NEC · 342 / 344 / 352 / 358

Conduit Types: EMT, PVC, RMC & IMC

Choosing the right conduit is not just a materials question — it determines whether the raceway itself can serve as a ground path and how deep it must be buried.

NEC 2017 2020 2023 Last updated 2026-06-27

The four common raceways

The journeyman exam tests four conduit types repeatedly. Each is governed by its own NEC article and has a distinct set of permitted uses, mechanical properties, and grounding implications. The articles are:

  • Article 342 — Intermediate Metal Conduit (IMC)
  • Article 344 — Rigid Metal Conduit (RMC)
  • Article 352 — Rigid Polyvinyl Chloride Conduit (PVC)
  • Article 358 — Electrical Metallic Tubing (EMT)

These four are not the only raceways in the NEC — flexible conduit, liquidtight flexible, and others also appear — but they account for the large majority of wiring-method questions on the journeyman exam and are the starting point for understanding raceway selection.

Each conduit type: construction, use, and limits

EMT — Electrical Metallic Tubing (Article 358)

EMT is the thin-wall steel conduit that dominates light commercial and commercial construction. It is unthreaded, connected with set-screw or compression couplings and connectors, and lightweight enough to bend and cut on the job with standard tools. EMT is permitted in most dry, damp, and wet locations when listed fittings are used, including exposed, concealed, embedded in concrete, and in or under cinder fill. It is not permitted where subject to severe physical damage, and its use in hazardous locations is restricted to specific conditions and listed fittings.

Because EMT is metallic and continuous, a properly installed EMT run — with listed fittings making good metal-to-metal contact at every joint — is recognized as an equipment grounding conductor under NEC 250.118.

RMC — Rigid Metal Conduit (Article 344)

RMC is the heaviest and most protective metallic conduit. It is a thick-walled, threaded conduit with couplings and locknuts that make gas-tight joints when properly assembled. Article 344 permits RMC in virtually every location: wet, damp, corrosive environments (with appropriate coatings or fittings), direct burial, embedded in concrete, and in hazardous locations. When there is doubt about which conduit will pass an inspection, RMC almost always qualifies. It is also recognized as an EGC when properly installed.

The trade-off is labor: threading requires a pipe threader, and the weight makes handling larger sizes demanding. RMC is most cost-effective where its physical protection or burial-depth advantage justifies the additional effort.

IMC — Intermediate Metal Conduit (Article 342)

IMC occupies the middle ground between RMC and EMT. It is a threaded metallic conduit with a wall thinner than RMC but thicker than EMT, resulting in a lighter conduit that still accepts threaded fittings. Its permitted uses closely parallel those of RMC — wet, damp, corrosive (with appropriate protection), direct burial, and hazardous locations — making it a popular alternative where RMC's weight is inconvenient but EMT's thinner wall is insufficient. IMC is also recognized as an EGC.

PVC — Rigid Polyvinyl Chloride Conduit (Article 352)

PVC conduit is the dominant nonmetallic raceway. Schedule 40 is the standard grade; Schedule 80 has a thicker wall for areas subject to physical damage. PVC is highly resistant to corrosion and moisture, making it the default choice in wet and corrosive environments where metallic conduit would require constant maintenance. It is permitted for direct burial, embedded in concrete, and in exposed or concealed dry, damp, and wet locations.

PVC is not generally permitted in hazardous locations, in areas where ambient temperatures exceed the conduit's listing, or in locations where it could be subject to physical damage (unless Schedule 80 or specifically listed for the purpose). It also requires expansion fittings on long runs because PVC expands and contracts significantly with temperature changes.

Critical grounding point: Because PVC is nonmetallic, it cannot serve as an EGC under any circumstances. Every circuit in PVC conduit requires a separate equipment grounding conductor inside the raceway, sized to Table 250.122. This single rule separates PVC from all three metallic conduit types and appears on nearly every conduit comparison question on the exam.

Support spacing — metallic vs. nonmetallic

Support requirements differ meaningfully between metallic and nonmetallic conduit, largely because PVC expands with heat and requires more frequent anchoring to prevent sagging.

Conduit type Typical max. support interval Within how far of boxes / terminations
EMT (Art. 358) 10 ft 3 ft
RMC (Art. 344) 10 ft (size-adjusted for larger trade sizes) 3 ft
IMC (Art. 342) 10 ft (size-adjusted for larger trade sizes) 3 ft
PVC (Art. 352) 3 ft for small trade sizes; increases with larger sizes 3 ft

The 10-foot interval for metallic conduit is a reliable benchmark for exam questions. PVC's requirement is meaningfully more frequent for smaller sizes, reflecting the need to control thermal expansion. On a long horizontal PVC run, expect to see supports and expansion fittings both called out.

Conduit selection on the exam

Most conduit-type questions follow a scenario structure: a given environment, a required outcome, and four conduit choices. Work through them by elimination using the key differentiators:

  • Hazardous location? Lean toward RMC or IMC. EMT has narrow permitted use there; PVC is generally excluded.
  • Corrosive or wet environment? PVC is chemical-resistant; all types are permitted in wet locations with appropriate fittings, but PVC requires no coating maintenance.
  • Ground path via conduit? Only metallic conduit qualifies. PVC always needs a separate wire EGC.
  • Direct burial? RMC, IMC, and listed PVC are all permitted; the conduit type determines the required cover depth under Table 300.5.
  • Physical damage risk? RMC gives the most protection; PVC Schedule 80 satisfies many exposed-location requirements; EMT is excluded where severe physical damage is likely.

Understanding the conduit fill rules is the other half of raceway work. How many conductors fit inside a given trade size of conduit is governed by Chapter 9 tables and Annex C. Use the conduit fill calculator to verify compliance, and review the conduit fill topic hub for the underlying rules.

Practice questions on this rule

Real journeyman-exam practice questions from Loomi's bank — answer first, then reveal the explanation.

Q1 NEC 358.28

An electrician wants to cut threads onto a piece of EMT in the field to attach it directly to a threaded hub. Is this permitted under 358.28(B)?

  1. A Yes, provided the threaded section is reinforced with a coupling sleeve
  2. B Yes, but only on EMT runs 6 ft (1.8 m) or shorter
  3. C Yes, as long as the threads are cut with a listed die specifically rated for thin-wall conduit
  4. D No, EMT shall not be threaded in the field
Show answer & explanation

Correct: D — No, EMT shall not be threaded in the field

358.28(B) is a flat prohibition: EMT shall not be threaded. There's no exception based on die type, run length, or added reinforcement. The only threaded EMT permitted is factory-made with integral threaded couplings complying with 358.100.

Q2 NEC 358.12

Per 358.12, which installation of EMT is NOT permitted?

  1. A Using EMT to support a lampholder, where the only support fitting is a conduit body no larger than the tubing's trade size
  2. B Installing EMT concealed in framing in a commercial building
  3. C Running EMT through a wall where it is not subject to severe physical damage
  4. D Using EMT to support a luminaire directly, with no conduit body involved
Show answer & explanation

Correct: D — Using EMT to support a luminaire directly, with no conduit body involved

358.12(2) permits a conduit body no larger than the largest trade size of the tubing to support equipment, but bars EMT from directly supporting a luminaire or other equipment. The other options describe uses that are allowed under 358.12.

Q3 NEC 358.10

Where EMT will be subject to physical damage, which material is permitted per 358.10(E)?

  1. A Any EMT type, provided it is installed concealed
  2. B Aluminum EMT with supplementary corrosion protection
  3. C Steel or stainless steel EMT
  4. D EMT of any material, provided fittings are identified for direct burial
Show answer & explanation

Correct: C — Steel or stainless steel EMT

358.10(E) limits EMT installations subject to physical damage to steel and stainless steel. Aluminum's corrosion protection under 358.10(B)(2) addresses concrete/earth exposure, not physical damage, and concealment or direct-burial-rated fittings don't substitute for the material requirement.

Q4 NEC 356.30

An electrician runs 900 mm (3 ft) of LFNC to a motor terminal where flexibility is needed to allow for vibration. Is support required at this connection?

  1. A No, because this length at a terminal requiring flexibility is specifically exempt
  2. B Yes, one fastener is required within 12 in. of the terminal regardless of length
  3. C Yes, because only fished conduit is exempt from support
  4. D No, because all LFNC under 1.8 m is exempt regardless of purpose
Show answer & explanation

Correct: A — No, because this length at a terminal requiring flexibility is specifically exempt

356.30(2) exempts securing or supporting where LFNC is installed in lengths not exceeding 900 mm (3 ft) at terminals where flexibility is required. The 1.8 m (6 ft) exemption applies only to the luminaire-tap and accessible-ceiling scenarios in items (2) and (4), not generally to all short lengths.

More practice questions: Wiring Methods and Materials (Articles 358–371)

Frequently asked questions

Can EMT serve as an equipment grounding conductor?
Yes, when properly installed with listed fittings, EMT is recognized as an equipment grounding conductor under NEC 250.118. The conduit must be continuous and all connectors and couplings must be listed for grounding. That said, a separate wire EGC is always permitted and is sometimes required — for example, when the conduit run includes expansion fittings or when the authority having jurisdiction requires it.
Does PVC conduit require a separate equipment grounding conductor?
Always. PVC is nonmetallic and cannot serve as an EGC. Every circuit run in PVC conduit must include a separate equipment grounding conductor inside the raceway, sized to Table 250.122. This is one of the most-tested distinctions between metallic and nonmetallic conduit on the journeyman exam.
Which conduit type is permitted in hazardous locations?
RMC and IMC are the metallic conduit types most broadly permitted in Class I, II, and III hazardous locations. EMT has limited permitted uses in hazardous locations (generally only in Class I, Division 2 with specifically listed fittings). PVC is generally not permitted in hazardous locations unless specifically listed for the classification. Always verify the Article 500-series requirements for the specific hazardous location class and division.
Loomi · NEC exam prep

Practice the NEC concepts in this article.

Loomi turns NEC content into 12,934 spaced-repetition exam questions built for the journeyman test. Try everything free for 3 days.

Get launch access