NEC · 310.15 / Table 310.16

Conductor Ampacity

Ampacity is how much current a conductor can carry continuously, and almost every sizing problem on the journeyman exam starts here.

NEC 2017 2020 2023 Last updated 2026-06-26

What conductor ampacity is

Ampacity is the maximum current, in amperes, that a conductor can carry continuously without exceeding its temperature rating. It is not a fixed property of the wire alone — it depends on the conductor size and material, the temperature rating of the insulation, and the conditions around the conductor, especially ambient heat and how many other current-carrying conductors share the raceway or cable. Table 310.16 is the workhorse for the exam: ampacities for insulated conductors run in a raceway, cable, or earth, with no more than three current-carrying conductors, based on a 30°C ambient.

Temperature ratings and terminations

Table 310.16 lists each conductor size in three insulation-temperature columns — 60°C, 75°C, and 90°C. The trap is that you rarely get to keep the 90°C value as your final ampacity. Section 110.14(C) ties the usable ampacity to the lowest temperature rating in the circuit, which is usually the equipment terminations. As a rule of thumb, terminations on equipment rated 100 amps or less default to 60°C unless the equipment and conductors are listed for 75°C, while equipment above 100 amps is generally rated 75°C.

So the 90°C column is mostly a starting point for math, not the answer. You apply correction and adjustment factors to the 90°C ampacity, but the final result can never exceed the ampacity shown in the column that matches your termination rating.

Correction and adjustment factors

Two derating steps come up constantly:

  • Ambient temperature correction. The table assumes 30°C. In a hotter space, multiply the conductor's ampacity by the temperature correction factor from 310.15(B); the hotter the ambient, the smaller the factor and the lower the ampacity.
  • Conductor bundling adjustment. When more than three current-carrying conductors share a raceway or cable, multiply by an adjustment factor: about 80 percent for 4 to 6 conductors, 70 percent for 7 to 9, and 50 percent for 10 to 20. Neutral conductors that carry only balanced return current generally are not counted.

When both apply, you multiply the 90°C ampacity by both factors.

Counting current-carrying conductors correctly is half the battle. The grounded (neutral) conductor of a balanced circuit, and the equipment grounding conductor, normally do not count. A neutral that carries only unbalanced current is not counted, but a neutral carrying significant harmonic current from nonlinear loads is treated as current-carrying. There is also a useful exemption: the adjustment factors do not apply to short raceway nipples — runs not exceeding 24 inches — so a packed but short connection between two enclosures escapes the bundling penalty.

A worked example

Take an 8 AWG copper THHN conductor, which is 90°C rated. Its 90°C ampacity is 55 amps and its 75°C ampacity is 50 amps. Suppose six current-carrying conductors share the raceway (80 percent adjustment) in a 40°C space (about a 0.91 correction factor). Starting from the 90°C value: 55 × 0.80 × 0.91 ≈ 40 amps. Because 40 amps is below the 50-amp termination limit, the corrected 40 amps governs. This two-step pattern — derate from the 90°C column, then cap at the termination column — is one of the most heavily tested calculations on the journeyman exam.

In most commercial work the 75°C column ends up being the practical sizing column, because that is the common termination rating, so the corrected 90°C value is compared against it and the smaller number wins. Read the question carefully for the termination rating and the conditions of use; those two details decide which column governs and which factors you have to apply.

Frequently asked questions

Why do you use the 90°C column if equipment is only rated 75°C?
The 90°C ampacity is the starting point for applying correction and adjustment factors, which lets you use the conductor's insulation rating during derating. The final corrected ampacity, however, can never exceed the value in the column that matches your termination temperature.
When do you have to derate conductor ampacity?
Whenever the ambient temperature differs from the table's 30°C basis, or when more than three current-carrying conductors share a raceway or cable. You apply the ambient correction factor and the bundling adjustment factor, multiplying both against the conductor's ampacity.
What is ampacity?
Ampacity is the maximum current a conductor can carry continuously without exceeding its temperature rating. It depends on the conductor's size and insulation, the ambient temperature, and how many current-carrying conductors are grouped together.
Loomi · NEC exam prep

Practice the NEC concepts in this article.

Loomi turns NEC content into 9,000+ spaced-repetition exam questions built for the journeyman test. Reserve your founders' seat before launch.

Join the waitlist