A house has both a ground rod and a concrete-encased electrode (Ufer ground) installed. The electrician needs to know the requirements for the conductor that ties these two electrodes together into a single grounding electrode system. Which section covers this jumper?
- A 250.53(D)(1)
- B 250.53(C)
- C 250.53(E)
- D 250.54
Show answer & explanation
Correct: B — 250.53(C)
250.53(C) covers the bonding jumper that connects the grounding electrodes together to form the grounding electrode system, including sizing per 250.66 and connection per 250.70. 250.53(E) only addresses sizing of the jumper to a supplemental rod/pipe/plate electrode, and 250.53(D)(1) covers continuity of a metal water pipe electrode, not the interconnecting bonding jumper itself.