NEC · 314.16

Box Fill Calculations

Every conductor, device, and clamp inside a box claims space. Section 314.16 tells you exactly how to add it up — and the counting rules are where journeyman exams find their traps.

NEC 2017 2020 2023 Last updated 2026-06-27

Why box fill matters

When too many conductors are stuffed into a box, connections loosen, insulation abrades, and heat builds up. NEC 314.16 prevents this by assigning a volume allowance to each conductor size and then requiring that the total volume of all items in the box — conductors, devices, clamps, and fittings — does not exceed the box's listed cubic-inch capacity. On the journeyman exam, box fill problems appear frequently because the counting rules look simple but have several specific exceptions that are easy to miss under time pressure.

The volume allowance for each conductor size comes from Table 314.16(B). A few common values across 2017, 2020, and 2023 editions:

Conductor size Volume allowance per conductor
14 AWG 2.00 cubic inches
12 AWG 2.25 cubic inches
10 AWG 2.50 cubic inches
8 AWG 3.00 cubic inches
6 AWG 5.00 cubic inches

In a box with mixed conductor sizes, each conductor uses its own size's allowance. If all conductors are the same size, every allowance is the same value — the easier exam scenario.

The five counting categories

Section 314.16(B) breaks box fill into five categories. Getting the rules for each one right is the whole game.

1. Conductors (314.16(B)(1)). Each conductor that enters or passes through the box from outside counts as one allowance at its own size. A conductor that passes through without a splice still counts as one — it still takes up space. The key exception: a conductor that does not leave the box through a knockout or cable fitting (that is, it originates entirely inside the box, like a pigtail) is not counted. This is the most frequently tested exception. Pigtails added to extend a termination do not add to the tally.

2. Internal clamps (314.16(B)(2)). When a box has one or more internal cable clamps, add a single volume allowance equal to the largest conductor entering the box. It does not matter how many clamps are present — all internal cable clamps together equal one allowance.

3. Support fittings (314.16(B)(3)). Fixture studs, hickeys, and similar support fittings each add one volume allowance based on the largest conductor in the box.

4. Device or equipment fill (314.16(B)(4)). Each yoke or strap that contains a device — a switch, receptacle, or similar — counts as two volume allowances. The two allowances are each sized to the largest conductor connected to that device. A two-gang box with two devices on two yokes adds four allowances; a duplex receptacle on a single yoke still adds only two, because it is one yoke.

5. Equipment grounding conductors (314.16(B)(5)). All equipment grounding conductors that enter or are contained in the box together count as a single allowance, sized to the largest EGC present. Five bare ground wires entering the box: still one allowance. This rule catches many exam takers who count each ground separately.

A worked example

Picture a single-gang device box fed by two 12/2 NM cables. Each cable carries a black hot, a white neutral, and a bare equipment grounding conductor. A duplex receptacle is installed on a single yoke. The box has internal cable clamps. One bare pigtail EGC is added inside to connect the device ground screw to the cable grounds — it stays entirely inside the box.

Count each category using the 2.25 cubic-inch allowance for 12 AWG:

  • Conductors: 4 current-carrying conductors (2 hots + 2 neutrals), each entering from outside — 4 × 2.25 = 9.00 cu in
  • Equipment grounding conductors: 2 bare EGCs enter from outside; the pigtail stays inside and is not counted. All EGCs together = 1 × 2.25 = 2.25 cu in
  • Internal clamps: 1 allowance at the largest conductor size = 1 × 2.25 = 2.25 cu in
  • Device (yoke): 1 yoke = 2 allowances at 12 AWG = 2 × 2.25 = 4.50 cu in

Total required box volume: 9.00 + 2.25 + 2.25 + 4.50 = 18.00 cubic inches. The box selected must be listed with a volume of at least 18 cubic inches.

Key rule: the pigtail EGC added inside the box does not raise the count. If you had counted it as a third EGC or a separate conductor, you would overshoot the total and potentially over-specify the box size — or miss the right answer on the exam.

How to approach box fill questions on the exam

Box fill questions are methodical: read the scenario, sort items into the five categories, and add. The traps are almost always the same three:

  • Counting pigtails as conductors when they originate and stay inside the box — they do not count.
  • Counting each EGC individually instead of grouping all grounds into a single allowance.
  • Forgetting that a yoke with a device counts as two allowances, not one.

With a consistent five-category checklist and the Table 314.16(B) values tabbed in your code book, a box fill problem on the journeyman exam should take under two minutes. The box fill calculator lets you practice the category logic before the exam so the sequence becomes automatic.

Practice questions on this rule

Real journeyman-exam practice questions from Loomi's bank — answer first, then reveal the explanation.

Q1 NEC 314.16

A device box contains 6 insulated conductors (all 14 AWG) and 2 equipment grounding conductor(s) at 14 AWG, secured with internal cable clamps and feeding a two-gang device plate (two yokes). What minimum box volume does NEC 314.16(B) require?

  1. A 24.00 in³
  2. B 20.00 in³
  3. C 22.00 in³
  4. D 26.00 in³
Show answer & explanation

Correct: A — 24.00 in³

314.16(B)(1): the 6 conductors add 12.00 in³. 314.16(B)(2): internal clamps add one allowance = 2.00 in³. 314.16(B)(4): each of the two device yokes gets a double allowance = 8.00 in³. 314.16(B)(5): the grounding conductors together add 2.00 in³. Total 24.00 in³ is the correct minimum; the other options drop the clamp allowance, count a yoke only once instead of double, or count each ground separately instead of as a single allowance.

Q2 NEC 314.16

A device box contains 4 insulated conductors (2 at 10 AWG and 2 at 12 AWG) and 2 equipment grounding conductor(s) at 10 AWG, secured with internal cable clamps and feeding a two-gang device plate (two yokes). What minimum box volume does NEC 314.16(B) require?

  1. A 19.50 in³
  2. B 24.50 in³
  3. C 22.00 in³
  4. D 27.00 in³
Show answer & explanation

Correct: B — 24.50 in³

314.16(B)(1): the 4 conductors add 9.50 in³. 314.16(B)(2): internal clamps add one allowance = 2.50 in³. 314.16(B)(4): each of the two device yokes gets a double allowance = 10.00 in³. 314.16(B)(5): the grounding conductors together add 2.50 in³. Total 24.50 in³ is the correct minimum; the other options drop the clamp allowance, count a yoke only once instead of double, or count each ground separately instead of as a single allowance.

Q3 NEC 314.16(B)

A box contains three internal cable clamps of different sizes. How many volume allowances for clamp fill does 314.16(B)(2) require?

  1. A One, based on the largest conductor present in the box
  2. B Three, one for each clamp
  3. C Two, since clamp allowances double like device allowances
  4. D None, because clamp fill is only counted when clamps are field-supplied
Show answer & explanation

Correct: A — One, based on the largest conductor present in the box

314.16(B)(2) requires a single volume allowance for one or more internal cable clamps, based on the largest conductor present in the box — regardless of how many clamps there are or whether they're factory or field supplied. Only a cable connector with its clamping mechanism outside the box needs no allowance.

Q4 NEC 314.16(C)

A service-entrance elbow conduit body encloses 6 AWG conductors. Which statement is correct?

  1. A Its conductor fill must be calculated per 314.16(B) like a marked conduit body
  2. B It shall not contain splices, taps, or devices, and must provide free space for all enclosed conductors
  3. C It may contain devices as long as it is supported in a rigid and secure manner
  4. D It may contain splices if its volume is marked by the manufacturer
Show answer & explanation

Correct: B — It shall not contain splices, taps, or devices, and must provide free space for all enclosed conductors

Under 314.16(C)(3), short-radius conduit bodies such as service-entrance elbows are only meant to enable installing the raceway and conductors — they shall not contain splices, taps, or devices regardless of volume marking, and must simply be sized to give free space for the enclosed conductors. The marking-and-314.16(B) fill path in 314.16(C)(2) applies to conduit bodies used for splicing, not short-radius types.

All Boxes and Conduit Bodies practice questions (Article 314)

Frequently asked questions

Do pigtails count toward box fill?
No. A conductor that originates entirely inside the box and does not leave through a knockout or cable fitting is not counted in the box fill calculation. This means a short pigtail added to connect a device to the splice wires adds zero volume.
How many volume allowances do all the equipment grounding conductors together take?
All equipment grounding conductors entering or contained in the box together count as a single volume allowance, based on the largest EGC present. Even if five separate cables each bring in a bare ground, the combined count is still one allowance.
A box has one yoke with a duplex receptacle. How many conductor volume allowances does that device add?
A single yoke — regardless of how many devices are on it — adds two volume allowances. Those two allowances are each sized to the volume of the largest conductor connected to that device or yoke.
Loomi · NEC exam prep

Practice the NEC concepts in this article.

Loomi turns NEC content into 12,934 spaced-repetition exam questions built for the journeyman test. Try everything free for 3 days.

Get launch access