Six-disconnect rule and grouping of disconnects
NEC 225.33 An outdoor feeder or branch circuit supply can have at most six disconnects in one location, and those disconnects must be grouped together and marked for the load they serve.
Q1 NEC 225.33
Under 225.33(A), what is the maximum number of switches or circuit breakers permitted as the disconnecting means for one supply, grouped in one location?
- A Four
- B Eight
- C Six
- D Two
Show answer & explanation
Correct: C — Six
225.33(A) limits the disconnecting means for each supply to not more than six switches or circuit breakers, whether mounted in a single enclosure, a group of separate enclosures, or a switchboard. Four and two are within the allowed range but not the maximum, and eight exceeds the limit set by this section.
Overhead clearance from roofs and nonbuilding structures
NEC 225.19(A) Open overhead conductors need 8 ft 6 in. above a roof (kept 3 ft back from the edge), with narrow exceptions for low-slope-free roofs and short overhangs, and 3 ft minimum from signs, tanks, and antennas.
Q2 NEC 225.19(A)
An overhead service span crosses a low-slope roof (less than 4 in 12) not subject to pedestrian or vehicular traffic. What vertical clearance above the roof surface is required, per 225.19(A)?
- A 2.6 m (8 ft 6 in.)
- B 3.0 m (10 ft)
- C 900 mm (3 ft)
- D 450 mm (18 in.)
Show answer & explanation
Correct: A — 2.6 m (8 ft 6 in.)
225.19(A) sets the default clearance above a roof at 2.6 m (8 ft 6 in.), maintained 3 ft in all directions from the roof edge. The 900 mm figure only applies to roofs with a 4-in-12 slope or greater at 300V or less, and the 450 mm figure only applies to a qualifying short overhang run — neither condition is met here.
Disconnecting means requirement and placement
NEC 225.31 Every building fed by outside conductors needs a disconnect for all ungrounded conductors, placed at the readily accessible point nearest where those conductors enter.
Q3 NEC 225.31
Under 225.31(A), the disconnecting means must be capable of disconnecting which conductors supplying or passing through a building?
- A All ungrounded conductors
- B Only the grounded (neutral) conductor
- C Only conductors rated over 100 amperes
- D Only conductors that terminate inside the building
Show answer & explanation
Correct: A — All ungrounded conductors
225.31(A) requires means to disconnect all ungrounded conductors that supply or pass through the building or structure. The grounded conductor isn't the target of this disconnecting requirement, and there's no ampere threshold or limitation to terminating conductors only.
Minimum ampere rating of feeder/branch-circuit disconnects
NEC 225.39 A feeder or branch-circuit disconnect must meet the calculated load, but it can never be rated below the 225.39 floor for its installation type.
Q4 NEC 225.39
A feeder disconnecting means is being sized for a one-family dwelling. Per 225.39, what is the minimum rating allowed?
- A 60 amperes
- B 15 amperes
- C 30 amperes
- D 100 amperes, 3-wire
Show answer & explanation
Correct: D — 100 amperes, 3-wire
225.39(C) sets a dedicated minimum of 100 amperes, 3-wire for one-family dwelling feeder disconnects. The 60-ampere minimum applies to installations that don't fit any of the other named categories under 225.39(D), and the 15- and 30-ampere minimums apply to single- and two-circuit installations, not dwelling feeders.
Emergency disconnect for one- and two-family dwellings
NEC 225.41 One- and two-family dwellings need an outdoor, readily accessible service disconnect marked EMERGENCY DISCONNECT in red and white.
Q5 NEC 225.41
Where must the emergency disconnect required by 225.41 be installed on a one-family dwelling?
- A Inside the main electrical room, adjacent to the panelboard
- B In any accessible location, indoors or outdoors, within 50 ft of the meter
- C In a readily accessible outdoor location on or within sight of the dwelling unit
- D In a locked outdoor enclosure accessible only to the utility
Show answer & explanation
Correct: C — In a readily accessible outdoor location on or within sight of the dwelling unit
225.41(A)(1) requires the disconnect to be in a readily accessible outdoor location on or within sight of the dwelling unit. An indoor location doesn't meet the outdoor requirement, and there's no 50 ft or utility-only-access provision in this section.
Surge protection for feeders to dwelling/sleeping occupancies
NEC 225.42 A feeder serving dwelling units, dorms, hotel/motel guest rooms, or nursing-home sleeping rooms needs an SPD at the downstream distribution equipment, rated at least 10 kA, Type 1 or Type 2.
Q6 NEC 225.42
A feeder supplies the distribution panel for a hotel guest room. Per 225.42, what is required?
- A A surge-protective device only if the feeder originates at a separate structure
- B A surge-protective device only if the guest room contains life safety equipment
- C No surge protection is required because the requirement applies only to services, not feeders
- D A surge-protective device installed in or adjacent to that distribution equipment
Show answer & explanation
Correct: D — A surge-protective device installed in or adjacent to that distribution equipment
225.42(A) specifically requires an SPD where a feeder supplies guest rooms and guest suites of hotels and motels, among other sleeping occupancies — this is a feeder-level requirement, not limited to services or separate structures. The location is set by 225.42(B): in or adjacent to the load-side distribution equipment.
Plaque/directory identification for multiple supplies
NEC 225.37 If a building has more than one feeder, branch circuit, or service feeding it or passing through it, every disconnect location needs a plaque or directory listing all the others and what each serves.
Q7 NEC 225.37
A commercial building receives two separate services and also has a feeder from an adjacent building passing through it. Per 225.37, what is required at each feeder and branch-circuit disconnect location?
- A A plaque only if the feeders originate from different utility companies
- B A permanent plaque or directory identifying all other services, feeders, or branch circuits and the area each serves
- C Nothing extra, since each disconnect is already labeled with its own circuit rating
- D A single directory posted only at the main service disconnect, covering the whole building
Show answer & explanation
Correct: B — A permanent plaque or directory identifying all other services, feeders, or branch circuits and the area each serves
225.37 requires a permanent plaque or directory at each feeder and branch-circuit disconnect location, not just the main one, and it must denote all other supplies and the area each serves. Ordinary circuit labeling doesn't satisfy this, and the requirement doesn't hinge on whether utilities differ.
One feeder/branch circuit per building, and exceptions
NEC 225.30 A building fed from another building's service gets only one feeder or branch circuit, unless it fits one of the seven named exceptions in 225.30(A) through (F).
Q8 NEC 225.30
A detached garage is supplied by a feeder from the main dwelling's service equipment. Under what condition would a second feeder to the garage be permitted?
- A If the garage owner simply prefers a backup supply
- B If the garage is more than 50 feet from the dwelling
- C If the second feeder is only for a legally required standby system
- D If the first feeder is undersized for the garage load
Show answer & explanation
Correct: C — If the second feeder is only for a legally required standby system
225.30(A)(3) permits an additional feeder or branch circuit specifically for legally required standby systems. Distance from the dwelling, owner preference, and an undersized first feeder are not among the 225.30(A) through (F) exceptions — the fix for an undersized feeder is resizing it, not adding a second one.
Overhead conductor clearance above grade, streets, and traffic areas
NEC 225.18 Overhead conductor clearance climbs with both what's below (foot traffic vs. trucks vs. rail) and the voltage to ground — never assume 10 ft covers everything.
Q9 NEC 225.18
An overhead 1000-volt-class span crosses a residential driveway at 250 volts to ground. What is the minimum required clearance?
- A 18 ft
- B 12 ft
- C 15 ft
- D 10 ft
Show answer & explanation
Correct: B — 12 ft
Per 225.18(2), residential property and driveways at or below 300 volts to ground require only 12 ft of clearance. 10 ft applies only to pedestrian-only areas at or below 150 volts. 15 ft would apply to this same residential setting only if the voltage exceeded 300 volts to ground. 18 ft is for streets and truck traffic, not residential driveways.
Point and means of attachment to a building
NEC 225.16 225.16 sets no independent standard — the point of attachment follows 230.26 and the means of attachment follows 230.27, exactly as for service conductors.
Q10 NEC 225.16 Code lookup
A service drop needs to be run to a two-story residence. Before installing the attachment fitting, which section tells the installer where on the building the point of attachment must be located?
- A 225.16(A)
- B 225.16(B)
- C 225.15
- D 225.19(C)
Show answer & explanation
Correct: A — 225.16(A)
225.16(A) governs the point of attachment itself, referring the installer to 230.26. 225.16(B) instead covers the means/fitting used to attach, and 225.15 addresses supports over buildings — not where the attachment point goes.
Insulation requirements for outdoor conductors near buildings
NEC 225.4 Open overhead conductors within 3.0 m (10 ft) of a building must be insulated for the nominal voltage; conductors in cables or raceways need thermoset or thermoplastic insulation, wet-location rated if wet.
Q11 NEC 225.4
Under 225.4, open individual aerial overhead conductors must be insulated for the nominal voltage when they run within what distance of a building or structure?
- A 3.0 m (10 ft)
- B 3.7 m (12 ft)
- C 1.5 m (5 ft)
- D 4.5 m (15 ft)
Show answer & explanation
Correct: A — 3.0 m (10 ft)
225.4 sets the proximity trigger at 3.0 m (10 ft) from any building or structure other than supporting poles or towers. The 1.5 m, 3.7 m, and 4.5 m distances are clearances used elsewhere in the Code (such as vertical or over-roof clearances), not the insulation trigger in 225.4.
Minimum conductor size for overhead spans and festoon lighting
NEC 225.6 Open overhead conductors need 10 AWG copper up to 50 ft (8 AWG copper past that, or a messenger wire); festoon lighting drops to 12 AWG only if messenger-supported.
Q12 NEC 225.6
An open overhead span of individual conductors between two structures runs 60 ft. Which is a code-compliant option per 225.6(A)?
- A 10 AWG copper conductors with no messenger wire
- B 10 AWG aluminum conductors with no messenger wire
- C 12 AWG copper conductors supported by a messenger wire
- D 8 AWG copper conductors with no messenger wire
Show answer & explanation
Correct: D — 8 AWG copper conductors with no messenger wire
225.6(A) requires at least 8 AWG copper (or 6 AWG aluminum) for spans longer than 15 m (50 ft) unless a messenger wire is used. The 10 AWG copper and 10 AWG aluminum options are only valid for spans up to 50 ft, and 12 AWG doesn't meet the minimum size for overhead spans at all, messenger or not — that size threshold applies to festoon lighting under 225.6(B), not general overhead spans.
Construction requirements for disconnect switches
NEC 225.38 A building/structure disconnect must open all ungrounded conductors together by hand, provide a way to disconnect the grounded conductor, and clearly show open or closed.
Q13 NEC 225.38 Code lookup
A power-operated switch is proposed as the building disconnecting means for a detached structure. During normal operation this is fine, but the inspector asks what happens if utility power to the building fails while someone needs to open the switch. Which section addresses the requirement that applies here?
- A 225.36
- B 225.38(B)
- C 225.38(D)
- D 225.38(A)
Show answer & explanation
Correct: D — 225.38(A)
225.38(A) requires that a power-operable disconnect be openable by hand in the event of a power failure. 225.38(B) governs simultaneous pole opening (a different concern), and 225.36 addresses the type of disconnecting means, not manual operability during a power outage.
Final-span clearance from windows, doors, and building openings
NEC 225.19(D) Final spans must stay 3 ft from openable windows and doors, keep vertical clearance near reachable surfaces, and never block or run beneath material-handling openings.
Q14 NEC 225.19(D)
A final span attaches to a dwelling and passes near a second-story window designed to be opened. What is the minimum required clearance from that window?
- A 900 mm (3 ft)
- B 1.0 m (3.5 ft)
- C No clearance is required if the span is a final span
- D 1.2 m (4 ft)
Show answer & explanation
Correct: A — 900 mm (3 ft)
225.19(D)(1) requires final spans to be kept not less than 900 mm (3 ft) from windows designed to be opened. Being a final span allows attachment to the building, but does not remove this clearance requirement, so the last option is wrong. The other distances are not the code value.
Open-conductor supports, spacing, and separation
NEC 225.12 Open conductors need approved insulating supports, spacing per Table 230.51(C), 100 mm from other circuits, and — on poles — climbing space that scales with voltage and communications proximity.
Q15 NEC 225.12
An electrician wants to support open conductors on a wood cross-arm using a metal bracket with no insulating material. Does this comply with 225.12?
- A No, open conductors may only be run in conduit
- B Yes, as long as the conductors are separated by 100 mm (4 in.)
- C Yes, any bracket rated for outdoor use is acceptable
- D No, supports must be knobs, racks, brackets, or strain insulators made of glass, porcelain, or other approved material
Show answer & explanation
Correct: D — No, supports must be knobs, racks, brackets, or strain insulators made of glass, porcelain, or other approved material
225.12 requires open-conductor supports to be knobs, racks, brackets, or strain insulators made of glass, porcelain, or other approved material — a bare metal bracket with no insulating value doesn't meet that. Conductor separation is a separate requirement under 225.14(A) and doesn't substitute for proper supports, and open conductors aren't required to be in conduit under this section.
Outdoor lampholder wiring and lamp location rules
NEC 225.24 Pendant lampholder connections must be staggered and piercing-type terminals need stranded conductors; outdoor lamps must sit below energized conductors unless relamping is made safe.
Q16 NEC 225.24
An outdoor pendant lampholder uses terminals that puncture the wire insulation to make contact. What conductor type must be used?
- A Solid conductors, but only in dry locations
- B Either solid or stranded, as long as connections are staggered
- C Solid conductors only, for a reliable insulation seal
- D Stranded conductors only
Show answer & explanation
Correct: D — Stranded conductors only
225.24 requires that lampholders with insulation-piercing terminals be attached only to stranded conductors. Solid conductors, staggering aside, are not a substitute for this requirement — staggering addresses spacing of connections, not conductor type.