Chapter 9, Table 4 — conduit & tubing areas

The dimensions table every fill calculation starts from: total internal area and the usable slice at each percent-fill level.

Free · NEC 2023 · Updated
0.213
21 · in.2
from Chapter 9, Table 4
Exam trapEvery conduit type has its own sub-table — EMT and PVC Schedule 40 differ by trade size. Grabbing the wrong sub-table is the classic speed-lookup error.

Table 4 gives each raceway’s internal dimensions and pre-computed areas at the fill percentages Table 1 allows. Look up your conduit type and trade size to get the 40% area, then divide by conductor area from Table 5 — that is the entire conduit-fill method.

EMT

MetricDesignatorTrade SizeOver 2 Wires40%60%1 Wire53%2 Wires31%NominalInternalDiameterTotal Area100%
MetricDesignatorTrade Sizemm2in.2mm2in.2mm2in.2mm2in.2mmin.mm2in.2
161/2780.1221180.1821040.161610.09415.80.6221960.304
213/41370.2132060.3201820.2831060.16520.90.8243430.533
2712220.3463330.5192950.4581720.26826.61.0495560.864
351143870.5985810.8975130.7933000.46435.11.3809681.496
411125260.8147881.2216961.0794070.63140.91.61013142.036
5328661.34212992.01311471.7786711.04052.52.06721653.356
6321215132.34322703.51520053.10511731.81669.42.73137835.858
78322803.53834215.30730224.68817672.74285.23.35657018.846
9131229804.61844716.92739496.11923103.57997.43.834745111.545
103438085.90157128.85250467.81929514.573110.14.334952114.753
129552208.085783012.127691610.71340456.266128.95.0731305020.212
1556752811.6631129217.495997515.45458349.039154.86.0931882129.158

Table 9.4

MetricDesignatorTradeSizeOver 2 Wires40%60%1 Wire53%2 Wires31%NominalInternalDiameterTotal Area100%
MetricDesignatorTradeSizemm2in.2mm2in.2mm2in.2mm2in.2mmin.mm2in.2
161/2730.1141100.171970.151570.08815.30.6021840.285
213/41310.2031970.3051740.2691020.15720.40.8043280.508
2712150.3333220.4992840.4411660.25826.11.0295370.832
351143750.5815620.8724970.7702910.45034.51.369371.453
411125120.7947691.1916791.0523970.61640.41.5912811.986
5328491.31612741.97511251.7446581.020522.04721233.291
63212————————————
783————————————
91312————————————

FMC

MetricDesignatorTradeSizeOver 2 Wires40%60%1 Wire53%2 Wires31%Nominal Internal DiameterTotal Area100%
MetricDesignatorTradeSizemm2in.2mm2in.2mm2in.2mm2in.2mmin.mm2in.2
123/8300.046440.069390.061230.0369.70.384740.116
161/2810.1271220.1901080.168630.09816.10.6352040.317
213/41370.2132060.3201820.2831060.16520.90.8243430.533
2712110.3273160.4902790.4331630.25325.91.0205270.817
351143300.5114950.7664370.6772560.39632.41.2758241.277
411124800.7437201.1156360.9853720.57639.11.53812011.858
5328431.30712641.96111171.7326531.01351.82.04021073.269
6321212671.96319002.94516782.6029821.52263.52.50031674.909
78318242.82727364.24124173.74614142.19176.23.00045607.069
9131224833.84837245.77332905.09919242.98388.93.50062079.621
103432435.02748647.54042976.66025133.896101.64.000810712.566

IMC

MetricDesignatorTradeSizeOver 2 Wires40%60%1 Wire53%2 Wires31%NominalInternalDiameterTotal Area100%
MetricDesignatorTradeSizemm2in.2mm2in.2mm2in.2mm2in.2mmin.mm2in.2
123/8————————————
161/2890.1371330.2051170.181690.10616.80.6602220.342
213/41510.2352260.3522000.3111170.18221.90.8643770.586
2712480.3843720.5753290.5081920.29728.11.1056200.959
351144250.6596380.9885640.8733300.51036.81.44810641.647
411125730.8908591.3357591.1794440.69042.71.68314322.225
5329371.45214052.17812411.9247261.12554.62.15023413.630
6321213232.05419853.08117532.72210261.59264.92.55733085.135
78320463.16930694.75327114.19915862.45680.73.17651157.922
9131227294.23440936.35136165.61021153.28193.23.671682210.584
103434905.45252358.17946247.22427054.226105.44.166872513.631
129554558.528818312.792722911.3042286.610131.785.2101363921.32
1556787812.3041181718.4561043916.30261069.536158.366.2581969630.76

Table 9.4

MetricDesignatorTradeSizeOver 2 Wires40%60%1 Wire53%2 Wires31%NominalInternalDiameterTotal Area100%
MetricDesignatorTradeSizemm2in.2mm2in.2mm2in.2mm2in.2mmin.mm2in.2
123/8500.077750.115660.102390.06012.60.4951250.192
161/2800.1251210.1871070.165620.09716.00.6302010.312
213/41390.2142080.3211840.2831070.16621.00.8253460.535
2712210.3423310.5132920.4531710.26526.51.0435520.854
351143870.6015810.9015130.7963000.46635.11.3839681.502
411125200.8077811.2116901.0704030.62640.71.60313012.018
5328631.33712942.00611431.7726691.03652.42.06321573.343
Notes that change the answer — 9.4

*Corresponds to 356.2(1).

Table 9.4

MetricDesignatorTradeSizeOver 2 Wires40%60%1 Wire53%2 Wires31%NominalInternalDiameterTotal Area100%
MetricDesignatorTradeSizemm2in.2mm2in.2mm2in.2mm2in.2mmin.mm2in.2
123/8490.077740.115650.102380.05912.50.4941230.192
161/2810.1251220.1881080.166630.09716.10.6322040.314
213/41400.2162100.3251850.2871080.16821.10.8303500.541
2712260.3493380.5242990.4621750.27026.81.0545640.873
351143940.6115910.9175220.8103050.47435.41.3959841.528
411125100.7927651.1886761.0503950.61440.31.58812761.981
5328361.29812551.94811081.7206481.00651.62.03320913.246
Notes that change the answer — 9.4

*Corresponds to 356.2(2).

Values derived from the 2023 National Electrical Code for exam study. Verify installations against the adopted code and local amendments.

Race your codebook — 3 lookups on this table

Q1

A fixed industrial process heating unit uses a hermetic refrigerant motor-compressor and also incorporates equipment covered by another NEC article. Which section directs the installer to the table listing those other applicable articles?

  1. A 425.4
  2. B 425.1
  3. C 425.3
  4. D 425.6
Show answer & explanation

Correct: C — 425.3

425.3 is the section that hosts Table 425.3, directing the installer to other NEC articles that apply to fixed industrial process heating equipment with a hermetic refrigerant motor-compressor. 425.1 only states the article's scope, 425.6 covers listed equipment requirements, and 425.4 covers branch-circuit sizing — none of these point to the cross-reference table.

Q2

An installer has two non-hermetic motors of different horsepower feeding a common branch circuit and needs to determine which one governs as the largest motor for 430.53(B) grouping rules. Neither nameplate lists rated-load current directly usable for comparison, so the tech must pull equivalent full-load current values from Table 430.248 based on horsepower. Which section directs this method of finding the highest rated motor?

  1. A 440.6(B)
  2. B 440.12(B)(2)
  3. C 440.7
  4. D 440.4(B)
Show answer & explanation

Correct: C — 440.7

440.7 specifically instructs that, for motors other than hermetic compressors or 440.6(B) multimotor equipment, full-load current for comparison purposes is taken from Table 430.248, 430.249, or 430.250 based on horsepower rating. 440.6(B) covers ampacity marking for multimotor equipment generally, not the largest-motor determination method, and 440.12(B)(2) deals with combination-load short-circuit protective device sizing instead.

Q3

An electrician is installing EMT to carry stage lighting circuit conductors and wants to know the conductor fill table that applies, along with confirmation that the usual 30-conductor cap on other raceway types doesn't apply here. Which section addresses this?

  1. A 520.21
  2. B 520.6
  3. C 520.10
  4. D 520.5(A)
Show answer & explanation

Correct: B — 520.6

520.6 directs use of Table 1 of Chapter 9 for percentage fill in metal conduit or EMT and expressly states the 30-conductor limitation of 366.22 and 376.22 does not apply. 520.5(A) only covers general wiring methods permitted for stage equipment, not conductor fill calculations.