NEC · Article 215

Feeders

A feeder is everything between your service and the final overcurrent device, and the exam expects you to size it, protect it, and tell it apart from a branch circuit.

NEC 2017 2020 2023 Last updated 2026-06-26

Feeder vs branch circuit

A feeder is every conductor between the service equipment — or another power source such as a generator or transformer — and the final branch-circuit overcurrent device. The branch circuit is what comes after that last overcurrent device: the conductors running to the outlets and loads. Drawing that line correctly is the first thing the exam checks, because feeder rules (Article 215) and branch-circuit rules (Article 210) are scored separately.

In a typical house, the conductors from the main panel out to a detached garage subpanel are a feeder; the circuits leaving that subpanel are branch circuits. Get the boundary right and the rest of the problem — sizing, protection, grounding — falls into place.

On the journeyman exam, feeder questions tend to test four things:

  • telling a feeder apart from a branch circuit or service conductor;
  • applying the 125 percent factor to the continuous portion of the load;
  • matching the overcurrent device and disconnect rules; and
  • recognizing the voltage-drop recommendation on long runs.

Sizing feeder conductors

Feeder conductors must have an ampacity at least equal to the load they serve, calculated under Article 220. The governing rule in 215.2 is that the minimum feeder ampacity is the noncontinuous load plus 125 percent of the continuous load, before any adjustment or correction factors. Once you have that minimum ampere figure, you pick a conductor from the ampacity tables at the appropriate termination temperature column.

Worked example: a feeder serves a 160-amp noncontinuous load and a 40-amp continuous load. The minimum conductor ampacity is 160 + (40 × 1.25) = 210 amps. You would then choose a conductor rated at least 210 amps in the 75°C column, assuming 75°C terminations.

Overcurrent protection and the disconnect count

The feeder overcurrent device protects the feeder at its ampacity, with the standard next-size-up allowance of 240.4(B) available where the feeder does not supply the loads that bar it. Just as a service is limited to six disconnecting means (230.71), a feeder that supplies a separate building or structure is limited to six disconnects at that building under 225.33 — the same "six operations of the hand" idea applied past the service. Knowing that the six-disconnect concept reaches feeders to outbuildings is a common exam distinction.

Voltage drop, grounding, and common mistakes

The NEC does not enforce voltage drop as a hard rule, but an informational note to 215.2 recommends sizing feeders so voltage drop does not exceed 3 percent, with the combined drop of the feeder plus its branch circuits held to 5 percent. On long runs you upsize the feeder conductors to stay within that recommendation — and remember that upsizing the phase conductors forces the equipment grounding conductor to grow proportionally under 250.122(B).

A feeder also needs an equipment grounding conductor, and it is sized from Table 250.122 using the feeder overcurrent device rating — the same logic as a branch circuit, just at a larger scale. Feeder tap conductors are a separate advanced topic: 240.21(B) lets a tap run a limited distance without overcurrent protection at the tap point, under the well-known 10-foot and 25-foot tap rules. Those are worth recognizing even if the journeyman exam keeps the heavy tap math light.

The mistakes that cost points on feeder questions are predictable:

  • applying the 125 percent factor to the whole load instead of only the continuous portion;
  • confusing feeder rules (Article 215) with service rules (Article 230); and
  • forgetting that a feeder to a separate building carries its own disconnect and grounding requirements.

Practice questions on this rule

Real journeyman-exam practice questions from Loomi's bank — answer first, then reveal the explanation.

Q1 NEC 215.2(B)

A 55 A service feeds a subpanel through a feeder that carries the entire service load. Under 215.2(C), what ampacity must that feeder have?

  1. A At least equal to the equipment grounding conductor size only
  2. B No special requirement, since the service is under 100 A
  3. C At least equal to the ampacity of the service conductors
  4. D At least 80% of the service conductor ampacity
Show answer & explanation

Correct: C — At least equal to the ampacity of the service conductors

215.2(C) requires the feeder's ampacity to be at least equal to the service conductors' ampacity whenever that feeder carries the total service load and the service is 55 A or less. The 80% figure and the 'under 100 A is exempt' idea aren't part of this rule, and the equipment grounding conductor size is the separate 215.2(B) floor, not the ampacity-matching rule.

Q2 NEC 215.2

215.2(A) requires feeder conductors to have an ampacity not less than the larger of two calculations. Alongside the continuous/noncontinuous load rule in 215.2(A)(1), what is the second calculation?

  1. A The ampacity remaining after applying adjustment or correction factors under 310.14
  2. B The ampacity needed to keep voltage drop under 3 percent
  3. C The smallest conductor size permitted by the equipment's termination temperature rating
  4. D The next standard ampere rating above the calculated load
Show answer & explanation

Correct: A — The ampacity remaining after applying adjustment or correction factors under 310.14

215.2(A)(2) sets the second required calculation as the ampacity remaining after any 310.14 adjustment or correction factors, and the feeder must meet whichever of the two calculations is larger. The 3 percent voltage-drop figure is only an informational note in 215.2(A)(2), not a mandatory sizing calculation.

Q3 NEC 215.3

Which load type receives the 125% multiplier when sizing a feeder's overcurrent device under 215.3?

  1. A Both the continuous and noncontinuous loads
  2. B Neither; the 125% multiplier applies only to conductor ampacity, not the overcurrent device
  3. C The continuous load only
  4. D The noncontinuous load only
Show answer & explanation

Correct: C — The continuous load only

215.3 applies the 125% factor to the continuous load; the noncontinuous load is added at 100%. The last distractor confuses this with the separate (though similarly structured) conductor-sizing rule — 215.3 is specifically about the overcurrent device rating, and it does apply a 125% factor there.

Q4 NEC 210.19(A)

A single-phase 120-volt circuit supplies a 24-ampere load 150 feet away, wired with 10 AWG copper. Using the K-method (K = 12.9 for copper), what is the approximate voltage drop?

  1. A 4.47 V
  2. B 7.75 V
  3. C 14.71 V
  4. D 8.95 V
Show answer & explanation

Correct: D — 8.95 V

Voltage drop = 2·K·I·L ÷ CM. With K = 12.9, I = 24 A, L = 150 ft, and CM = 10380 circular mils (Table 8 area of 10 AWG): 2 × 12.9 × 24 × 150 ÷ 10380 = 8.95 V. The distractors drop the factor of 2 (one-way run), use √3 (three-phase), or use aluminum's K = 21.2.

More practice questions: Wiring and Protection (Articles 200–245)

Frequently asked questions

What is the difference between a feeder and a branch circuit?
A feeder is the conductors between the service equipment or other power source and the final branch-circuit overcurrent device. The branch circuit is the conductors past that final overcurrent device, running to the outlets and loads.
How do you size a feeder conductor?
Size it for the calculated load under Article 220, with a minimum ampacity of the noncontinuous load plus 125 percent of the continuous load. Then select a conductor that meets that ampacity at the termination temperature rating, and check voltage drop on long runs.
Does the six-disconnect rule apply to feeders?
Yes, in a parallel form. A service is limited to six disconnects under 230.71, and a feeder supplying a separate building or structure is limited to six disconnecting means at that building under 225.33.
Loomi · NEC exam prep

Practice the NEC concepts in this article.

Loomi turns NEC content into 12,934 spaced-repetition exam questions built for the journeyman test. Try everything free for 3 days.

Get launch access