Free NEC practice test · Article 315

Medium Voltage Conductors, Cable, Cable Joints, and Cable Terminations practice questions

A free NEC Article 315 practice test for the journeyman exam: 13 questions on Medium Voltage Conductors, Cable, Cable Joints, and Cable Terminations, each with the answer and the why behind it.

13 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 13 journeyman-exam practice questions cover NEC Article 315 across 13 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

When MV cable (and its joints/terminations) must be shielded and grounded

NEC 315.44

Above 2000 volts, solid dielectric MV conductors need ozone-resistant, shielded insulation, and every metallic shield must be grounded — at the cable and at every joint or termination.

Q1 NEC 315.44

A permanent installation uses solid dielectric insulated conductors operated at 4160 volts phase-to-phase. Per 315.44, what does the NEC require?

  1. A Ozone-resistant insulation and shielding
  2. B Ozone-resistant insulation only, shielding is optional above 2000 volts
  3. C Neither, because the listed nonshielded exception applies up to 5000 volts in all establishments
  4. D Shielding only, since ozone resistance is required only in wet locations
Show answer & explanation

Correct: A — Ozone-resistant insulation and shielding

315.44 requires both ozone-resistant insulation and shielding for solid dielectric conductors operated above 2000 volts in permanent installations. The 5000-volt nonshielded allowance is limited to industrial establishments with qualified maintenance and supervision, not all establishments, so it doesn't apply generally.

Choosing the Right MV Ampacity Table by Voltage

NEC 315.60(C)

Tables 315.60(C)(1) through (20) cover 2001–35,000 volt conductors, and picking the right one depends on conductor metal, cable configuration, and installation method — not just voltage.

Q2 NEC 315.60(C)

An installer needs the ampacity of a three-conductor aluminum medium-voltage cable, directly buried in earth. Which factor set must ALL match before pulling a value from the correct table under 315.60(C)?

  1. A Conductor material, cable configuration, and installation method
  2. B Insulation type only, since installation method does not affect medium-voltage ampacity
  3. C Voltage class only, since all 315.60(C) tables use the same base ambient
  4. D Conductor size only, since copper and aluminum share the same table
Show answer & explanation

Correct: A — Conductor material, cable configuration, and installation method

315.60(C) splits ampacities across 20 tables by conductor material (copper/aluminum), cable configuration (single vs. three-conductor, triplexed vs. isolated), and installation method (air, conduit, duct, direct buried). Voltage alone doesn't select a table — the entire 2001-35,000 volt range shares this same set of tables. Copper and aluminum have separate tables because their ampacities differ, and installation method matters because heat dissipation differs by installation.

Base Conditions for Underground/Direct-Buried MV Ampacity Tables

NEC 315.60(F)

Tables 315.60(C)(11) through (20) only hold if earth is 20°C, load factor is 100%, thermal resistance (Rho) is 90, and burial depth stays within the stated max.

Q3 NEC 315.60(F)

Per 315.60(F), what is the maximum depth to the top of a direct-buried MV cable for the Table 315.60(C)(11) through (20) ampacities to apply as tabulated?

  1. A 750 mm (30 in.)
  2. B 1050 mm (42 in.)
  3. C 900 mm (36 in.)
  4. D 600 mm (24 in.)
Show answer & explanation

Correct: C — 900 mm (36 in.)

315.60(F)(7) caps the maximum depth to the top of direct-buried cables at 900 mm (36 in.). 750 mm (30 in.) is the maximum for duct banks instead, a common mix-up the closest distractor tests. The other depths aren't referenced in this section.

Required marking info and methods for MV cables/conductors

NEC 315.16(A)

Every MV cable must show voltage rating, type letters, maker's mark, and AWG/kcmil size, using one of four approved marking methods.

Q4 NEC 315.16(A)

Per 315.16(A), which of the following is NOT one of the required markings for Type MV cables and conductors?

  1. A The AWG size or circular mil area
  2. B The maximum rated voltage
  3. C The manufacturer's name, trademark, or other distinctive marking
  4. D The installation date of the cable
Show answer & explanation

Correct: D — The installation date of the cable

315.16(A) requires the maximum rated voltage, the type letters, the manufacturer's identifying mark, and the AWG or circular mil size. Installation date is not a required marking item.

Where Type MV cable is permitted to be installed

NEC 315.32(A)

Type MV cable is rated up to 35,000 volts and is permitted in wet or dry locations, raceways, cable trays, messenger-supported wiring, exposed runs, direct burial, and corrosive or sunlit locations when identified for that use.

Q5 NEC 315.32(A)

Type MV cable is permitted for use on power systems rated up to and including what nominal voltage?

  1. A 35,000 volts
  2. B 15,000 volts
  3. C 600 volts
  4. D 1,000 volts
Show answer & explanation

Correct: A — 35,000 volts

Per 315.32(A), Type MV cable is permitted on power systems rated up to and including 35,000 volts, nominal. The 600-volt and 1,000-volt options describe low-voltage wiring thresholds, not the MV cable ceiling, and 15,000 volts is simply below the actual limit.

Insulation and jacket thickness for MV conductors

NEC 315.10(A)

MV conductor insulation type, and its thickness, are set by voltage class and by whether the conductor is shielded — you can't mix and match.

Q6 NEC 315.10(A)

An installer is selecting insulation thickness for a shielded solid dielectric MV conductor rated 25,000 volts. Which table applies?

  1. A Table 315.10(A)
  2. B Table 315.10(C)
  3. C Table 315.10(B)
  4. D No table applies above 5000 volts
Show answer & explanation

Correct: B — Table 315.10(C)

Table 315.10(C), per 315.10(C), covers thickness of insulation for shielded solid dielectric insulated conductors rated 2001 volts to 35,000 volts — 25,000 V shielded falls squarely in that range. Table 315.10(B) is for nonshielded conductors only, and only up to 5000 V. Table 315.10(A) covers conductor application and insulation type, not thickness.

Direct-burial requirements for MV conductors and cables

NEC 315.36

Direct-buried MV cable must be shielded and grounded through its metallic shield, sheath, or armor — with narrow exceptions for low-range multiconductor cable and airfield lighting.

Q7 NEC 315.36

Per 315.36, what is the general requirement for Type MV conductors and cables used in direct-burial applications?

  1. A They must be rated above 5000 volts to qualify for burial
  2. B They must be installed only in rigid metal conduit, never buried directly
  3. C They must be shielded and identified for direct-burial use
  4. D They must be nonshielded with a nonmetallic jacket only
Show answer & explanation

Correct: C — They must be shielded and identified for direct-burial use

315.36 requires direct-burial MV conductors and cables to be shielded, identified for such use, and installed per 305.15. A nonmetallic-jacket-only nonshielded cable doesn't meet this unless it falls under the narrow 2001-2400V metallic sheath/armor exception, and direct burial itself is the point of this section, not conduit-only installation.

Required marking for MV cable joints, terminations, and connectors

NEC 315.17(A)

MV cable joints, terminations, and connectors must be marked with voltage, type letters, manufacturer, and conductor size — by surface marking or a durable tag.

Q8 NEC 315.17(A)

Under 315.17(B), how may a Type MV cable joint or termination be marked?

  1. A By surface marking only, since tags are prohibited on MV joints
  2. B Only by a tag, because MV joint surfaces cannot hold a legible marking
  3. C By durable surface marking or a durably printed tag/label attached to the joint or termination
  4. D By listing the information solely in the installation instructions shipped with the joint
Show answer & explanation

Correct: C — By durable surface marking or a durably printed tag/label attached to the joint or termination

315.17(B)(1) and (B)(2) allow either durable surface marking or a durably printed tag/label attached to the joint or termination — one or both methods satisfy the requirement. Restricting to only surface marking or only a tag, or relying on separate paperwork, isn't what the code specifies.

Where MV cable joints and terminations are permitted to be installed

NEC 315.32(B)

MV cable joints and terminations up to 35,000 volts are allowed in sunlight, direct burial, submersion, vaults, and cable trays — but only when identified for that specific use.

Q9 NEC 315.32(B)

A Type MV cable termination is being installed on a 35,000-volt system where it will be exposed to direct sunlight. What does 315.32(B) require?

  1. A The termination must additionally be rated for submersion
  2. B The termination must be identified for use in direct sunlight
  3. C Direct sunlight exposure is not addressed and defaults to general MV cable rules
  4. D No special identification is needed if the system voltage is at or below 35,000 volts
Show answer & explanation

Correct: B — The termination must be identified for use in direct sunlight

315.32(B)(1) specifically requires that Type MV cable joints and terminations exposed to direct sunlight be identified for that use. Meeting the 35,000-volt ceiling alone isn't sufficient, and submersion identification is a separate, unrelated requirement under 315.32(B)(3).

Ambient Temperature Correction for MV Ampacities

NEC 315.60(D)(4)

MV cable ampacities from the tables are only valid at the table's stated ambient — anything hotter or cooler requires a correction factor before you can trust the number.

Q10 NEC 315.60(D)(4) Code lookup

A 15 kV shielded MV cable feeder is run through a boiler room where the ambient temperature will run well above the 40°C base used in the ampacity tables. Which section provides the correction factors (or equation) needed to adjust the tabulated ampacity for this higher ambient temperature?

  1. A 315.60(D)(1)
  2. B 315.60(D)(4)
  3. C 315.60(D)(2)
  4. D 315.60(E)
Show answer & explanation

Correct: B — 315.60(D)(4)

315.60(D)(4) is the ambient temperature correction rule and hosts Table 315.60(D)(4) with the correction factors and equation. 315.60(D)(2) covers burial depth adjustment and 315.60(D)(1) covers grounded shields — both are different adjustment factors, not ambient temperature.

Base Conditions for In-Air MV Ampacity Tables

NEC 315.60(E)

The in-air ampacity tables assume 90°C or 105°C conductors in 40°C ambient air — correct for anything else using 315.60(D)(4).

Q11 NEC 315.60(E)

The ampacities in Table 315.60(C)(1) through Table 315.60(C)(10) for medium-voltage conductors in air are based on which ambient air temperature?

  1. A 20°C (68°F)
  2. B 30°C (86°F)
  3. C 25°C (77°F)
  4. D 40°C (104°F)
Show answer & explanation

Correct: D — 40°C (104°F)

315.60(E)(2) sets the base ambient air temperature for the in-air ampacity tables at 40°C (104°F). The other values are common base ambients for other ampacity contexts but not the one specified for this section.

Ampacity Adjustment for Changed Burial Depth

NEC 315.60(D)(2)

Going shallower never needs a derate; going deeper does — 6% per foot deeper, unless the deeper run is under 25% of the total duct length.

Q12 NEC 315.60(D)(2)

An electrical duct bank run is mostly at the table's assumed burial depth, but 15% of the total run length was installed deeper to clear an existing storm drain. What does 315.60(D)(2)(a) permit?

  1. A A full 6% per foot derate must be applied to the entire run
  2. B No decrease in ampacity is required, since the deepened portion is less than 25% of the total run length
  3. C The derate requirement is waived only if the deepened section is backfilled with low-rho material
  4. D A full 6% per foot derate must be applied, but only to the deepened 15% portion
Show answer & explanation

Correct: B — No decrease in ampacity is required, since the deepened portion is less than 25% of the total run length

315.60(D)(2)(a) allows skipping the ampacity decrease when the total length of deepened duct run is less than 25 percent of the total run length — 15% qualifies. Applying the 6% per foot factor (to the whole run or just the deepened part) is the 315.60(D)(2)(b) rule for when depth is deeper than the table basis generally, and it doesn't come with a backfill-material exception in this section.

Calculating MV Ampacity Under Engineering Supervision

NEC 315.60(B)

Under engineering supervision, MV conductor ampacity can be calculated from a heat-balance equation instead of read from a table.

Q13 NEC 315.60(B)

Per 315.60(B), under what condition may MV conductor ampacity be determined by direct calculation rather than by table?

  1. A Only when no applicable ampacity table exists for the cable type
  2. B Under engineering supervision
  3. C Only when the AHJ pre-approves the specific cable run
  4. D Only for conductors operating above 46 kV
Show answer & explanation

Correct: B — Under engineering supervision

315.60(B) permits ampacity to be calculated using the general equation when done under engineering supervision. It is not limited to voltages above 46 kV, does not require AHJ pre-approval of the calculation itself, and isn't restricted to cases where no table exists.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access