A fire alarm control panel powers 16 AWG Class 1 remote-control conductors run to field devices. What is the maximum standard overcurrent device rating permitted to protect these conductors, and which section of Article 724 sets this limit?
- A 724.49
- B 724.43
- C 724.51
- D 724.45
Show answer & explanation
Correct: B — 724.43
724.43 sets the specific overcurrent maximums for small Class 1 conductors — 7 A for 18 AWG and 10 A for 16 AWG — and requires 14 AWG and larger to be protected per conductor ampacity without 310.15 adjustment/correction factors. 724.45 only addresses where the overcurrent device may be located, not its rating, and 724.49 covers conductor sizing/insulation, not overcurrent protection.