When a primary protector is required
NEC 805.90(A) Aerial or exposed communications circuits need a listed primary protector wherever they can contact power conductors or face lightning exposure.
Q1 NEC 805.90(A)
Under 805.90(A), a communications circuit located entirely underground within the block containing the served building still requires a listed primary protector if:
- A It exceeds 42 m (140 ft) in length
- B It is exposed to accidental contact with power conductors operating at over 300 volts to ground
- C It is installed in nonmetallic conduit
- D It serves a metal-frame building
Show answer & explanation
Correct: B — It is exposed to accidental contact with power conductors operating at over 300 volts to ground
805.90(A) requires a primary protector on any circuit within the block, aerial or underground, that is exposed to accidental contact with power conductors over 300 volts to ground. Length, building frame material, and conduit type are not the triggers named in this section.
How communications cables enter the building: bushing vs. raceway rules
NEC 805.50(C) Where a primary protector sits inside the building, the entrance cable needs an insulating bushing or metal raceway, sloped upward or drip-looped, with the raceway grounded and service-headed.
Q2 NEC 805.50(C)
A primary protector is installed inside a building. Communications wires and cables enter through masonry. Under 805.50(C)(1), is an insulating bushing required?
- A Only if the primary protector is omitted under 805.90(A)(1)
- B Yes, masonry entry always requires a bushing in addition to the raceway
- C Only if the cable is not metal-sheathed
- D No, passing through masonry is one of the listed exceptions to the bushing requirement
Show answer & explanation
Correct: D — No, passing through masonry is one of the listed exceptions to the bushing requirement
Per 805.50(C)(1), the insulating bushing is not required where the entering wires and cables pass through masonry — this is one of four independent exceptions, not something that depends on sheath type or protector omission.
Keeping communications wires separated from power conductors
NEC 805.50(A) Unshielded communications wires feeding a primary protector must be listed, then kept at least 100 mm (4 in.) from power conductors — or permanently separated by a rigid nonconductor.
Q3 NEC 805.50(A)
Listed communications cable runs alongside open (not-in-raceway) electric power conductors on the outside of a building. What separation satisfies 805.50(B)?
- A No separation is required as long as both are listed
- B At least 100 mm (4 in.), or a continuous fixed nonconductor separating the two
- C Separation is only required if the power conductors exceed 600 volts
- D At least 300 mm (12 in.) in all cases, with no substitute permitted
Show answer & explanation
Correct: B — At least 100 mm (4 in.), or a continuous fixed nonconductor separating the two
805.50(B) sets the baseline separation at 100 mm (4 in.) from open electric light or power conductors, or a continuous, firmly fixed nonconductor such as porcelain tubing as an alternative. There's no 12-inch minimum in this rule, listing of the cable doesn't waive separation, and the requirement isn't limited to conductors over 600 volts.
Fuseless vs. fused primary protector types
NEC 805.90(A)(1) Fuseless-type primary protectors are allowed only when the specific safe-fusing conditions of 805.90(A)(1) are met; otherwise a fused-type protector with an arrester and fuse per line conductor is required.
Q4 NEC 805.90(A)(1) Code lookup
A telephone drop cable enters a building through a cable with an effectively grounded metallic sheath, and the installer wants to skip the fused-type protector by showing the sheath conductors will safely fuse on any current above the protector's and bonding conductor's current-carrying capacity. Which section lists the conditions that permit use of a fuseless-type primary protector?
- A 805.90(B)
- B 805.90(A)(1)
- C 805.90(A)(2)
- D 805.93(A)
Show answer & explanation
Correct: B — 805.90(A)(1)
805.90(A)(1) lists the five conditions under which fuseless-type primary protectors are permitted. 805.90(A)(2) instead governs fused-type protectors, used when none of the 805.90(A)(1) conditions are met, and 805.93(A) covers sheath grounding at building entry, not protector type selection.
Where primary protectors may and may not be located
NEC 805.90(B) Put the primary protector as close as practicable to the point of entrance, and never in a hazardous location or near easily ignitible material.
Q5 NEC 805.90(B) Code lookup
A technician is installing a telephone service on a single-family dwelling and must decide where to mount the primary protector relative to the point where the communications cable enters the structure. Which section specifies where the primary protector must be located?
- A 805.170(A)
- B 805.50(C)
- C 805.90(B)
- D 805.90(C)
Show answer & explanation
Correct: C — 805.90(B)
805.90(B) is the Location rule, requiring the primary protector to be in, on, or immediately adjacent to the structure and as close as practicable to the point of entrance. 805.50(C) instead governs how the communications wire/cable itself enters the building, and 805.170(A) just lists primary protectors as a required protector type without addressing placement.
Listing requirements for primary and secondary protectors
NEC 805.170 Primary protectors arrest overvoltage line-to-ground; secondary protectors limit current — both must be listed, and only one specific standard applies to each.
Q6 NEC 805.170
Under 805.170, how must communications circuit protectors be qualified for use?
- A They must be field-tested by a licensed electrician before installation
- B They must be identified for use only in wet locations
- C They must be approved by the local AHJ on a case-by-case basis
- D They must be listed as either a primary or secondary protector
Show answer & explanation
Correct: D — They must be listed as either a primary or secondary protector
805.170 requires protectors to be listed in accordance with 805.170(A) (primary) or 805.170(B) (secondary). There's no field-test or case-by-case AHJ approval path in this section, and wet-location identification isn't the qualifying requirement here.
Grounding, bonding, or interrupting communications cable sheaths
NEC 805.93 A metallic sheath on a communications cable must be grounded, bonded per 800.100, or broken with an insulating joint — as close as practicable to where the cable enters or terminates.
Q7 NEC 805.93
A communications cable with a metallic sheath enters a building. Per 805.93(A), where must the sheath be grounded, bonded, or interrupted?
- A Within 6 ft of the building's grounding electrode system
- B As close as practicable to the point of entrance
- C At the nearest panelboard, regardless of distance
- D Only at the equipment the cable ultimately serves
Show answer & explanation
Correct: B — As close as practicable to the point of entrance
805.93(A) requires the grounding, bonding, or interruption to be as close as practicable to the point of entrance — not tied to panelboard location, end equipment, or a fixed 6 ft distance from the grounding electrode system.
Substituting CATV coaxial cable types
NEC 820.154 Table 820.154 lets a coaxial CATV cable rated for tougher conditions substitute for one rated for lighter duty, but every substitute must still be coaxial cable.
Q8 NEC 820.154
Per 820.154, which cable is permitted to substitute for a CATV coaxial cable listed for riser use?
- A A coaxial cable listed for plenum use
- B A coaxial cable listed only for limited (dwelling) use
- C A CMR-rated communications cable
- D Any cable jacketed for riser-rated locations, regardless of type
Show answer & explanation
Correct: A — A coaxial cable listed for plenum use
820.154 allows a coax cable with a more stringent listing to replace one with a less stringent listing, so plenum-rated coax can stand in for riser-rated coax. The CMR-rated communications cable fails because 820.154 requires the substitute to be coaxial-type, not a communications cable. The limited-use coax is a lower rating than riser, so it can't substitute upward. Any riser-rated cable regardless of type ignores the coax-only requirement.
CATV primary protector location and hazardous-location limits
NEC 820.93(C) The CATV primary protector goes as close as practicable to the cable's entrance point, and never in a hazardous location or near easily ignitible material.
Q9 NEC 820.93(C)
Per 820.93(C), where should a listed CATV primary protector be located relative to the cable's building entrance point?
- A At the service equipment, regardless of distance from the entrance point
- B Within 1.8 m (6 ft) of the nearest receptacle outlet
- C Anywhere inside the building, provided it is accessible
- D As close as practicable to the entrance point, or integral to the ground block
Show answer & explanation
Correct: D — As close as practicable to the entrance point, or integral to the ground block
820.93(C) requires the primary protector to be located as close as practicable to the cable's entrance point, on either side, or integral to the ground block. Placing it elsewhere in the building or tying its location to service equipment or receptacle spacing are not the rule in this section.
Bonding/grounding the coaxial cable shield
NEC 820.100 The coax shield must be grounded or bonded — usually to the equipment grounding conductor, but never through a cord-and-plug connection.
Q10 NEC 820.100
An installer wants to ground a coaxial cable shield by plugging a bonding device into a nearby grounded receptacle using a cord and plug. Is this permitted under 820.100?
- A Yes, but only for drop cable, not building-entrance cable
- B No, receptacle connections of any kind are prohibited for coax shield grounding
- C No, cord-and-plug connections are not permitted for this grounding path
- D Yes, as long as the receptacle is verified grounded
Show answer & explanation
Correct: C — No, cord-and-plug connections are not permitted for this grounding path
820.100 explicitly permits connecting to the equipment grounding conductor through a grounded receptacle using a dedicated bonding jumper and a permanently connected listed device, but states that use of a cord and plug for this connection is not permitted. The grounded-receptacle option itself is allowed when done with a permanent, listed device — it's specifically the cord-and-plug method that's barred.
When primary electrical protection is required for network-powered broadband conductors
NEC 830.90(A) Ungrounded, uninterrupted network-powered broadband conductors need primary protection whenever they run aerial outside a block, or are exposed to lightning or contact with over-300-volt power conductors within the block.
Q11 NEC 830.90(A)
A network-powered broadband communications conductor is grounded and interrupted, and runs aerially outside the block containing the served building. Per 830.90(A), is primary electrical protection required?
- A Yes, all aerial network-powered broadband conductors require primary protection regardless of grounding
- B No, but only because it is confined within the block
- C Yes, because it is not confined within a block
- D No, because the conductor is grounded and interrupted, the aerial-outside-block trigger does not apply
Show answer & explanation
Correct: D — No, because the conductor is grounded and interrupted, the aerial-outside-block trigger does not apply
830.90(A) requires primary protection on conductors that are neither grounded nor interrupted and run partly or entirely in aerial cable not confined within a block. Since this conductor is grounded and interrupted, that trigger doesn't apply, regardless of whether it's aerial or outside the block.
Aerial cable clearance over ground, roads, and pools
NEC 830.44(B) Overhead network-powered broadband cables need more clearance the more traffic or hazard is below them: pedestrians only, vehicles, or pools each set a different minimum.
Q12 NEC 830.44(B)
An aerial span of network-powered broadband communications cable crosses a commercial parking lot that is regularly used by delivery trucks. What is the minimum required clearance from the ground?
- A 4.7 m (15½ ft)
- B 2.9 m (9½ ft)
- C 5.5 m (18 ft)
- D 3.5 m (11½ ft)
Show answer & explanation
Correct: A — 4.7 m (15½ ft)
Per 830.44(B)(3), areas subject to truck traffic — including parking areas, public streets, and similar vehicle-traversed land — require 4.7 m (15½ ft) of clearance. The 3.5 m distance only applies to residential property, driveways, and commercial areas NOT subject to truck traffic, and 2.9 m applies only to pedestrian-only walkways.
Listing & marking rules for network-powered broadband cables
NEC 830.179 Network-powered broadband cables must be listed factory-assembled cables, and only the BMU/BLU types are rated for direct burial or outdoor underground use.
Q13 NEC 830.179
An installer needs a network-powered broadband medium-power cable for a direct-buried outdoor run. Which type satisfies this per 830.179(B)?
- A Any jacketed coaxial cable rated 300 volts
- B Type BLU
- C Pre-2000 CATV coaxial cable installed under Article 820
- D Type BMU
Show answer & explanation
Correct: D — Type BMU
830.179(B) requires Type BMU cable to be jacketed and listed as suitable for outdoor underground use for medium-power circuits. Type BLU is the low-power counterpart under 830.179(C), a generic 300-volt-rated jacketed coax isn't automatically underground-listed, and the pre-2000 CATV exemption in 830.179 only excuses old low-power coax from the listing requirement — it doesn't qualify as underground-rated new construction.
Classifying network-powered broadband systems by power level
NEC 830.15 Network-powered broadband sources are classified as low-power or medium-power based on voltage, current, and power limits in Table 830.15.
Q14 NEC 830.15
A DC network-powered broadband source operates at 175 volts to ground. Under what condition can it still be classified as a medium-power source per 830.15(2)?
- A It automatically qualifies as long as it is listed to UL 60950-21
- B The current to ground is limited to 10 mA dc, and it meets Table 830.15's current and power limits for medium-power sources
- C The current to ground is limited to 5 mA dc, regardless of Table 830.15 limits
- D It cannot be classified as medium-power because it exceeds 150 volts to ground
Show answer & explanation
Correct: B — The current to ground is limited to 10 mA dc, and it meets Table 830.15's current and power limits for medium-power sources
830.15(2) allows DC sources exceeding 150 V to ground but not more than 200 V to ground to be classified as medium-power only if the current to ground is limited to 10 mA dc AND the source meets Table 830.15's current and power limitations for medium-power sources. 150 V doesn't disqualify it — that's the whole point of the exception — and UL 60950-21 is referenced only as a listing standard, not a substitute for meeting the classification criteria.
Sharing raceways and cable trays with other circuits
NEC 830.133(A)(1) Low-power broadband cable can mix with most communications-type circuits, medium-power cannot mix with any of them, and neither can share space with light or power conductors unless separated by a barrier.
Q15 NEC 830.133(A)(1)
A medium-power network-powered broadband communications cable is being installed. Which of the following may NOT share the same cable tray with it?
- A Another medium-power broadband cable from a different system
- B A Class 2 remote-control circuit cable
- C A low-power network-powered broadband communications cable
- D Another medium-power network-powered broadband communications cable
Show answer & explanation
Correct: B — A Class 2 remote-control circuit cable
830.133(A)(1)(d) bars medium-power network-powered broadband cables from sharing a raceway, tray, box, or enclosure with Class 2 or Class 3 circuits, or with power-limited fire alarm circuits. Broadband cables (low- or medium-power) may share space with each other per 830.133(A)(1)(a).
Grounding network-powered broadband cable shields and metallic members
NEC 830.93 Whether the network-powered broadband cable enters the building or terminates outside at the NIU, the shield must be grounded per 800.100 and other metallic members grounded or interrupted, as close as practicable to that entry or attachment point.
Q16 NEC 830.93 Code lookup
An underground network-powered broadband communications cable enters a building and its shield needs to be grounded. The metallic strength members are not used for communications or powering. Which section covers grounding or interrupting those metallic members at the point of entrance?
- A 830.93(A)
- B 830.90(B)
- C 830.47(A)
- D 830.93(B)
Show answer & explanation
Correct: A — 830.93(A)
830.93(A) governs grounding or interruption of the shield and metallic members where the cable enters the building, requiring it as close as practicable to the point of entrance. 830.93(B) is the parallel rule for cables terminated outside the building at the NIU, and 830.47(A) only addresses physical damage protection for underground cables, not grounding.
Where to locate the primary protector and NIU
NEC 830.90(B) Primary protectors must sit as close as practicable to the point of entrance, on the network side of (or built into) the network interface unit.
Q17 NEC 830.90(B)
A network-powered broadband communications cable enters a building. Per 830.90(B), where must an externally applied listed primary protector be placed relative to the network interface unit (NIU)?
- A Inside the NIU enclosure regardless of listing
- B On the network side of the NIU, on the external cable
- C On the derived circuit output side of the NIU only
- D Anywhere within the building as long as it is grounded
Show answer & explanation
Correct: B — On the network side of the NIU, on the external cable
Under 830.90(B)(1), a listed primary protector applied externally must be on each network-powered broadband cable external to and on the network side of the NIU. Placing it only on the derived (output) circuit side matches a different, separately listed option under 830.90(B)(3), not the general external-protector case. Just grounding it anywhere in the building, or assuming any NIU enclosure qualifies, ignores the listing and location requirements in 830.90(B).
Underground entrance cables: burial depth and physical protection
NEC 830.47(A) Direct-buried network-powered broadband cable must meet the cover depth in Table 830.47(A), and where it comes up out of the ground it needs physical protection up to 2.5 m (8 ft) above grade.
Q18 NEC 830.47(A) Code lookup
A direct-buried network-powered broadband communications cable is installed in a residential yard, then rises out of the ground to enter the building. Which section's table gives the minimum cover (burial depth) requirements for this cable?
- A 830.93(A)
- B 830.40(A)
- C 830.47(A)
- D 830.44(B)
Show answer & explanation
Correct: C — 830.47(A)
Table 830.47(A), Network-Powered Broadband Communications Systems Minimum Cover Requirements, lives at 830.47(A), which governs direct-buried cable cover depths. 830.44(B) instead addresses overhead cable clearance from ground, not burial depth, so it can't answer a direct-burial cover question.
Supporting and splicing network-powered broadband cable
NEC 830.133(B) Never strap network-powered broadband cable to a raceway for support, and always splice medium-powered cable inside a listed junction box or patch panel.
Q19 NEC 830.133(B)
An installer wants to run network-powered broadband communications cable alongside an existing EMT raceway and plans to tape the cable to the raceway's exterior every few feet for support. Is this permitted?
- A Yes, if the raceway is grounded and bonded
- B No, raceways are to be used for their intended purpose and cannot be used as a support means for the cable
- C Yes, as long as the tape is rated for the environment
- D Yes, but only for low-powered network-powered broadband circuits
Show answer & explanation
Correct: B — No, raceways are to be used for their intended purpose and cannot be used as a support means for the cable
Per 830.133(B), raceways must be used only for their intended purpose, and network-powered broadband communications cables cannot be strapped, taped, or otherwise attached to the exterior of a conduit or raceway as a means of support. Power level, tape rating, and grounding/bonding status don't change this restriction.
Listing requirements for premises-powered broadband equipment
NEC 840.170 Every piece of a premises-powered broadband system — network terminal, cable, power source, and accessories — must be listed for that specific use.
Q20 NEC 840.170
Under 840.170(A), what governs the grounding methodology used for the network terminal in a premises-powered broadband communications system?
- A The bonding requirements in Article 250 for grounding electrode systems
- B Whatever grounding means is covered by the product's listing
- C The primary protector grounding rules in 800.100
- D A dedicated grounding electrode conductor sized per the largest service conductor
Show answer & explanation
Correct: B — Whatever grounding means is covered by the product's listing
840.170(A) states there are no requirements on the network terminal and its grounding methodologies except for those covered by the listing of the product — Article 250 electrode rules, 800.100 primary protector grounding, and a dedicated grounding electrode conductor are not imposed here.
Grounding the coaxial cable shield (circuits confined to the building)
NEC 840.101(A) Even when a coax circuit never leaves the building, its shield still must be grounded — via CATV bonding methods, a direct EGC connection, or the network terminal's own ground.
Q21 NEC 840.101(A)
Under 840.101, the coax shield-grounding methods in 840.101(A) apply when a premises broadband circuit meets which condition?
- A The network terminal is served by a nonconductive optical fiber cable and the circuit stays entirely inside the building
- B The building contains more than one coaxial branch circuit
- C The network terminal uses a fully conductive optical fiber cable with no insulating joint
- D The coax cable exits the building to a service point
Show answer & explanation
Correct: A — The network terminal is served by a nonconductive optical fiber cable and the circuit stays entirely inside the building
840.101 applies when the network terminal is fed by nonconductive optical fiber (or a conductive fiber cable's metal member is broken by an insulating joint) and the circuits from that terminal are completely contained within the building. A circuit that leaves the building, or a fully conductive fiber cable with no interruption, doesn't trigger this section; the number of coax circuits is irrelevant.
When communications circuits and network terminals must be grounded
NEC 840.101(C) Communications circuits and network terminals are grounded only when something else requires it — the terminal's listing, or a separately grounded coaxial shield.
Q22 NEC 840.101(C)
Under 840.101(B), what is the grounding requirement for a communications circuit?
- A It must always be grounded at the point of entrance
- B It is not required to be grounded
- C It must be bonded to the coaxial shield in all cases
- D It must be grounded only in commercial occupancies
Show answer & explanation
Correct: B — It is not required to be grounded
840.101(B) states plainly that communications circuits shall not be required to be grounded. There is no exception carving out commercial occupancies, no mandatory point-of-entrance grounding, and no blanket bonding-to-shield requirement in this section.
Circuits leaving the building beyond the protection zone
NEC 840.94 Once a network-powered broadband circuit leaves the building and goes past the 46 m (150 ft) rolling sphere zone of lightning protection, it must meet 805.90 and 805.93 like any outside communications circuit.
Q23 NEC 840.94
A network-powered broadband circuit runs from a building to equipment mounted on a pole well outside the building's exterior zone of protection. Under 840.94, which sections now govern that circuit?
- A 840.90 and 840.93 only, since Article 840 already covers the entire installation
- B 805.90 and 805.93
- C The rules for outside plant cable under Article 800 in full, replacing Article 840 entirely
- D Only the listing requirements of 805.90, with no protector requirements
Show answer & explanation
Correct: B — 805.90 and 805.93
840.94 states that once a circuit leaves the building to power remote equipment or exits the 46 m (150 ft) rolling-sphere zone of protection, 805.90 and 805.93 apply. It's not that Article 840 keeps governing unchanged, and it's not just the listing rule alone — both the listing (805.90) and protector (805.93) requirements kick in together.
Powering communications equipment over communications cables
NEC 840.160 Listed 4-pair communications cables can carry both data and power, but once the power source exceeds 0.3 A per 24 AWG (or larger) conductor, the bundle must meet 725.144 heat-rise rules.
Q24 NEC 840.160
A listed 4-pair communications cable is carrying a PoE power circuit at 0.25 A in each 24 AWG conductor. Per 840.160, what is required?
- A Nothing additional — 725.144 compliance is not required at this current
- B The power source must be derated to 0.1 A per conductor
- C The cable must be reclassified as a Class 2 power-limited cable
- D The installation must still comply with 725.144 regardless of current
Show answer & explanation
Correct: A — Nothing additional — 725.144 compliance is not required at this current
840.160 waives the 725.144 compliance requirement for listed 4-pair communications cables when the power source's rated current does not exceed 0.3 A in any 24 AWG or larger conductor. At 0.25 A, that threshold isn't met, so no additional bundling compliance is required. The other choices misstate the rule as unconditional or invent unrelated requirements.
Electrical Theory: Ohm's Law, Power & Power Factor
NEC FND.1 Ohm's law (V = I·R) and the power formulas (P = V·I, P = I²·R, and P = √3·V·I·PF for three-phase) are the algebra behind most exam calculations — know which to reach for and don't drop the power factor or the √3.
Q25 NEC FND.1
A 20-ohm load is connected across a 120-volt supply. How much current flows through it?
- A 2400 A
- B 0.17 A
- C 6 A
- D 60 A
Show answer & explanation
Correct: C — 6 A
Ohm's law: I = V ÷ R = 120 ÷ 20 = 6 A. The distractors multiply or invert V and R, or slip a decimal.