Ampacity is how much current a conductor can carry continuously, and almost every sizing problem on the journeyman exam starts here.
Ampacity is the maximum current, in amperes, that a conductor can carry continuously without exceeding its temperature rating. It is not a fixed property of the wire alone — it depends on the conductor size and material, the temperature rating of the insulation, and the conditions around the conductor, especially ambient heat and how many other current-carrying conductors share the raceway or cable. Table 310.16 is the workhorse for the exam: ampacities for insulated conductors run in a raceway, cable, or earth, with no more than three current-carrying conductors, based on a 30°C ambient.
Table 310.16 lists each conductor size in three insulation-temperature columns — 60°C, 75°C, and 90°C. The trap is that you rarely get to keep the 90°C value as your final ampacity. Section 110.14(C) ties the usable ampacity to the lowest temperature rating in the circuit, which is usually the equipment terminations. As a rule of thumb, terminations on equipment rated 100 amps or less default to 60°C unless the equipment and conductors are listed for 75°C, while equipment above 100 amps is generally rated 75°C.
So the 90°C column is mostly a starting point for math, not the answer. You apply correction and adjustment factors to the 90°C ampacity, but the final result can never exceed the ampacity shown in the column that matches your termination rating.
Two derating steps come up constantly:
When both apply, you multiply the 90°C ampacity by both factors.
Counting current-carrying conductors correctly is half the battle. The grounded (neutral) conductor of a balanced circuit, and the equipment grounding conductor, normally do not count. A neutral that carries only unbalanced current is not counted, but a neutral carrying significant harmonic current from nonlinear loads is treated as current-carrying. There is also a useful exemption: the adjustment factors do not apply to short raceway nipples — runs not exceeding 24 inches — so a packed but short connection between two enclosures escapes the bundling penalty.
Take an 8 AWG copper THHN conductor, which is 90°C rated. Its 90°C ampacity is 55 amps and its 75°C ampacity is 50 amps. Suppose six current-carrying conductors share the raceway (80 percent adjustment) in a 40°C space (about a 0.91 correction factor). Starting from the 90°C value: 55 × 0.80 × 0.91 ≈ 40 amps. Because 40 amps is below the 50-amp termination limit, the corrected 40 amps governs. This two-step pattern — derate from the 90°C column, then cap at the termination column — is one of the most heavily tested calculations on the journeyman exam.
In most commercial work the 75°C column ends up being the practical sizing column, because that is the common termination rating, so the corrected 90°C value is compared against it and the smaller number wins. Read the question carefully for the termination rating and the conditions of use; those two details decide which column governs and which factors you have to apply.
Loomi turns NEC content into 9,000+ spaced-repetition exam questions built for the journeyman test. Reserve your founders' seat before launch.
Join the waitlist