NEC · 210.19 / 210.20 / 215.2

Continuous Load & the 125% Rule

Any load that runs for three hours or more is continuous under the NEC, and that single classification forces the conductor and breaker to be sized bigger than the load alone — by exactly 125 percent.

NEC 2017 2020 2023 Last updated 2026-06-27

The definition: three hours or more

Article 100 defines a continuous load as a load where the maximum current is expected to continue for three hours or more. That is the entire definition — three hours. There is no list of load types, no occupancy-based exception. A lighting circuit in a warehouse that runs an overnight shift is continuous. A kitchen exhaust hood that runs for four hours during a dinner service is continuous. A receptacle circuit serving a data center that is always on is continuous.

On the exam, the three-hour threshold is either given in the question or implied by the load type. Commercial and industrial lighting, continuous process equipment, and always-on circuits are the scenarios where you should immediately flag "continuous" without being told explicitly. Residential circuits are less often tested as continuous, but a lighting circuit in a common area of an apartment building can qualify.

The 125% sizing rule and where it appears

The NEC addresses continuous loads at three key locations, and the journeyman exam draws from all three:

  • 210.19(A)(1) — Branch-circuit conductors must have an ampacity of not less than the noncontinuous load plus 125 percent of the continuous load.
  • 210.20(A) — Branch-circuit overcurrent devices must be rated not less than the noncontinuous load plus 125 percent of the continuous load.
  • 215.2(A)(1) — Feeder conductors carry the identical requirement: noncontinuous load at 100 percent plus continuous load at 125 percent.

In each case the formula is the same: add the full noncontinuous load to 125 percent of the continuous load. The result is the minimum ampacity or rating required before you go to a conductor table or breaker selection.

Worked example

A branch circuit serves a 32-ampere noncontinuous load and a 40-ampere continuous load. What is the minimum conductor ampacity and overcurrent device rating?

  • Continuous load at 125%: 40 A × 1.25 = 50 A
  • Noncontinuous load at 100%: 32 A
  • Minimum required: 50 + 32 = 82 amperes

You would select a conductor with at least 82 amperes of ampacity (at the correct termination temperature column) and a breaker rated at least 82 amperes — in practice, the next standard size up, which is 90 amperes under 240.6(A). If the circuit had only the 40-ampere continuous load with no noncontinuous component, the minimum would be 40 × 1.25 = 50 amperes, meaning a 50-ampere breaker and a conductor rated at least 50 amperes. That straightforward case — a purely continuous load — is the most common exam scenario.

The 80% rule: the same requirement, stated differently

The 125% sizing rule is sometimes expressed as "do not load a breaker above 80 percent of its rating for continuous use." Both statements describe the same mathematical relationship:

  • A 50-ampere breaker loaded to 80% carries 40 amperes of continuous load.
  • A 40-ampere continuous load requires a breaker rated at least 40 × 1.25 = 50 amperes.

Dividing by 1.25 is the same as multiplying by 0.80. On the exam, knowing both formulations matters because questions are written both ways: "size the breaker for a 40-amp continuous load" and "what is the maximum continuous load on a 50-amp breaker?" have the same underlying answer — 40 amperes and 50 amperes respectively — but require opposite operations.

One important caveat: some overcurrent devices are listed for continuous operation at 100 percent of their rating. When a question or equipment specification calls out a 100-percent-rated breaker, the 125% derating does not apply to that device. Those devices are less common and the exam will tell you when one is involved; the default assumption is always 125 percent unless stated otherwise.

Interaction with ampacity adjustment factors

The 125% figure is applied to the load to set a minimum ampacity requirement. Ampacity adjustment factors — temperature correction and conduit fill — are applied to the conductor's rated ampacity to determine what the conductor can actually carry in that installation. The two calculations work in opposite directions and must both be satisfied.

A conductor running through a hot attic, or bundled with many other conductors, has a derated ampacity that may be lower than its table value. The derated ampacity still has to meet or exceed the minimum calculated from the continuous load rule. If the 125% calculation gives you 82 amperes but the conductor's derated ampacity is only 78 amperes, the conductor is undersized regardless of the breaker rating. Load calculations that involve continuous loads must account for both effects.

Practice questions on this rule

Real journeyman-exam practice questions from Loomi's bank — answer first, then reveal the explanation.

Q1 NEC 210.19(B)

Some individual branch circuits serving a single, known load are permitted to use conductors sized to the actual connected load rather than the circuit's full rating. Does that same allowance apply to a circuit feeding multiple receptacles for cord-and-plug loads?

  1. A No — but only for circuits rated above 30 amperes
  2. B No — 210.19(B) requires conductor ampacity not less than the branch-circuit rating whenever more than one receptacle serves portable loads
  3. C Yes — as long as the combined connected load stays under the circuit rating
  4. D Yes — provided all the receptacles are on the same wall or room
Show answer & explanation

Correct: B — No — 210.19(B) requires conductor ampacity not less than the branch-circuit rating whenever more than one receptacle serves portable loads

Once a circuit supplies more than one receptacle for cord-and-plug portable loads, 210.19(B) removes any allowance to size conductors to a specific known load. The conductors must carry the full branch-circuit rating because any receptacle could be loaded up to that rating at any time — there's no exception based on total connected load, receptacle location, or circuit rating threshold.

Q2 NEC 210.19(D)

Which of these taps is NOT covered by the reduced ampacity minimums in 210.19(D)?

  1. A A nonheating lead of a snow-melting mat
  2. B A tap not longer than 450 mm (18 in.) to an individual outlet other than a receptacle outlet
  3. C A tap conductor supplying an infrared lamp industrial heating appliance
  4. D A tap conductor supplying a receptacle outlet
Show answer & explanation

Correct: D — A tap conductor supplying a receptacle outlet

210.19(D) lists individual outlets other than receptacle outlets, infrared heating appliances, and nonheating leads of deicing/snow-melting equipment among the covered tap uses — receptacle outlets are specifically excluded from this exception.

Q3 NEC 210.19(C)

Tap conductors run from a 50-ampere branch circuit to a wall-mounted oven. What is the minimum ampacity these tap conductors must have?

  1. A Whatever the appliance nameplate states, with no code-imposed minimum
  2. B 20 amperes, and sufficient for the load served
  3. C 50 amperes, matching the branch-circuit conductors
  4. D 15 amperes, since ovens are treated like lighting loads
Show answer & explanation

Correct: B — 20 amperes, and sufficient for the load served

210.19(C) permits tap conductors from a branch circuit of 50 amperes or less to be smaller than the branch-circuit conductors, but they must still have an ampacity of at least 20 amperes and be sufficient for the load. Matching the full 50-ampere branch conductors defeats the purpose of allowing a tap, and there is no exception tying the minimum to the appliance nameplate alone.

Q4 NEC 210.19(C)

A 3-wire branch circuit supplies a household electric range of 8¾ kW or more, and demand has been calculated using Column C of Table 220.55. Which neutral conductor is permitted?

  1. A 8 AWG, since its ampacity is at least 70% of the branch-circuit rating
  2. B 10 AWG, regardless of its ampacity relative to the branch-circuit rating
  3. C 10 AWG, since its ampacity is at least 70% of the branch-circuit rating
  4. D Any size smaller than the ungrounded conductors, as long as it is not fine-stranded
Show answer & explanation

Correct: C — 10 AWG, since its ampacity is at least 70% of the branch-circuit rating

210.19(C) requires the reduced neutral to satisfy two conditions together: ampacity of at least 70% of the branch-circuit rating, and a minimum size of 10 AWG. An 8 AWG conductor violates the 10 AWG floor even if its ampacity clears 70%, and a 10 AWG conductor still has to clear the 70% ampacity test — the size alone isn't enough.

All Branch Circuits practice questions (Article 210)

Frequently asked questions

What makes a load "continuous" under the NEC?
A load is continuous when it is expected to remain energized for three or more hours, as defined in NEC Article 100. The three-hour threshold is the only criterion — the type of load, the occupancy, or the time of day are not factors. Lighting circuits in commercial buildings are the classic continuous load example.
Does the 125% rule apply to both the conductor and the breaker?
Yes. Both the branch-circuit conductor ampacity (210.19) and the overcurrent device rating (210.20) must be at least 125 percent of the continuous load, plus the full noncontinuous load. In practice this usually means selecting the next standard breaker size up from what the load alone would require.
What does "80% loading" mean, and is it the same rule?
It is the same rule stated from the opposite direction. If a breaker must be rated at 125% of the continuous load, then the continuous load cannot exceed 80% of the breaker rating — 1 ÷ 1.25 = 0.80. Both expressions describe the same requirement; which way the exam phrases it changes how you solve the math, not which code section applies.
Loomi · NEC exam prep

Practice the NEC concepts in this article.

Loomi turns NEC content into 12,934 spaced-repetition exam questions built for the journeyman test. Try everything free for 3 days.

Get launch access