Size the EGC from the OCPD and the GEC from the service conductor.
Enter values to calculate
Table 250.122 (EGC by OCPD) / Table 250.66 (GEC by service conductor). Simplified — EGC may need upsizing for voltage-drop (250.122(B)); GEC has rod/pipe/concrete caps (250.66(A–C)).
The NEC treats the equipment grounding conductor (EGC) and the grounding electrode conductor (GEC) as two distinct conductors with different sizing rules. They are not interchangeable terms — each connects to a different part of the grounding system and is sized from a different input.
The EGC (NEC 250.122) provides the fault-current return path from metal equipment enclosures and raceways back to the source. Its minimum size comes from Table 250.122 — look up the rating or setting of the OCPD protecting the circuit ahead of the equipment. A 100 A breaker requires at minimum an 8 AWG copper or 6 AWG aluminum EGC. Note that 250.122(B) may require upsizing the EGC proportionally when the ungrounded conductors are increased for voltage-drop reasons.
The GEC (NEC 250.66) bonds the grounding electrode system (ground rod, metal water pipe, concrete-encased electrode, etc.) to the grounded conductor at the service. Its size is determined by the largest ungrounded service-entrance conductor — not the OCPD. Table 250.66 caps at 3/0 AWG copper / 250 kcmil aluminum regardless of service size. Electrodes such as rods and pipes have additional caps under 250.66(A–C): a single ground rod never requires more than 6 AWG copper to the rod clamp, even on a large service.
| Conductor | NEC Section | Sized by | Table |
|---|---|---|---|
| EGC | 250.122 | OCPD rating ahead of circuit | Table 250.122 |
| GEC | 250.66 | Largest ungrounded service conductor | Table 250.66 |
Loomi turns these calcs into 9,000+ timed, NEC-referenced exam questions, with spaced repetition that hammers your weak spots. Reserve your founders' seat before launch.
Join the waitlist