NM cable — the Romex found in virtually every house — looks simple until the exam asks why you use the 60°C ampacity column for conductors stamped 90°C.
Type NM cable — sold under the trade name Romex and governed by NEC Article 334 — is a factory-assembled wiring method consisting of two or more insulated conductors and a bare equipment grounding conductor, all enclosed in a flame-retardant, moisture-resistant nonmetallic sheath. It is the dominant wiring method in residential new construction because it is lightweight, easy to route, and inexpensive.
Article 334 also covers two related types: NMC, which adds a corrosion-resistant outer jacket for use in damp or corrosive locations within the permitted occupancies, and NMS, which includes communications conductors. The journeyman exam focuses almost entirely on plain Type NM.
Section 334.10 lists the structures where NM cable is permitted: one- and two-family dwellings, multi-family dwellings, and other structures where the NEC specifically allows it. Within those structures it may be used for branch circuits and feeders in dry locations, exposed or concealed.
Section 334.12 is the prohibited-use list, and it is heavily tested. NM cable is not permitted in the following situations:
The practical takeaway for the exam: NM cable belongs in wood-frame residential structures in dry, protected locations. Any question that introduces a commercial building, a wet space, a concrete pour, or a corrosive environment is pushing you toward a different wiring method — most often MC cable (Article 330) or conduit.
This is the single most-tested NM cable rule on the journeyman exam because it seems to contradict what you see on the wire. The conductors inside a typical NM cable carry a 90°C insulation rating — THHN or THWN-2 inside the jacket. A candidate might assume they can use the 90°C column of Table 310.16 and get a higher allowable current.
Section 334.80 says otherwise. The ampacity of NM cable shall be determined from the 60°C column of Table 310.16. The reason is thermal: the nonmetallic sheath traps heat, so the conductors run hotter than they would in open air or in a raceway. The code addresses this by requiring the lower 60°C column.
Key exam rule: For NM cable, always start and finish with the 60°C column. If you need to derate for bundling or elevated ambient temperature, you may apply those factors to the 90°C column ampacity, but the resulting corrected value still cannot exceed the 60°C column ampacity for that conductor size. For a 12 AWG copper conductor, the 60°C ampacity is 20 A — regardless of what the 90°C column shows.
Article 334.30 governs how NM cable must be fastened. The two numbers to memorize are 4½ feet and 12 inches:
Contrast this with MC cable, which is supported every 6 feet and within 12 inches of boxes — the box distance is the same, but the mid-run interval is longer for MC. That difference is a frequent distractor question.
NM cable must also be protected where it passes through framing members and where it emerges from concealed locations and becomes exposed. Bored holes in studs and joists require the cable to be at least 1¼ inches from the edge of the framing, or a nail plate must protect the cable.
| Feature | NM Cable (Art. 334) | MC Cable (Art. 330) |
|---|---|---|
| Primary use | Residential, dry locations | Commercial; broad permitted uses |
| Wet locations | Not permitted (NM); NMC permitted in damp | Listed type permitted |
| Ampacity column | 60°C (334.80) | Per 310.16 and termination rating |
| Support interval | Every 4½ ft | Every 6 ft |
| Within-box distance | 12 in. | 12 in. |
| Equipment ground | Bare wire EGC inside sheath | Dedicated EGC; armor not the ground path |
Journeyman exam questions on NM cable cluster around three themes: the 60°C ampacity cap, the prohibited-use list (wet, concrete, certain occupancies), and the support interval compared against MC cable. Know those three areas cold and most NM questions become straightforward.
Loomi turns NEC content into 9,000+ spaced-repetition exam questions built for the journeyman test. Reserve your founders' seat before launch.
Join the waitlist