Free NEC practice test · Chapter 3

Wiring Methods and Materials practice questions (Articles 372–393)

A free practice test over NEC Chapter 3 — wiring methods and materials — for the journeyman exam: 50 questions across 11 articles, each with the answer and the why behind it.

50 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 50 journeyman-exam practice questions cover NEC Chapter 3 · Articles 372–393 across 50 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Header installation and bonding

NEC 372.18(A)

The header must run straight and square to the cells, stay electrically continuous end to end, and bond to the distribution center enclosure.

Q1 NEC 372.18(A)

Per 372.18(A), how must a header be oriented relative to the cells of a cellular concrete floor?

  1. A At a 45-degree diagonal to minimize bends
  2. B In a straight line at right angles to the cells
  3. C In any direction as long as it reaches the distribution center
  4. D Parallel to the cells along the shortest run
Show answer & explanation

Correct: B — In a straight line at right angles to the cells

372.18(A) requires the header to be installed in a straight line at right angles to the cells. Running it parallel, diagonal, or in an arbitrary direction does not meet this installation requirement.

Insert installation and grounding

NEC 372.18(D)

Inserts must be metal, leveled, sealed against concrete, and grounded back to the header — and any cutting near the cell must not damage conductors or leave debris.

Q2 NEC 372.18(D)

Per 372.18(D), how must a cellular metal floor insert receptacle be grounded?

  1. A By an equipment grounding conductor or bonding jumper to a positive ground connection on the header
  2. B By a separate ground rod driven near the insert location
  3. C By the metal insert body alone, with no jumper required
  4. D By reliance on contact between the insert and the surrounding concrete
Show answer & explanation

Correct: A — By an equipment grounding conductor or bonding jumper to a positive ground connection on the header

372.18(D) requires an equipment grounding conductor or bonding jumper connecting insert receptacles to a positive ground connection on the header. Concrete contact, a separate ground rod, and relying on the insert body alone are not recognized grounding paths under this section.

Conductor size and fill limits

NEC 372.20

Cellular metal floor raceways cap conductors at 1/0 AWG and cap total fill at 40% of the cell or header's cross-sectional area.

Q3 NEC 372.20

How is the maximum fill for conductors and cables in a cellular metal floor cell or header determined?

  1. A By the combined cross-sectional area of all conductors and cables not exceeding 40 percent of the cell or header area
  2. B By counting no more than three current-carrying conductors per cell
  3. C By a fixed conduit fill table like Chapter 9
  4. D By limiting fill to 40 percent of only the largest single conductor's area
Show answer & explanation

Correct: A — By the combined cross-sectional area of all conductors and cables not exceeding 40 percent of the cell or header area

372.22 measures fill as the combined cross-sectional area of all conductors or cables against the cell or header's own cross-sectional area, capped at 40 percent. This is not a conduit-fill-table calculation, a conductor-count rule, or based on a single conductor's area.

Removing conductors at abandoned outlets

NEC 372.58

When a cellular metal floor raceway outlet is discontinued, pull the dead conductors out entirely — don't leave spliced or reinsulated wire capped off inside the raceway.

Q4 NEC 372.58 Code lookup

A general-purpose outlet fed from a cellular concrete floor raceway is being removed as part of a remodel, and the outlet box will no longer be used. Which section governs what must be done with the circuit conductors that fed that outlet?

  1. A 372.56
  2. B 372.12
  3. C 372.58
  4. D 372.18(D)
Show answer & explanation

Correct: C — 372.58

372.58 specifically requires that conductors supplying a discontinued outlet be removed from the raceway, with no splices or reinsulated conductors left in place. 372.56 covers splices and taps for conductors still in service, and 372.18(D) addresses inserts for cellular concrete floor raceway installation, not abandoned-outlet conductor removal.

Junction box leveling and bonding

NEC 372.18(C)

Cellular floor junction boxes must be leveled to floor grade, sealed against water and concrete, and made of metal that's mechanically and electrically continuous with the header.

Q5 NEC 372.18(C)

Per 372.18(C), a junction box in a cellular metal floor raceway system must be sealed against the free entrance of what during a concrete pour?

  1. A Conduit fill material
  2. B Insulation fibers
  3. C Water or concrete
  4. D Dust and debris only
Show answer & explanation

Correct: C — Water or concrete

372.18(C) specifically requires junction boxes to be sealed against the free entrance of water or concrete, since these boxes sit at floor level during pours. Dust, insulation, and conduit fill are not the hazards this rule addresses.

Connecting Cellular Floor Raceways to Cabinets and Wall Outlets

NEC 374.18(A)

Cellular metal floor raceways must connect to cabinets and wall outlets using a specific list of conduit types, with nonmetallic options allowed only when an equipment grounding conductor termination is provided.

Q6 NEC 374.18(A) Code lookup

A cellular metal floor raceway system is installed in a concrete slab, and the electrician needs to run a listed, direct-burial-marked liquidtight flexible nonmetallic conduit from the raceway up into a wall outlet. Which section covers the permitted methods for making this connection?

  1. A 374.18(C)
  2. B 374.18(A)
  3. C 374.18(B)
  4. D 374.56
Show answer & explanation

Correct: B — 374.18(A)

374.18(A) specifically lists the permitted wiring methods — including liquidtight flexible nonmetallic conduit listed and marked for direct burial when installed in concrete — for connecting cellular metal floor raceways to cabinets and wall outlets. 374.18(B) covers junction boxes and 374.18(C) covers inserts, not the connection wiring method; 374.56 governs splices and taps within the raceway itself, not the riser connection to a cabinet.

Junction Boxes and Inserts: Leveling, Sealing, and Metal Continuity

NEC 374.18(B)

Junction boxes and inserts in cellular metal floor raceways must be level with the floor, sealed against water or concrete, and metal for electrical continuity with the raceway.

Q7 NEC 374.18(B)

An electrician is installing a junction box on a cellular metal floor raceway before the concrete pour. Which requirement applies specifically to this junction box under 374.18(B)?

  1. A It must be leveled to floor grade and sealed against the free entrance of water or concrete
  2. B It must be leveled to floor grade only, with sealing left to the concrete contractor
  3. C It may be nonmetallic as long as it is sealed against water
  4. D It must be sealed against concrete only, since water entry is addressed elsewhere
Show answer & explanation

Correct: A — It must be leveled to floor grade and sealed against the free entrance of water or concrete

374.18(B) requires junction boxes to be leveled to floor grade and sealed against the free entrance of water or concrete, and to be metal and electrically continuous with the raceway. Leaving sealing to others, allowing a nonmetallic box, or sealing against concrete alone all omit part of the actual requirement.

Splices, Taps, and Discontinued Outlets with Loop Wiring

NEC 374.56

Splices and taps in cellular metal floor raceways belong only in header access units or junction boxes, and abandoned outlets must have their conductors pulled out, not just capped.

Q8 NEC 374.56

In a cellular metal floor raceway system, where are splices and taps permitted to be made?

  1. A Only within 300 mm (12 in.) of an outlet
  2. B Only at the point where loop wiring enters the floor
  3. C Only in header access units or junction boxes
  4. D Anywhere along the raceway as long as it's accessible
Show answer & explanation

Correct: C — Only in header access units or junction boxes

374.56 restricts splices and taps to header access units or junction boxes. There's no general allowance for splicing anywhere accessible, no special loop-wiring-entry exception, and no 300 mm distance rule in this section.

Where Cellular Metal Floor Raceways Cannot Be Used

NEC 374.12

Cellular metal floor raceways are barred from corrosive-vapor areas, hazardous locations, and most commercial garage wiring.

Q9 NEC 374.12

Under 374.12, in which location are conductors prohibited from being installed in cellular metal floor raceways?

  1. A An area subject to corrosive vapor
  2. B A dry commercial office floor
  3. C A floor slab in a retail store
  4. D An area below a raised computer room floor
Show answer & explanation

Correct: A — An area subject to corrosive vapor

374.12(1) prohibits conductors in cellular metal floor raceways where subject to corrosive vapor. The other listed areas aren't among the prohibited-use conditions in this section.

Conductor size limits and wireway fill

NEC 376.22

Wireway conductors can't exceed 20% fill at any cross section, and derating only kicks in past 30 current-carrying conductors.

Q10 NEC 376.22

An electrician is filling a wireway with multiple conductors and cables. Per 376.22(A), what limits the total fill?

  1. A The sum of cross-sectional areas cannot exceed 40% of the wireway's interior cross-sectional area
  2. B The fill percentage is averaged over the entire length of the wireway run
  3. C The sum of cross-sectional areas of all conductors and cables cannot exceed 20% of the wireway's interior cross-sectional area at any cross section
  4. D No more than 30 conductors may occupy the wireway at any cross section
Show answer & explanation

Correct: C — The sum of cross-sectional areas of all conductors and cables cannot exceed 20% of the wireway's interior cross-sectional area at any cross section

376.22(A) caps wireway fill at 20% of interior cross-sectional area at any cross section — not 40% (a conduit-fill-style figure that doesn't apply here), not a conductor count, and not an average over the run since the rule applies at any cross section.

Installing power distribution blocks in wireways

NEC 376.56(B)

Power distribution blocks in metal wireways must be listed, sized to the wireway per instructions, keep live parts covered, and leave terminals unobstructed with proper bending space.

Q11 NEC 376.56(B) Code lookup

A metal wireway on a service entrance job will have a listed power distribution block installed on the line side of the service equipment. Which section specifies the installation and marking requirements for that block?

  1. A 376.56(A)
  2. B 376.56(B)(1)
  3. C 376.60
  4. D 376.56(B)(4)
Show answer & explanation

Correct: B — 376.56(B)(1)

376.56(B)(1) requires power distribution blocks in metal wireways to be listed, and marked for line-side service use when installed ahead of the service equipment. 376.56(A) instead governs splices and taps (not distribution blocks), and 376.56(B)(4) addresses exposed live parts rather than listing/marking.

Wireway construction requirements

NEC 376.100(B)

A wireway must be a rigid, corrosion-protected enclosure with fasteners no more than 300 mm (12 in.) apart, smooth bushed openings, and covers securely fastened.

Q12 NEC 376.100(B)

Per 376.100(B), corner joints of a wireway assembled with screws must have fasteners spaced no more than what distance apart?

  1. A 150 mm (6 in.)
  2. B 300 mm (12 in.)
  3. C 600 mm (24 in.)
  4. D 450 mm (18 in.)
Show answer & explanation

Correct: B — 300 mm (12 in.)

376.100(B) requires corner joint fasteners (rivets, bolts, or screws) to be spaced not more than 300 mm (12 in.) apart. The 150 mm option is too tight and not a code figure here, while 450 mm and 600 mm exceed the maximum allowed spacing and would risk gaps in the enclosure.

Insulated conductors: deflection and pull-box use

NEC 376.23

Deflected conductors in a metal wireway need Table 312.6(A) one-wire-per-terminal spacing, and wireways used as pull boxes follow the 314.28 straight- and angle-pull distances.

Q13 NEC 376.23

Insulated conductors in a metal wireway are deflected 45 degrees where a conduit enters the wireway. Which requirement applies?

  1. A Dimensions corresponding to one wire per terminal in Table 312.6(A)
  2. B The straight-pull distance formula in 314.28(A)(1)
  3. C No special spacing is required since the wireway itself is not a terminal
  4. D The angle-pull distance formula in 314.28(A)(2)
Show answer & explanation

Correct: A — Dimensions corresponding to one wire per terminal in Table 312.6(A)

Per 376.23(A), a deflection greater than 30 degrees at a raceway entry requires dimensions corresponding to one wire per terminal in Table 312.6(A). The 314.28(A) distance formulas apply instead to wireways used as pull boxes for 4 AWG and larger conductors under 376.23(B), not to deflection at entries.

Supporting wireways horizontally and vertically

NEC 376.30

Horizontal wireway runs need support every 5 ft (10 ft max between supports); vertical runs need support every 15 ft with no more than one joint between supports.

Q14 NEC 376.30

An electrician is installing a metal wireway in a horizontal run using individual lengths longer than 5 ft, supported only at each end or joint. What is the maximum spacing allowed between those supports?

  1. A 4.5 m (15 ft)
  2. B 3 m (10 ft)
  3. C 1.5 m (5 ft)
  4. D 6 m (20 ft)
Show answer & explanation

Correct: B — 3 m (10 ft)

Per 376.30(A), even when individual lengths longer than 5 ft are supported at each end or joint instead of at 5 ft intervals, the distance between supports still cannot exceed 3 m (10 ft). The 5 ft figure is the standard interval, not the max gap for this case, and 15 ft and 20 ft are well beyond the horizontal limit.

Closing dead ends and grounding metal wireways

NEC 376.60

Every dead end of a metal wireway must be closed, and listed metal wireway can itself serve as the equipment grounding conductor.

Q15 NEC 376.60

Under what condition is a metal wireway permitted to serve as the equipment grounding conductor for the circuits it contains?

  1. A When the wireway is listed for that purpose, per 250.118(A)(13)
  2. B Only in industrial establishments with qualified maintenance and supervision
  3. C Only when a separate bonding jumper is also installed inside the wireway
  4. D Whenever the wireway is metal, regardless of listing
Show answer & explanation

Correct: A — When the wireway is listed for that purpose, per 250.118(A)(13)

376.60 permits listed metal wireway to serve as an equipment grounding conductor in accordance with 250.118(A)(13) — the listing is the key qualifier, not simply being metal. A separate bonding jumper or an industrial-only condition is not part of this permission as stated in these sections.

Conductor sizing and fill limits in nonmetallic wireway

NEC 378.22

Nonmetallic wireway conductors are capped at 20% fill, and beyond that, adjustment factors still apply once you cross the 20% threshold, not before.

Q16 NEC 378.22

Per 378.22, what is the maximum permitted fill for the sum of cross-sectional areas of all contained conductors and cables at any cross section of a nonmetallic wireway?

  1. A 40 percent of the interior cross-sectional area
  2. B 20 percent of the exterior cross-sectional area
  3. C 53 percent of the interior cross-sectional area
  4. D 20 percent of the interior cross-sectional area
Show answer & explanation

Correct: D — 20 percent of the interior cross-sectional area

378.22 sets the nonmetallic wireway fill cap at 20 percent of the interior cross-sectional area. The 40 percent figure is a conduit-fill number from a different chapter, not wireway, and the exterior-area option misstates that the rule is based on interior area.

Expansion fittings for thermal movement

NEC 378.44

Install an expansion fitting in nonmetallic wireway wherever a straight run is expected to change length by 6 mm (0.25 in.) or more.

Q17 NEC 378.44

Per 378.44, an expansion fitting is required in a straight run of nonmetallic wireway when the expected length change is:

  1. A 13 mm (0.5 in.) or greater
  2. B 3 mm (0.125 in.) or greater
  3. C 6 mm (0.25 in.) or greater
  4. D Any measurable amount, however small
Show answer & explanation

Correct: C — 6 mm (0.25 in.) or greater

378.44 sets the threshold at 6 mm (0.25 in.) or greater expected length change in a straight run. The 3 mm and 13 mm figures are both plausible-sounding but wrong thresholds, and 'any measurable amount' overstates the rule — small movements below 1/4 in. don't trigger the requirement.

Grounding and extending from nonmetallic wireway

NEC 378.60

Nonmetallic wireway has no metal to ground through, so a separate equipment grounding conductor is required unless the grounded conductor is doing that job under 250.142, and any extension off the wireway must carry or connect to that ground too.

Q18 NEC 378.60 Code lookup

A crew is running conductors through a nonmetallic wireway on a job where equipment grounding is required for the connected equipment. Which section specifies whether a separate equipment grounding conductor must be installed in the wireway?

  1. A 378.70
  2. B 378.23
  3. C 378.56
  4. D 378.60
Show answer & explanation

Correct: D — 378.60

378.60 (Grounding) requires a separate equipment grounding conductor in the nonmetallic wireway unless the grounded conductor is permitted to ground equipment under 250.142. 378.70 covers grounding only for extensions leaving the wireway via cord pendants or Chapter 3 wiring methods, not conductors run within the wireway itself.

Insulated conductor deflection and pull-box use

NEC 378.23

Sharp bends in a nonmetallic wireway need Table 312.6(A) one-wire-per-terminal spacing, and using one as a pull box for 4 AWG+ conductors triggers 314.28 sizing.

Q19 NEC 378.23

6 AWG insulated conductors are pulled through a nonmetallic wireway between two raceway entries enclosing the same conductors. Does 378.23(B)'s pull-box distance rule apply?

  1. A Yes, but only because the wireway is nonmetallic
  2. B Yes, because any conductor pulled through a wireway is subject to 314.28 distances
  3. C No, because pull-box rules never apply to wireways, only to boxes
  4. D No, because 378.23(B) only applies to conductors 4 AWG or larger
Show answer & explanation

Correct: D — No, because 378.23(B) only applies to conductors 4 AWG or larger

378.23(B) sets its pull-box distance requirement specifically for insulated conductors 4 AWG or larger; 6 AWG falls below that threshold, so the rule doesn't trigger. The wireway's material isn't the deciding factor, and wireways are explicitly addressed by this section as functioning like pull boxes when the size threshold is met.

Installing parallel conductors in nonmetallic wireway

NEC 378.20

In nonmetallic wireway, paralleled single conductors must be grouped with one conductor per phase, neutral, and ground in each group to avoid inductive imbalance.

Q20 NEC 378.20 Code lookup

A contractor is running three sets of parallel 500 kcmil single-conductor cables per phase for a feeder inside a nonmetallic wireway. Which section specifies how the individual conductors must be grouped within the wireway to prevent current imbalance from inductive reactance?

  1. A 378.21
  2. B 378.22
  3. C 378.23
  4. D 378.20
Show answer & explanation

Correct: D — 378.20

378.20 directly addresses parallel single-conductor cables in nonmetallic wireway, requiring each group to contain no more than one conductor per phase, neutral, or grounded conductor to avoid inductive imbalance. 378.22 (Number of Conductors) governs fill/derating, not paralleling groups, and 378.21 covers conductor sizing, not arrangement.

Where multioutlet assemblies are prohibited

NEC 380.12

Multioutlet assemblies can't be hidden in walls, exposed to damage or corrosion, used above 300V unless thick metal, run in hoistways or hazardous locations, or be cord-and-plug connected.

Q21 NEC 380.12

Under what condition is it permissible for a multioutlet assembly to be partly concealed by building finish?

  1. A When the circuit voltage is under 50 volts
  2. B When it is metal and the building finish surrounds the back and sides
  3. C When it is nonmetallic and the building finish surrounds the back and sides
  4. D When it is installed in a hoistway shaft wall
Show answer & explanation

Correct: B — When it is metal and the building finish surrounds the back and sides

Per 380.12(1), a metal multioutlet assembly may have its back and sides surrounded by building finish; the exception for a nonmetallic assembly is recessing into a baseboard, not general wall concealment. Hoistways are separately prohibited, and voltage under 50 volts has no bearing on this exception.

Insulated conductor rules for multioutlet assemblies

NEC 380.23

Conductors deflected inside a multioutlet assembly need one-wire-per-terminal spacing from Table 312.6(A), and 4 AWG+ conductors pulled through it as a raceway follow the 314.28 pull-box distances.

Q22 NEC 380.23

A field-assembled multioutlet assembly changes direction by 45 degrees. What sizing rule applies to the insulated conductors at that point?

  1. A Dimensions corresponding to one wire per terminal in Table 312.6(A) apply
  2. B The assembly must be treated as a junction box sized under 314.28(A)(2) regardless of conductor size
  3. C Table 312.6(A) applies only if the conductors are 4 AWG or larger
  4. D No special sizing is required since multioutlet assemblies are exempt from box fill rules
Show answer & explanation

Correct: A — Dimensions corresponding to one wire per terminal in Table 312.6(A) apply

Per 380.23(A), any deflection greater than 30 degrees in a multioutlet assembly's direction requires dimensions for one wire per terminal from Table 312.6(A) — this applies regardless of conductor size, unlike the pull-box rule in 380.23(B) which is specific to 4 AWG and larger.

Concealable nonmetallic extension: three-layer flat conductor construction

NEC 382.100

Concealable nonmetallic extension is built in three flat layers: an ungrounded center, a sectioned grounded conductor around it, and a sectioned EGC on the outside.

Q23 NEC 382.100

Per 382.100, how is a concealable nonmetallic extension built, from the center outward?

  1. A Grounded conductor at center, ungrounded conductor sectioned around it, EGC outermost
  2. B Ungrounded conductor at center, sectioned EGC around it, sectioned grounded conductor outermost
  3. C Two ungrounded conductors at center with a single overall grounded/EGC combination layer outside
  4. D Ungrounded conductor at center, sectioned grounded conductor around it, sectioned equipment grounding conductor outermost
Show answer & explanation

Correct: D — Ungrounded conductor at center, sectioned grounded conductor around it, sectioned equipment grounding conductor outermost

382.100 defines the multilayer flat conductor design as a center ungrounded conductor enclosed by a sectioned grounded conductor, with an overall sectioned equipment grounding conductor as the outermost layer. Swapping the grounded and EGC layer order, or centering the grounded conductor, misstates the required layer sequence.

Receptacles and devices used with concealable extensions

NEC 382.42

Every receptacle, housing, or self-contained device used with concealable nonmetallic extensions must be identified for that specific use.

Q24 NEC 382.42

Under 382.42(A), what is required of receptacles and self-contained devices used with concealable nonmetallic extensions?

  1. A They must be rated for at least 20 amperes
  2. B They must be identified for use with concealable nonmetallic extensions
  3. C They must be listed for use in wet locations
  4. D They must be metal-clad for mechanical protection
Show answer & explanation

Correct: B — They must be identified for use with concealable nonmetallic extensions

382.42(A) specifically requires that all receptacles, receptacle housings, and self-contained devices used with concealable nonmetallic extensions be identified for this use. Wet-location listing, a minimum 20 A rating, and metal-clad construction are not requirements found in this section.

Securing and anchoring extension runs

NEC 382.30

Nonmetallic surface extensions fasten every 200 mm (8 in.), while concealable types skip fasteners entirely for an identified adhesive or mechanical anchoring system.

Q25 NEC 382.30

A nonmetallic surface extension runs along plaster finish between two outlets. What is the maximum spacing allowed between fasteners?

  1. A 150 mm (6 in.)
  2. B 300 mm (12 in.)
  3. C 200 mm (8 in.)
  4. D 450 mm (18 in.)
Show answer & explanation

Correct: C — 200 mm (8 in.)

382.30(A) sets the maximum fastening interval at 200 mm (8 in.). The 300 mm (12 in.) figure is a distractor — it's only the allowed distance to the first fastener where the extension connects to its supplying outlet via an attachment plug, not the general spacing rule.

Where nonmetallic extensions are prohibited

NEC 382.12

Nonmetallic extensions are banned in unfinished basements/attics, above 150V (300V for aerial cable), near corrosive vapors, and anywhere they'd run through a floor, partition, or leave the room they started in.

Q26 NEC 382.12

Which location is a nonmetallic extension prohibited from being installed in?

  1. A A retail sales floor
  2. B A finished basement recreation room
  3. C An unfinished attic
  4. D A finished office with a suspended ceiling
Show answer & explanation

Correct: C — An unfinished attic

382.12(1) prohibits nonmetallic extensions in unfinished basements, attics, or roof spaces because of exposure to physical damage. Finished spaces like a basement rec room, an office, or a retail floor aren't covered by this prohibition.

Where nonmetallic extensions can originate and be installed

NEC 382.10

A nonmetallic extension must tap off an existing 15- or 20-amp outlet, stay exposed or permissibly concealed in a dry location, and surface types are capped at three stories unless identified for higher use.

Q27 NEC 382.10

An electrician wants to install a nonmetallic surface extension in a building. Under what condition is this permitted per 382.10(C)?

  1. A The building is used for industrial storage and is two floors above grade
  2. B The building is any occupancy type as long as it is a single floor
  3. C The building is occupied for residential or office purposes and does not exceed three floors above grade
  4. D The extension is identified for use above three floors and the building is a warehouse
Show answer & explanation

Correct: C — The building is occupied for residential or office purposes and does not exceed three floors above grade

382.10(C) permits surface-mounted nonmetallic extensions only in buildings occupied for residential or office purposes, not exceeding three floors above grade. Industrial or warehouse occupancies aren't listed as permitted regardless of floor count, and the 'identified for use above three floors' exception applies only to concealable extensions, not surface-mounted ones.

Concealable nonmetallic extension: cable and conductor marking

NEC 382.120

Concealable nonmetallic extension cable must be marked on both sides at least every 24 in. (610 mm), while the conductors inside must be identified continuously along their whole length.

Q28 NEC 382.120 Code lookup

A concealable nonmetallic extension is installed and must be checked for the required cable markings, including conductor material, maximum temperature rating, and ampacity, printed on both sides at set intervals. Which section specifies these cable marking requirements?

  1. A 382.120(A)
  2. B 382.120(B)
  3. C 382.112
  4. D 382.104
Show answer & explanation

Correct: A — 382.120(A)

382.120(A) is the specific subsection requiring durable marking on both sides at 610 mm (24 in.) intervals with conductor material, maximum temperature rating, and ampacity. 382.120(B) instead governs individual conductor identification, not the cable's exterior marking, and 382.104/382.112 cover conductor construction and insulation, not marking.

Securing and supporting strut-type channel raceways

NEC 384.30

Strut-type channel raceways — surface or suspension mounted — need support every 10 ft max, and within 3 ft of any termination.

Q29 NEC 384.30 Code lookup

A run of surface-mounted strut-type channel raceway is installed along a wall between two junction boxes, with no other terminations in between. Which section specifies the maximum spacing for the retention straps securing it to the wall?

  1. A 384.22
  2. B 384.30(B)
  3. C 384.30(A)
  4. D 384.6
Show answer & explanation

Correct: C — 384.30(A)

384.30(A) sets the 3 m (10 ft) maximum spacing and 900 mm (3 ft) from termination rule specifically for surface-mounted strut-type channel raceway retention straps. 384.30(B) covers suspension mounting instead of surface mounting, and 384.22/384.6 don't address securing intervals.

Strut-type channel raceway construction requirements

NEC 384.100

Strut-type channel raceway must be steel, stainless steel, or aluminum, with steel protected against corrosion, and covers can be metal or nonmetallic.

Q30 NEC 384.100

Which material is NOT permitted for forming strut-type channel raceways and their accessories per 384.100(A)?

  1. A Stainless steel
  2. B Aluminum
  3. C Rigid PVC
  4. D Steel
Show answer & explanation

Correct: C — Rigid PVC

384.100(A) limits strut-type channel raceways and accessories to steel, stainless steel, or aluminum. Rigid PVC is not a listed material for the raceway body itself — PVC is only mentioned in 384.100(B) as an example of an organic coating used to protect steel raceways from corrosion, not as a raceway material.

Conductor sizing and fill limits in strut-type channel raceways

NEC 384.22

Conductors must match the raceway's listing for size, and total fill is capped by Table 384.22 unless a specific large-raceway exception lifts the adjustment factors.

Q31 NEC 384.22 Code lookup

An electrician is installing THHN conductors in a strut-type channel raceway and needs to determine how many conductors are allowed based on the raceway's cross-sectional area and percentage fill. Which section provides this fill limit?

  1. A 384.100
  2. B 384.6
  3. C 384.22
  4. D 384.21
Show answer & explanation

Correct: C — 384.22

384.22 governs the number of conductors permitted, referencing Table 384.22 for percentage fill and Chapter 9 for conductor area. 384.21 only limits conductor size to what the raceway is listed for, not fill quantity, and 384.6/384.100 deal with listing and construction, not conductor count.

Grounding strut-type channel raceways

NEC 384.60

Strut-type channel can serve as the equipment grounding conductor itself, but a snap-fit metal cover can't be the grounding path for a receptacle mounted in it.

Q32 NEC 384.60

A receptacle is mounted directly in a snap-fit metal cover on a strut-type channel raceway. The cover achieves electrical continuity per its listing. Per 384.60, what does this mean for grounding the receptacle?

  1. A The receptacle never needs a grounding means in strut raceway
  2. B The strut raceway must be reclassified as nonmetallic once a receptacle is added
  3. C The cover's listed continuity is sufficient to ground the receptacle
  4. D The cover cannot be used as the grounding means for the receptacle mounted in it
Show answer & explanation

Correct: D — The cover cannot be used as the grounding means for the receptacle mounted in it

384.60 specifically excludes the snap-fit cover from serving as the grounding means for a receptacle mounted in it, even though that same cover can achieve electrical continuity for the raceway system generally. The idea that listed continuity automatically covers the receptacle is the exact confusion this rule addresses.

Where surface metal raceway can be used

NEC 386.10

Surface metal raceway is a dry-location product — it can pass through walls, floors, and partitions only if unbroken and only if it stays dry inside.

Q33 NEC 386.10

Under 386.10, surface metal raceway extending transversely through a dry partition is permitted only if which condition is met?

  1. A The length passing through the partition is unbroken and conductors remain accessible on both sides
  2. B The partition is rated for at least a 1-hour fire resistance
  3. C The raceway is grounded independently at each side of the partition
  4. D The raceway is filled with a fire-rated sealant at the penetration
Show answer & explanation

Correct: A — The length passing through the partition is unbroken and conductors remain accessible on both sides

386.10(4) requires that the length of surface metal raceway passing through a dry wall, partition, or floor be unbroken, and that access to the conductors be maintained on both sides. Fire sealant, independent grounding at each side, and a specific fire-resistance rating are not conditions imposed by this section.

Where surface metal raceway is prohibited

NEC 386.12

Surface metal raceway is banned from physical-damage zones, hoistways, corrosive areas, concealed spaces, and 300V+ circuits unless the metal is at least 0.040 in. thick.

Q34 NEC 386.12

Under what condition is surface metal raceway permitted on a circuit operating at 300 volts or more between conductors?

  1. A Only if the raceway metal is at least 1.02 mm (0.040 in.) thick
  2. B Only if the raceway is listed for wet locations
  3. C Surface metal raceway may never be used at 300 volts or more, regardless of construction
  4. D Only if an equipment grounding conductor is added inside the raceway
Show answer & explanation

Correct: A — Only if the raceway metal is at least 1.02 mm (0.040 in.) thick

386.12(2) prohibits surface metal raceway at 300 volts or more between conductors unless the metal has a nominal thickness of at least 1.02 mm (0.040 in.). Wet-location listing and added grounding conductors don't address this specific voltage/thickness rule, and the flat 'never' option ignores the thickness exception.

Splices and taps in surface metal raceway

NEC 386.56

Splices and taps are allowed in surface metal raceway only if the cover stays removable and accessible, and the fill at that point never exceeds 75%.

Q35 NEC 386.56 Code lookup

An electrician is running conductors through surface metal raceway on a warehouse wall and needs to splice two conductors mid-run. The raceway section has a removable cover accessible after installation. Which section specifies the maximum fill percentage allowed at the point of the splice?

  1. A 386.22
  2. B 386.21
  3. C 386.56
  4. D 386.30
Show answer & explanation

Correct: C — 386.56

386.56 covers splices and taps in surface metal raceway and sets the 75 percent fill limit at the splice point, provided the cover is removable and accessible. 386.22 governs the general number of conductors/cables the raceway can hold (not the splice-specific fill rule), and 386.21 covers conductor sizing, not splice fill.

Conductor sizing and fill limits in surface metal raceway

NEC 386.22

Surface metal raceway is rated for a specific conductor size and count — stay inside both, or drop the 310.15(C)(1) adjustment factors only if the low-fill exception applies.

Q36 NEC 386.22

An installer wants to skip applying the 310.15(C)(1) conductor adjustment factors for conductors run in a surface metal raceway. Which condition would disqualify the installation from that exception?

  1. A The raceway's interior cross-sectional area is 3000 mm2
  2. B The raceway contains 18 current-carrying conductors
  3. C The cables installed are permitted by their respective cable articles
  4. D The sum of conductor cross-sectional areas is 35 percent of the raceway's interior area
Show answer & explanation

Correct: D — The sum of conductor cross-sectional areas is 35 percent of the raceway's interior area

Per 386.22, the exception to 310.15(C)(1) adjustment factors requires the sum of conductor cross-sectional areas to be 20 percent or less of the raceway's interior area — 35 percent fails that test. A 3000 mm2 area exceeds the 2500 mm2 minimum (passes), 18 conductors is under the 30-conductor cap (passes), and cable use permitted by its own article is simply allowed under 386.22, not a disqualifier.

Where surface nonmetallic raceway can and can't be used

NEC 388.10

Surface nonmetallic raceway is a dry-location, low-abuse product: no concealment, no physical damage exposure, and nothing near 300 volts unless it's listed for it.

Q37 NEC 388.10 Code lookup

An electrician wants to run a surface nonmetallic raceway concealed above a drop ceiling in a dry office to hide it from view. Which section addresses whether this installation is allowed?

  1. A 388.10
  2. B 388.12
  3. C 388.30
  4. D 388.6
Show answer & explanation

Correct: B — 388.12

388.12(1) prohibits surface nonmetallic raceway where concealed, except for the transverse wall/floor extension allowed in 388.10(2). 388.10 covers where it IS permitted (dry locations, transverse extensions), not the concealment prohibition, and 388.6/388.30 cover listing and support, not location restrictions.

Splices and taps in surface nonmetallic raceway

NEC 388.56

Splices and taps are allowed inside surface nonmetallic raceway only if the cover opens in place after installation, and fill can't exceed 75% at that point.

Q38 NEC 388.56

Per 388.56, what is the maximum fill allowed at a point in surface nonmetallic raceway where splices and taps are located?

  1. A 53 percent of the cross-sectional area
  2. B 75 percent of the cross-sectional area
  3. C 40 percent of the cross-sectional area
  4. D 100 percent of the cross-sectional area
Show answer & explanation

Correct: B — 75 percent of the cross-sectional area

388.56 caps conductors, including splices and taps, at 75 percent of the raceway's area at that point. The 40 percent and 53 percent figures are conduit fill percentages used elsewhere in the Code for different conditions, not this section's rule.

Surface nonmetallic raceway construction requirements

NEC 388.100

Surface nonmetallic raceway must be distinguishable from other raceways, couple together without abrading wires, and resist moisture, chemicals, impact, heat distortion, and cold.

Q39 NEC 388.100

Which requirement does 388.100 place on the design of surface nonmetallic raceway couplings and fittings?

  1. A Fittings must be metallic to provide a bonding path
  2. B Couplings must be threaded to match rigid PVC conduit fittings
  3. C Sections must be solvent-welded to prevent any future disassembly
  4. D Sections must mechanically couple together without subjecting wires to abrasion
Show answer & explanation

Correct: D — Sections must mechanically couple together without subjecting wires to abrasion

388.100 requires that surface nonmetallic raceways, elbows, couplings, and similar fittings be designed so sections mechanically couple together and install without abrading the wires. It does not require solvent welding, metallic fittings, or threaded PVC-style couplings.

Separating signaling from power circuits in combination raceways

NEC 388.70

In a combination surface nonmetallic raceway, signaling and power/lighting circuits must run in separate identified compartments — never mixed in the same one.

Q40 NEC 388.70

A combination surface nonmetallic raceway is installed to carry both a signaling circuit and a lighting circuit. Per 388.70, what is required?

  1. A The different systems must be run in separate compartments identified by stamping, imprinting, or color coding
  2. B The circuits may share a compartment as long as the signaling conductors are insulated for the power circuit voltage
  3. C A grounded barrier strip must be installed between the conductor groups
  4. D The raceway must be metallic if it carries both signaling and power circuits
Show answer & explanation

Correct: A — The different systems must be run in separate compartments identified by stamping, imprinting, or color coding

388.70 requires that when combination surface nonmetallic raceways carry both signaling and lighting/power circuits, the systems be run in separate compartments identified by stamping, imprinting, or color coding of the interior finish. Insulating signaling conductors for the power voltage, requiring a metallic raceway, or adding a grounded barrier strip are not the rule this section states.

Junction Box and Insert Installation Requirements

NEC 390.74

Junction boxes and inserts in underfloor raceway systems must be leveled, sealed against concrete or water, and metal ones must stay electrically continuous with metal raceways.

Q41 NEC 390.74

An electrician is installing a junction box in an underfloor metal raceway system. Besides leveling and sealing, what additional requirement applies?

  1. A The box must be metal and electrically continuous with the raceway
  2. B The box must be nonmetallic to prevent stray current in the slab
  3. C The box must be filled with sealant compound before backfilling
  4. D The box must be bonded with a separate green ground wire to the panel
Show answer & explanation

Correct: A — The box must be metal and electrically continuous with the raceway

Per 390.74, junction boxes used with metal raceways must be metal and electrically continuous with the raceway. There's no separate bonding-wire requirement stated, no sealant-fill requirement, and nonmetallic boxes are not the rule for metal raceways.

Raceway Alignment, End Markers, and Dead Ends

NEC 390.70

Underfloor raceways must run in straight lines between junction boxes, have a marker at each run's end, and every dead end must be closed.

Q42 NEC 390.70

How must an underfloor raceway run be laid out between two junction boxes?

  1. A In the shortest path available, regardless of box alignment
  2. B With a gentle curve to ease conductor pulling
  3. C In a straight line coinciding with the centerline from box center to box center
  4. D Offset from center to avoid crossing other raceways
Show answer & explanation

Correct: C — In a straight line coinciding with the centerline from box center to box center

390.70 requires that a straight line from the center of one junction box to the center of the next coincide with the raceway's centerline. Curves, offsets, or arbitrary shortest paths are not permitted layouts under this section.

Where Underfloor Raceways Can and Cannot Be Used

NEC 390.10

Underfloor raceways are for flush-in-floor installs under concrete or office flooring — never in corrosive vapors, hazardous locations, or unprotected metal in concrete.

Q43 NEC 390.10 Code lookup

An electrician is installing an underfloor raceway system in an office building. To be permitted, the raceway must be laid flush with the concrete floor and covered with what, and under which section is this installation method authorized?

  1. A 390.76
  2. B 390.15(D)
  3. C 390.10
  4. D 390.12
Show answer & explanation

Correct: C — 390.10

390.10 is the Uses Permitted section, allowing underfloor raceways in office occupancies when laid flush with the concrete floor and covered with linoleum or equivalent flooring. 390.15(D) instead covers the concrete covering thickness for raceways once installed, not whether the installation itself is permitted.

Splices, Taps, and Abandoned Conductors in Underfloor Raceways

NEC 390.56

Splices and taps in underfloor raceways belong only in junction boxes or accessible trench-type covers, and dead conductors from removed outlets must come out, not stay capped inside.

Q44 NEC 390.56

In an underfloor raceway system, where are splices and taps generally required to be made?

  1. A Only at the raceway's terminal end fitting
  2. B Anywhere along the raceway run, provided the conductors are taped
  3. C Inside the outlet fitting itself
  4. D In junction boxes
Show answer & explanation

Correct: D — In junction boxes

390.56 requires splices and taps to be made only in junction boxes, with a narrow exception for trench-type flush raceway with an accessible removable cover. Taping conductors mid-run or landing them at a terminal fitting or outlet body doesn't satisfy this.

Listing requirements for suspended ceiling power distribution

NEC 393.6

A low-voltage suspended ceiling power system must either be listed as one complete package or be built entirely from parts each listed for that use.

Q45 NEC 393.6

A suspended ceiling power distribution system operates at 24 volts ac. Per 393.6, which installation approach is code-compliant?

  1. A Using any UL-listed low-voltage power supply paired with unlisted grid rail connectors
  2. B Listing only the power supply, since the fittings carry low enough voltage to not require listing
  3. C Listing as a complete system, or assembling entirely from parts listed for their specific function
  4. D Field-assembling the system without listing, since the voltage is below 30 volts
Show answer & explanation

Correct: C — Listing as a complete system, or assembling entirely from parts listed for their specific function

393.6 requires the system to be listed either as a complete package under 393.6(A) or built entirely from parts each listed for their appropriate function under 393.6(B). Mixing listed and unlisted components, or assuming low voltage exempts listing, does not satisfy either path.

Installing and supporting exposed grid conductors

NEC 393.14

Exposed grid support wiring must be neatly supported by the building structure without damage, and secondary conductors must be Class 2 cable or a Chapter 3 wiring method.

Q46 NEC 393.14

An electrician is installing exposed cable across the top of a suspended ceiling grid distribution system. Per 393.14(A), how must the cable be supported?

  1. A By the same messenger wire used to suspend the ceiling tiles
  2. B Laid across the ceiling grid tees without additional fasteners, since the grid itself is structural
  3. C By straps, staples, hangers, or listed cable ties so it isn't damaged by normal building use
  4. D Only where it passes through a wall, since exposed ceiling runs need no support
Show answer & explanation

Correct: C — By straps, staples, hangers, or listed cable ties so it isn't damaged by normal building use

Section 393.14(A) requires cables supported on ceilings and sidewalls to be secured by straps, staples, hangers, cable ties listed and identified for securement and support, or similar fittings that won't damage the cable. Resting cable on grid tees, relying on ceiling suspension wires, or leaving exposed ceiling runs unsupported do not meet this requirement.

Where suspended ceiling power grids are prohibited

NEC 393.12

Suspended ceiling power distribution systems are banned from wet/damp spaces, corrosive areas, physical-damage zones, concealed spaces, hazardous locations, unlisted fire-rated assemblies, and patient care lighting.

Q47 NEC 393.12

A designer proposes using a suspended ceiling power distribution system for general lighting in a hospital's general patient care area. Per 393.12, is this permitted?

  1. A Yes, as long as the branch circuit is GFCI protected
  2. B No, lighting in general or critical patient care areas is prohibited
  3. C No, but it is allowed in critical patient care areas specifically
  4. D Yes, as long as it's for general lighting only, not receptacles
Show answer & explanation

Correct: B — No, lighting in general or critical patient care areas is prohibited

393.12(7) prohibits suspended ceiling power distribution systems for lighting in both general and critical patient care areas — there's no GFCI or receptacle-vs-lighting carve-out, and the prohibition covers both area types, not just critical care.

Where suspended ceiling power grids are allowed

NEC 393.10

Suspended ceiling power grids are permanently wired, capped at Class 2 low-voltage levels, and only for listed lighting, control, or signaling equipment in dry indoor spaces.

Q48 NEC 393.10

Which type of load is permitted on a suspended ceiling power distribution system per 393.10(1)?

  1. A A 120-volt general-purpose receptacle outlet
  2. B A listed Class 2 lighting fixture rated within the 30-volt ac limit
  3. C A Class 1 power-limited signaling circuit
  4. D A motor-operated damper drawing standard branch-circuit power
Show answer & explanation

Correct: B — A listed Class 2 lighting fixture rated within the 30-volt ac limit

393.10(1) limits use to listed utilization equipment at 30 volts ac/60 volts dc maximum, within Class 2 power levels, for lighting, control, and signaling circuits only. Standard 120-volt receptacles and Class 1 circuits exceed the Class 2 / low-voltage scope.

Connector types and enclosure requirements

NEC 393.40

Busbar grid rail connections must use listed insulating connectors matched to their job — load, pendant, power feed, or rail-to-rail — and stay accessible after installation.

Q49 NEC 393.40

A low-voltage suspended ceiling grid system needs a connector to interconnect the busbar of one ceiling grid rail to an adjoining grid rail. Which connector type is required?

  1. A Load connector
  2. B Pendant connector
  3. C Power feed connector
  4. D Rail-to-rail connector
Show answer & explanation

Correct: D — Rail-to-rail connector

Per 393.40(A)(4), a rail-to-rail connector interconnects busbars from one ceiling grid rail to another. A load connector feeds utilization equipment, a pendant connector suspends luminaires below the rail, and a power feed connector ties the supply to the distribution cable and busbar — none of those join rail to rail.

Disconnect location and multiwire branch circuit rules

NEC 393.21

The Class 2 power source disconnect must be within sight and accessible, and on a multiwire branch circuit it has to open all supply conductors — including grounded conductors — at the same time.

Q50 NEC 393.21

Per 393.21(A), where must the disconnecting means for the Class 2 supply to a power grid system be located?

  1. A Within sight of the load equipment rather than the source
  2. B At the main service equipment only
  3. C Accessible and within sight of the Class 2 power source
  4. D Anywhere in the same building, regardless of sightline to the source
Show answer & explanation

Correct: C — Accessible and within sight of the Class 2 power source

393.21(A) requires the disconnecting means to be accessible and within sight of the Class 2 power source, so it's usable for servicing or maintaining the grid system. Placing it elsewhere in the building, at service equipment, or within sight of the load instead of the source does not satisfy this location requirement.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access