A single hermetic refrigerant motor-compressor has a rated-load current of 40A and no branch-circuit selection current is marked on the nameplate. A standard dual-element fuse sized at 175% of the rated-load current is not a standard fuse size, and the next higher standard size is not sufficient to carry the compressor's starting current. Which section allows increasing the fuse rating above 175% (up to 225%) of the rated-load current to handle the starting current?
- A 440.22(B)(1)
- B 440.12(A)(1)
- C 440.22(A)
- D 440.32
Show answer & explanation
Correct: C — 440.22(A)
440.22(A) sets the base 175% rating for individual motor-compressor branch-circuit protection and its exception permits going up to 225% when 175% won't carry starting current. 440.22(B)(1) covers equipment where the motor-compressor is the largest load in a multimotor unit, not an individual motor-compressor circuit.