertical-throw arrangement, the 'up' position must be the 'on' position?

  1. A 240.83
  2. B 240.83(D)
  3. C 240.81
  4. D 240.80
Show answer & explanation

Correct: C — 240.81

240.81 specifically requires breakers to indicate open/closed and sets the 'up equals on' rule for vertically operated handles. 240.80 only covers the method of operation (manual plus automatic trip), and 240.83 governs ampere-rating marking, not on/off position indication.

Overcurrent protection of flexible cords, cables, and fixture wires

NEC 240.5

Flexible cords, flexible cables, and fixture wires must be protected at their own ampacity, not at the ampacity of the branch-circuit conductors feeding them.

Q40 NEC 240.5

An extension cord is connected to a 20 A branch circuit. According to 240.5(A), what determines the overcurrent protection required for that cord?

  1. A The ampacity of the cord itself, per Table 400.5(A)(1) or Table 400.5(A)(2)
  2. B The rating of the attachment plug on the cord
  3. C The horsepower rating of any motor load connected to the cord
  4. D The ampacity of the branch-circuit conductors supplying the receptacle
Show answer & explanation

Correct: A — The ampacity of the cord itself, per Table 400.5(A)(1) or Table 400.5(A)(2)

240.5(A) requires flexible cord to be protected by an overcurrent device sized to its own ampacity from Table 400.5(A)(1) or Table 400.5(A)(2), not by the ampacity of the upstream branch-circuit conductors or plug rating.

Guarding against injury from fuses and circuit breakers

NEC 240.41

Fuses and breakers must be placed or shielded so operation can't burn anyone, and any handle or lever that moves suddenly must be guarded or isolated from bystanders.

Q41 NEC 240.41 Code lookup

An electrician is installing a panelboard in a mechanical room and wants to make sure the circuit breaker handles won't strike anyone standing nearby when tripped or reset. Which section addresses guarding against injury from suddenly moving handles or levers?

  1. A 240.30(B)
  2. B 240.41(A)
  3. C 240.40
  4. D 240.41(B)
Show answer & explanation

Correct: D — 240.41(B)

240.41(B) specifically requires that handles or levers of circuit breakers likely to strike nearby persons be guarded or isolated. 240.41(A) instead addresses burn/injury protection from fuse and breaker operation generally (arcing/location), and 240.30(B) covers operating handle accessibility for supply-side equipment, not injury guarding.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access