A branch circuit is the last leg of the electrical system — from the final overcurrent device to the load — and Article 210 governs everything about it, from allowable ratings to the specific circuits every dwelling must have.
The NEC defines a branch circuit as the conductors between the final overcurrent device protecting the circuit and the outlets it supplies. That boundary matters: the instant you cross from the downstream side of the last breaker or fuse to the first outlet or load, you are in branch-circuit territory and Article 210 applies. Everything between the service equipment and that final overcurrent device is a feeder, governed by Article 215.
Journeyman exam questions on branch circuits almost always start by testing whether you can draw that line correctly. A circuit with two panelboards in series has a feeder feeding the second panel and branch circuits leaving it — the location of the last overcurrent device is what decides which rules apply.
Article 210 recognizes four branch-circuit types, and knowing them by name helps on exam questions that ask which rules apply:
Section 210.3 lists the allowable ratings for branch circuits that serve two or more outlets: 15, 20, 30, 40, and 50 amperes. A circuit at any of those ratings can supply multiple outlets. Individual branch circuits — those that serve only a single load — are not limited to that list and can be any size needed for the equipment.
| Rating | Minimum conductor (copper, 60/75 °C terminal) | Typical use |
|---|---|---|
| 15 A | 14 AWG | General lighting, receptacles |
| 20 A | 12 AWG | Kitchen/bath receptacles, small appliances |
| 30 A | 10 AWG | Clothes dryers, air conditioners |
| 40 A | 8 AWG | Ranges, large HVAC |
| 50 A | 6 AWG | Ranges, EV charging (individual circuits) |
These minimum conductor sizes come from 310.12 for dwelling units and the ampacity tables for other occupancies. Always verify against the termination temperature rating of the equipment — most residential panels list 60°C or 75°C terminals, which controls which column of the ampacity table you use.
The NEC does not leave it to the designer to decide whether certain circuits exist. Section 210.11 mandates specific branch circuits in every dwelling unit:
These are minimums. An exam question may ask what the code requires, not what a good design would add. Knowing that the small-appliance circuits must be 20-ampere, must supply only those areas, and that at least two are needed is the core fact to lock in.
Branch-circuit conductors and overcurrent devices must also account for continuous loads — any load expected to run for three or more hours must have the conductor and breaker sized at 125 percent of that load. That rule from 210.19 and 210.20 applies at the branch-circuit level the same way it does to feeders.
Loomi turns NEC content into 9,000+ spaced-repetition exam questions built for the journeyman test. Reserve your founders' seat before launch.
Join the waitlist