Free NEC practice test · Chapter 3

Wiring Methods and Materials practice questions (Articles 348–356)

A free practice test over NEC Chapter 3 — wiring methods and materials — for the journeyman exam: 45 questions across 7 articles, each with the answer and the why behind it.

45 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 45 journeyman-exam practice questions cover NEC Chapter 3 · Articles 348–356 across 45 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Securing and supporting FMC runs

NEC 348.30

FMC needs a fastener within 12 in. of every termination and support at least every 4½ ft, with specific longer-tail exceptions for flexibility and fished runs.

Q1 NEC 348.30

An electrician runs FMC through bored holes in wall studs, horizontally, terminating into a panel. What is required for the framing-member openings to count as support under 348.30(B)?

  1. A The FMC must still be supported by straps every 300 mm (12 in.) regardless of the framing openings
  2. B Framing openings never qualify as support; a separate strap is always required
  3. C The openings must be spaced not greater than 1.4 m (4½ ft) apart
  4. D The openings must be spaced not greater than 900 mm (3 ft) apart
Show answer & explanation

Correct: C — The openings must be spaced not greater than 1.4 m (4½ ft) apart

Per 348.30(B), horizontal FMC runs supported by openings through framing members at intervals not greater than 1.4 m (4½ ft) are permitted, provided the FMC is still securely fastened within 300 mm (12 in.) of termination points. The 900 mm figure is a flexibility-tail length from 348.30(A), not the framing-opening interval, and framing openings do qualify as support so a separate strap every 12 in. is not required.

Bending FMC: radius and cumulative limits

NEC 348.24

FMC bends can't damage the raceway or pinch its inside diameter, and a run can't have more than 360° of total bend between pull points.

Q2 NEC 348.24

An electrician is installing a long FMC run with several changes of direction between two pull points. What is the maximum total bend allowed for this run per 348.24(B)?

  1. A There is no limit as long as a fish tape can still pass
  2. B 270 degrees
  3. C 360 degrees
  4. D 180 degrees
Show answer & explanation

Correct: C — 360 degrees

348.24(B) limits the total degrees of bends in a conduit run to 360 degrees between pull points, the same cumulative-bend limit used for other raceway types. 270 and 180 degrees are lower thresholds sometimes confused with other installation limits, and there is in fact a hard numeric cap, not a pull-test standard.

Grounding and bonding requirements for FMC

NEC 348.60

FMC can serve as the equipment grounding conductor only in a fixed installation with no flexibility needed after install — anywhere vibration or movement is a factor, run a separate EGC.

Q3 NEC 348.60

FMC is installed to connect a motor where flexibility is needed after installation to allow for movement. What does 348.60 require?

  1. A No equipment grounding conductor is required if the run is under 6 ft
  2. B The FMC jacket alone may serve as the equipment grounding conductor
  3. C A separate equipment grounding conductor is only needed if the FMC exceeds 6 ft
  4. D A separate equipment grounding conductor must be installed
Show answer & explanation

Correct: D — A separate equipment grounding conductor must be installed

Per 348.60(B), where flexibility is necessary after installation (such as to allow equipment movement), an equipment grounding conductor must be installed — the FMC itself cannot be relied on as the ground path. Using the FMC jacket alone applies only to fixed installations under 250.118(A)(5). The 6 ft references describe the separate bonding jumper length allowance elsewhere in Article 250, not an exception to this requirement.

Where FMC is prohibited

NEC 348.12

FMC is banned wet, buried, classified, physically exposed, or anywhere it can corrode or get crushed.

Q4 NEC 348.12 Code lookup

A contractor wants to route FMC through a below-grade duct bank, embedding it directly in poured concrete to reach a pull point. Which section addresses whether this installation method is permitted?

  1. A 348.42
  2. B 348.12
  3. C 348.10
  4. D 348.30
Show answer & explanation

Correct: B — 348.12

348.12(6) specifically prohibits FMC underground or embedded in poured concrete or aggregate. 348.10 lists where FMC IS permitted (the mirror-image section), and 348.42/348.30 cover couplings/connectors and securing/supporting, not permitted uses.

Conductor fill count for FMC

NEC 348.22

FMC conductor fill follows Chapter 9, Table 1 percentage rules, except metric designator 12 (trade size 3/8) which uses the fixed conductor count in Table 348.22.

Q5 NEC 348.22

An electrician is sizing conductor fill for a run of 1-inch trade size flexible metal conduit (FMC). Which method applies?

  1. A The 40% fill rule for conduit nipples
  2. B Fixed conductor count from Table 348.22
  3. C Ampacity adjustment factors from Table 310.15(C)(1)
  4. D Percentage fill from Table 1, Chapter 9
Show answer & explanation

Correct: D — Percentage fill from Table 1, Chapter 9

348.22 requires standard trade sizes of FMC to use the percentage fill in Table 1, Chapter 9. Only metric designator 12 (trade size 3/8) uses the fixed count in Table 348.22. The nipple fill rule and ampacity adjustment tables address different questions entirely.

FMC minimum and maximum trade size

NEC 348.20

Flexible metal conduit runs from metric designator 16 (trade size 3/8) up to metric designator 103 (trade size 4), with narrow exceptions allowing smaller sizes.

Q6 NEC 348.20 Code lookup

A contractor wants to run FMC to enclose the leads of a motor, using a size smaller than metric designator 16 (trade size 3/8). Which section lists the specific exceptions that permit undersized FMC in cases like this?

  1. A 348.22
  2. B 348.20(B)
  3. C 348.12
  4. D 348.20(A)
Show answer & explanation

Correct: D — 348.20(A)

348.20(A) lists the five permitted exceptions (including motor lead enclosures per 430.245(B)) allowing FMC smaller than metric designator 16. 348.20(B) instead sets the maximum size limit, and 348.12/348.22 don't address minimum trade size at all.

Securing and supporting LFMC runs

NEC 350.30

LFMC needs a fastener within 12 in. of every termination and support every 4½ ft, unless one of the flexibility exceptions applies.

Q7 NEC 350.30

An electrician is installing a straight run of LFMC with no flexibility requirements after installation. What is the maximum interval allowed between supports?

  1. A 1.4 m (4½ ft)
  2. B 900 mm (3 ft)
  3. C 1.8 m (6 ft)
  4. D 300 mm (12 in.)
Show answer & explanation

Correct: A — 1.4 m (4½ ft)

Per 350.30(A), LFMC must be supported and secured at intervals not exceeding 1.4 m (4½ ft). The 900 mm figure is the flexibility-exception limit for smaller trade sizes, 1.8 m applies to luminaire taps and accessible-ceiling connections, and 300 mm is the fastening distance from terminations, not the support interval.

Equipment grounding and bonding with LFMC

NEC 350.60

LFMC can serve as the equipment grounding conductor only in fixed installations; if the equipment needs to flex or vibrate after install, you must run a separate EGC.

Q8 NEC 350.60

An LFMC run connects to a motor that requires flexibility after installation to allow for movement. What does 350.60(B) require?

  1. A The LFMC jacket alone may serve as the equipment grounding conductor
  2. B A bonding jumper sized per 250.102 may substitute for the EGC in all cases
  3. C No equipment grounding conductor is required if the run is under 6 ft
  4. D A separate equipment grounding conductor must be installed
Show answer & explanation

Correct: D — A separate equipment grounding conductor must be installed

Per 350.60(B), where flexibility is necessary to minimize vibration transmission or allow equipment movement after installation, an equipment grounding conductor shall be installed. Relying on the LFMC jacket alone is only permitted for fixed installations under 350.60(A), and the 6 ft length rule relates to flexible connection permissions elsewhere, not to omitting the EGC here.

LFMC minimum and maximum trade size

NEC 350.20

LFMC runs from metric designator 16 (trade size 1/2) up to metric designator 103 (trade size 4), with a narrow 3/8 exception tied back to 348.20(A).

Q9 NEC 350.20

Under normal conditions, what is the smallest trade size of LFMC permitted for a new installation?

  1. A Trade size 1
  2. B Trade size 1/2
  3. C Trade size 3/4
  4. D Trade size 3/8
Show answer & explanation

Correct: B — Trade size 1/2

350.20(A) sets the general minimum at metric designator 16 (trade size 1/2). Trade size 3/8 is smaller and only permitted under the limited conditions referenced in 348.20(A), not as the default minimum.

Bend radius and bend limits for LFMC

NEC 350.24

LFMC bends must follow Table 2, Chapter 9 minimum radii and can't exceed 360 total degrees between pull points.

Q10 NEC 350.24

What is the maximum total number of degrees of bends permitted in an LFMC run between pull points?

  1. A 180 degrees
  2. B 360 degrees
  3. C 720 degrees
  4. D 270 degrees
Show answer & explanation

Correct: B — 360 degrees

Per 350.24(B), the total degrees of bends in a conduit run cannot exceed 360 degrees between pull points. The other values are not recognized thresholds under this section.

Conductor and cable fill in LFMC

NEC 350.22

Trade size 3/8 LFMC uses the fixed conductor counts in Table 348.22, while trade sizes 1/2 and up use the percentage fill in Chapter 9, Table 1.

Q11 NEC 350.22 Code lookup

An installer is pulling four 10 AWG THHN conductors into a run of 3/4 in. (metric designator 21) liquidtight flexible metal conduit. Which section establishes the percentage fill limit that governs how many conductors can be pulled into this raceway?

  1. A 350.20(B)
  2. B 350.22(B)
  3. C 350.22(A)
  4. D 350.24(B)
Show answer & explanation

Correct: C — 350.22(A)

350.22(A) covers metric designators 16 through 103 (trade sizes 1/2 through 4) and directs fill to Table 1, Chapter 9. 350.22(B) only applies to the smaller 3/8 in. (metric designator 12) size, which uses Table 348.22 instead; 350.20(B) sets maximum trade size, not fill.

Fittings, couplings, and connectors for LFMC

NEC 350.42

Only listed LFMC fittings are allowed, angle connectors must stay accessible, and direct burial needs fittings marked for that use.

Q12 NEC 350.42

An electrician wants to install an angle connector on a run of LFMC inside a finished wall cavity, where it would not be accessible after drywall is installed. Is this permitted?

  1. A Yes, as long as the LFMC is direct-burial marked
  2. B Yes, as long as the connector is listed for use with LFMC
  3. C No, LFMC fittings can never be installed inside wall cavities
  4. D No, angle connectors are not permitted to be concealed
Show answer & explanation

Correct: D — No, angle connectors are not permitted to be concealed

Per 350.42, angle connectors shall not be concealed, regardless of whether the fitting is listed for LFMC. Being listed for LFMC is a separate requirement and doesn't override the concealment prohibition. Direct-burial marking applies to straight fittings for earth burial, not to concealment in a wall. LFMC fittings in general are not banned from wall cavities — only angle connectors are restricted from being concealed.

What PVC Conduit Can (and Can't) Support

NEC 352.10(I)

PVC conduit may support only small nonmetallic conduit bodies holding splices — never luminaires or other equipment.

Q13 NEC 352.10(I)

Per 352.10(I), what may a nonmetallic conduit body supported solely by PVC conduit contain?

  1. A Splicing devices only, as permitted by 110.14(B) and 314.16(C)(2)
  2. B A dimmer or other control device
  3. C Any device rated for the conduit body's trade size
  4. D A snap switch controlling a single luminaire
Show answer & explanation

Correct: A — Splicing devices only, as permitted by 110.14(B) and 314.16(C)(2)

352.10(I) permits a PVC-supported conduit body to contain only splicing devices allowed by 110.14(B) and 314.16(C)(2). A snap switch or dimmer isn't a splicing device, and being rated for the trade size doesn't override that restriction.

Expansion Fittings for PVC Thermal Movement (Including Underground Runs)

NEC 352.44(A)

PVC conduit needs an expansion fitting whenever a straight run's calculated thermal length change reaches 1/4 in., using Table 352.44(A).

Q14 NEC 352.44(A)

A long straight run of PVC rigid nonmetallic conduit is installed between two securely mounted cabinets outdoors, where it will see a wide temperature swing. When must an expansion fitting be installed in this run?

  1. A Only if the conduit is also exposed to direct sunlight
  2. B Whenever the calculated thermal length change is 6 mm (1/4 in.) or greater
  3. C Only if the run exceeds 100 ft between terminations
  4. D Only if the conduit is larger than 2 in. trade size
Show answer & explanation

Correct: B — Whenever the calculated thermal length change is 6 mm (1/4 in.) or greater

352.44(A) sets the trigger as expected length change of 6 mm (1/4 in.) or greater between securely mounted terminations, based on Table 352.44(A) — not sunlight exposure, a fixed run length, or trade size.

PVC conduit marking requirements

NEC 352.120

PVC conduit must be durably marked at least every 3 m (10 ft), with permanence required for aboveground types and legibility-until-installed for underground-only types.

Q15 NEC 352.120

Per 352.120, at what minimum interval must each length of PVC conduit be clearly and durably marked?

  1. A At least every 1.5 m (5 ft)
  2. B Once per length, at either end
  3. C At least every 3 m (10 ft)
  4. D At least every 6 m (20 ft)
Show answer & explanation

Correct: C — At least every 3 m (10 ft)

352.120 requires marking at least every 3 m (10 ft), consistent with 110.21(A). The 5 ft, 20 ft, and once-per-length options don't match the stated interval.

PVC conduit material requirements

NEC 352.100

PVC conduit is rigid, nonplasticized polyvinyl chloride, and the specific properties it must resist depend on whether it's installed aboveground or underground.

Q16 NEC 352.100

Which property is specifically required for PVC conduit used aboveground but is NOT listed as a separate requirement for underground PVC conduit under 352.100?

  1. A Sufficient strength to resist impact and crushing
  2. B Resistance to sunlight effects
  3. C Resistance to moisture
  4. D Resistance to corrosive agents
Show answer & explanation

Correct: B — Resistance to sunlight effects

352.100 lists flame retardance plus resistance to impact/crushing, heat distortion, low temperature, and sunlight as aboveground-specific requirements. Sunlight resistance only appears in the aboveground list. Moisture resistance applies to both, impact/crushing strength is required underground too (for handling and installation abuse), and corrosive-agent resistance is an underground-specific requirement, not an aboveground one.

PVC Permitted in Concealed, Encased, Corrosive, Cinder, Dry/Damp & Exposed Locations

NEC 352.10(A)

PVC conduit is allowed concealed in walls/floors/ceilings, encased in concrete, in cinder fill, corrosive areas, dry/damp locations, and exposed — a broad general-use raceway.

Q17 NEC 352.10(A)

A raceway will be installed in an area with severe corrosive influences. What must be true for PVC conduit to be permitted there?

  1. A PVC is never permitted in any location with corrosive influences
  2. B Any standard PVC conduit may be used regardless of the chemical present
  3. C The PVC material must be specifically approved for the chemicals present
  4. D Only metallic conduit may be used, per 352.10(C)
Show answer & explanation

Correct: C — The PVC material must be specifically approved for the chemicals present

352.10(C) permits PVC in severely corrosive locations per 300.6, but only where the material is specifically approved for the chemicals involved — not just any PVC, and it isn't blanket-prohibited or blanket-approved.

PVC Not Permitted — Hazardous Locations, High Ambient Heat, Theaters

NEC 352.12(A)

Rigid PVC conduit is banned in classified hazardous locations, in ambient heat over 50°C unless specially listed, and in theaters and similar assembly spaces except where 518.4 or 520.5 allow it.

Q18 NEC 352.12(A) Code lookup

A contractor wants to run rigid PVC conduit through a Class I, Division 1 spray-finishing booth area at an auto body shop. Which NEC section addresses whether PVC conduit is permitted in this classified area?

  1. A 352.10(C)
  2. B 352.12(A)
  3. C 352.12(D)
  4. D 352.12(E)
Show answer & explanation

Correct: B — 352.12(A)

352.12(A) prohibits PVC conduit in hazardous (classified) locations except as permitted elsewhere in the Code. 352.12(D) governs excessive ambient heat and 352.12(E) governs theaters — neither addresses classified locations, and 352.10(C) only covers corrosive influences for permitted uses.

Bending PVC Conduit — Technique and 360° Limit

NEC 352.24(A)

Field bends need identified bending equipment and the right radius, and a run can't exceed 360° of total bend between pull points.

Q19 NEC 352.24(A)

An electrician is field-bending a run of PVC conduit that already has two 90-degree bends between pull points. What is the maximum additional bend allowed in that run before a pull point is required?

  1. A 90 degrees
  2. B 180 degrees
  3. C 270 degrees
  4. D No additional bend is allowed
Show answer & explanation

Correct: B — 180 degrees

Section 352.24(B) caps total bends at 360 degrees between pull points. Two 90-degree bends already used 180 degrees, leaving 180 degrees before another pull point is needed. 90 degrees and 270 degrees misjudge the remaining allowance, and bending is still permitted since the 360-degree cap hasn't been reached.

Bushings Required at PVC Conduit Entries

NEC 352.46

Every PVC conduit entry into a box or enclosure needs a bushing or adapter to protect conductors from abrasion, unless the fitting itself already does that job.

Q20 NEC 352.46 Code lookup

A 3/4 in. rigid PVC conduit stubs up into a metal panelboard enclosure through a standard knockout, and the enclosure opening has no integral smooth-edge protection built in. Which section requires that a bushing or adapter be installed at this entry to protect the conductors from abrasion?

  1. A 352.28
  2. B 352.24
  3. C 352.46
  4. D 352.48
Show answer & explanation

Correct: C — 352.46

352.46 is the section requiring a bushing or adapter at any box, fitting, or enclosure entry unless the enclosure's design already gives equivalent protection. 352.48 (Joints) covers joining conduit lengths, 352.28 (Trimming) covers deburring cut ends, and 352.24 (Bends) governs how bends are made and how many are allowed per run — none of these address protecting conductors at an enclosure entry.

Conductor Temperature Rating vs. PVC Conduit Temperature Rating

NEC 352.10(J)

You can pull higher-temperature-rated conductors into PVC conduit, but you can never actually operate them above the conduit's own temperature rating.

Q21 NEC 352.10(J) Code lookup

A contractor wants to pull 90°C-rated THHN conductors through a run of rigid PVC conduit, but plans to load the circuit so the conductors actually operate above the conduit's listed temperature rating. Which section governs whether this installation is acceptable?

  1. A 352.22
  2. B 352.12(D)
  3. C 352.10(J)
  4. D 352.6
Show answer & explanation

Correct: C — 352.10(J)

352.10(J) is the specific rule allowing higher-temperature-rated conductors in PVC as long as actual operating temperature doesn't exceed the conduit's listed rating. 352.12(D) addresses ambient temperature limits for where PVC itself may be used (an installation-location restriction), not the conductor-vs-conduit operating temperature relationship, so it doesn't answer this scenario.

Equipment Grounding Conductor Requirements in PVC Conduit

NEC 352.60

PVC conduit can't act as the equipment ground, so a separate equipment grounding conductor must be pulled inside it whenever grounding is required.

Q22 NEC 352.60

A branch circuit runs entirely in rigid PVC conduit and equipment grounding is required. What must the installation include?

  1. A A separate equipment grounding conductor installed in the conduit
  2. B A bonding jumper sized to the conduit's trade size
  3. C No additional grounding means, since PVC is nonconductive and self-insulating
  4. D Metallic bushings bonded at each end of the conduit run
Show answer & explanation

Correct: A — A separate equipment grounding conductor installed in the conduit

Per 352.60, because PVC conduit cannot serve as an equipment grounding path, a separate equipment grounding conductor shall be installed in the conduit where equipment grounding is required. Bonding jumpers and metallic bushings address raceway continuity for metal systems, not PVC, and 'no grounding means' is incorrect since 352.60 mandates one absent a 250.142 exception.

Bending HDPE conduit

NEC 353.24

HDPE conduit bends can be made by hand as long as the internal diameter isn't reduced, and a run can't exceed 360° total between pull points.

Q23 NEC 353.24

An installer is hand-bending a run of HDPE conduit with several bends between two pull points. What is the maximum total bend allowed for that run?

  1. A No limit, as long as a pulling lubricant is used
  2. B 360 degrees total between pull points
  3. C 180 degrees total between pull points
  4. D 360 degrees per individual bend
Show answer & explanation

Correct: B — 360 degrees total between pull points

353.24(B) caps the total degrees of bend in a run at 360 degrees between pull points, not per individual bend. The 180-degree figure and the 'no limit' option are both incorrect thresholds; 360.24(B) doesn't reference lubricant as a workaround.

Conductor and cable fill count

NEC 353.22

The number of conductors or cables in HDPE conduit is capped by the percentage fill in Table 1, Chapter 9 — not by guesswork.

Q24 NEC 353.22 Code lookup

An electrician is installing 12 THHN conductors inside a run of ENT (electrical nonmetallic tubing) on a job site. Which NEC section governs the maximum number of conductors permitted based on the required percentage fill?

  1. A 353.22
  2. B 353.20(B)
  3. C 353.24(B)
  4. D 353.6
Show answer & explanation

Correct: A — 353.22

353.22 sets conductor and cable fill by referencing Table 1, Chapter 9. 353.20(B) covers maximum trade size of the ENT itself, and 353.24(B) covers the number of bends allowed in one run — neither addresses conductor fill count.

HDPE conduit material and marking requirements

NEC 353.100

HDPE conduit must be tough enough for burial and abuse, and marked every 3 m (10 ft) with maker and material type.

Q25 NEC 353.100

Per 353.100, what additional property must HDPE conduit have if it will be direct buried without concrete encasement?

  1. A Capability of withstanding continued loading likely to be encountered after installation
  2. B Resistance to ultraviolet degradation
  3. C Factory-installed corrosion-resistant coating
  4. D A minimum wall thickness of 3 mm
Show answer & explanation

Correct: A — Capability of withstanding continued loading likely to be encountered after installation

353.100 requires HDPE intended for direct burial without concrete encasement to withstand continued loading likely to be encountered after installation. UV resistance, a specific wall thickness, and a factory coating are not requirements stated in this section.

Grounding conductor requirements

NEC 353.60

Type HDPE conduit is nonmetallic, so a separate equipment grounding conductor must run in the conduit — with two narrow exceptions.

Q26 NEC 353.60 Code lookup

A raceway installation requires an equipment grounding conductor to be installed. Which section specifies where in the conduit this grounding conductor must be run and when a separate conductor is not required?

  1. A 353.48
  2. B 353.56
  3. C 353.20
  4. D 353.60
Show answer & explanation

Correct: D — 353.60

353.60 covers grounding requirements for this raceway type, including when the equipment grounding conductor must be installed in the conduit and the exceptions tied to 250.134 and 250.142. 353.56 addresses splices and taps, not grounding, so it wouldn't be the section a student needs for this scenario.

Joining HDPE conduit lengths

NEC 353.48

HDPE conduit joints must be made by heat fusion, electrofusion, or mechanical fittings — no solvent cement.

Q27 NEC 353.48 Code lookup

An installer is fusing together two 10-ft lengths of HDPE conduit on a directional-bore job and wants to confirm which methods are approved for making up the joint. Which section governs joints between lengths of HDPE conduit?

  1. A 353.56
  2. B 353.48
  3. C 353.6
  4. D 353.24(A)
Show answer & explanation

Correct: B — 353.48

353.48 specifically addresses how joints between conduit lengths (and to couplings, fittings, and boxes) must be made, including heat fusion, electrofusion, or mechanical fittings for HDPE. 353.24(A) instead covers how bends are made, and 353.56 covers splices and taps of conductors, not conduit joints.

NUCC construction: assembly form, material, and conductor requirements

NEC 354.100

NUCC ships as a continuous coiled assembly of listed, corrosion-resistant conduit with listed conductors already inside, sized per 310.10(C).

Q28 NEC 354.100

Per 354.100(A), how is NUCC provided as an assembly?

  1. A Pre-cut to standard trade lengths matching rigid metal conduit
  2. B Only as a custom-length assembly built to order for each job
  3. C In 10 ft rigid sticks bundled for pallet shipping
  4. D In continuous lengths shipped in a coil, reel, or carton
Show answer & explanation

Correct: D — In continuous lengths shipped in a coil, reel, or carton

354.100(A) states NUCC is an assembly provided in continuous lengths shipped in a coil, reel, or carton — not pre-cut rigid sticks or a custom-built assembly. This distinguishes NUCC from rigid raceway products sold in fixed trade lengths.

NUCC marking and identification requirements

NEC 354.120

NUCC must be durably marked every 10 ft with the conduit material, and every conductor/cable assembly inside needs a tag at both ends or on the reel.

Q29 NEC 354.120

Per 354.120, at what maximum interval must NUCC be durably marked?

  1. A Every 3.05 m (10 ft)
  2. B Every 6.1 m (20 ft)
  3. C Only at each end of the run
  4. D Every 1.83 m (6 ft)
Show answer & explanation

Correct: A — Every 3.05 m (10 ft)

354.120 requires NUCC to be clearly and durably marked at least every 3.05 m (10 ft) as required by 110.21. Marking only at each end, or at the 6 ft or 20 ft intervals used for other purposes elsewhere in the Code, doesn't meet this spacing requirement.

Where NUCC can and can't be used

NEC 354.10

NUCC is an underground and encased-in-concrete product only — it can't be exposed, run inside buildings, or land in hazardous locations.

Q30 NEC 354.10

Under what condition is NUCC permitted to be installed above ground?

  1. A When installed in free air with adequate clearance
  2. B When encased in not less than 2 in. (50 mm) of concrete
  3. C When strapped to a building wall in a raceway
  4. D When protected by a metal raceway sleeve
Show answer & explanation

Correct: B — When encased in not less than 2 in. (50 mm) of concrete

354.10(5) permits above-ground NUCC only where encased in not less than 50 mm (2 in.) of concrete. Strapping to a wall, running in free air, or sleeving in metal raceway are not the code-recognized above-ground method and would leave it exposed, which 354.12(1) prohibits.

Bending NUCC: radius and total degrees per run

NEC 354.24

Bend NUCC by hand without kinking or flattening it, keep the centerline radius at or above Table 354.24(A), and never exceed 360 degrees total between pull points.

Q31 NEC 354.24

A run of NUCC between two pull points has accumulated four 90-degree bends. Per 354.24(B), is a fifth 90-degree bend permitted in that same run?

  1. A Yes, as long as each individual bend has an approved centerline radius
  2. B No, because NUCC is limited to two bends per run regardless of degrees
  3. C No, because the run has already reached the 360-degree maximum
  4. D Yes, because the limit applies only between the conduit and its termination, not between pull points
Show answer & explanation

Correct: C — No, because the run has already reached the 360-degree maximum

354.24(B) caps total bends at 360 degrees between pull points. Four 90-degree bends already total 360 degrees, so no additional bend is allowed in that run. Meeting the minimum radius from 354.24(A) is a separate requirement and doesn't override the cumulative-degree limit.

Conductor fill limits for NUCC

NEC 354.22

The number of conductors allowed in NUCC is set by Table 1, Chapter 9's percentage-fill limits, not by any NUCC-specific rule.

Q32 NEC 354.22 Code lookup

A contractor is installing NUCC (Type NUCC nonmetallic underground conduit with conductors) and needs to determine how many current-carrying conductors can be pulled into a given trade size of the conduit. Which section governs the maximum fill count?

  1. A 354.20(B)
  2. B 354.24(B)
  3. C 354.22
  4. D 354.100(D)
Show answer & explanation

Correct: C — 354.22

354.22 sends the installer to Table 1 of Chapter 9 for percentage fill, which is the actual conductor-count limit. 354.20(B) only addresses the maximum trade size of the conduit itself, and 354.100(D) is a construction/product-standard requirement on the manufactured assembly's conductor fill, not a field fill-limit rule for conductor count.

Bending RTRC: radius, method, and total bend limit per run

NEC 355.24

Field bends in RTRC must use identified bending equipment, follow the Table 2, Chapter 9 radius, and never exceed 360° total between pull points.

Q33 NEC 355.24

A long RTRC run has two 90-degree sweeps and one 45-degree offset between pull points, with no pull boxes in between. Is this compliant with 355.24(B)?

  1. A Yes, but only if each individual bend is 90 degrees or less
  2. B No, because only a single bend is allowed per run regardless of degrees
  3. C Yes, because the total is 225 degrees, under the 360-degree limit
  4. D No, because RTRC runs cannot include offsets, only sweeps
Show answer & explanation

Correct: C — Yes, because the total is 225 degrees, under the 360-degree limit

355.24(B) caps the total degrees of bend in a run at 360 degrees between pull points, regardless of how many individual bends make up that total. Here 90 + 90 + 45 = 225 degrees, which is compliant. There's no rule limiting the run to a single bend, no per-bend degree cap, and offsets are ordinary bends, not a prohibited feature.

Securing and support spacing for RTRC runs

NEC 355.30

RTRC needs a fastener within 3 ft of every box or termination, plus supports along the run at the spacing in Table 355.30(B) unless the listing says otherwise.

Q34 NEC 355.30

An electrician is installing RTRC and needs to fasten it near a junction box. Per the general rule, how far from the box can the nearest fastening point be?

  1. A No more than 1.5 m (5 ft) from the box
  2. B No more than 1.8 m (6 ft) from the box
  3. C Fastening near boxes is not required if mid-run supports are used
  4. D No more than 900 mm (3 ft) from the box
Show answer & explanation

Correct: D — No more than 900 mm (3 ft) from the box

355.30(A) requires RTRC to be securely fastened within 900 mm (3 ft) of each outlet box, junction box, device box, conduit body, or other termination, unless the conduit is listed for a different distance. The 1.5 m and 1.8 m options and skipping fastening near boxes are not permitted under the general rule.

Where RTRC conduit is prohibited

NEC 355.12

RTRC is barred from hazardous locations (with narrow exceptions), luminaire support beyond 355.10(H), unprotected physical damage areas, over 50°C ambient, and most theater wiring.

Q35 NEC 355.12

An installer wants to run RTRC conduit in a Class I, Division 2 hazardous location. What does 355.12(A) say?

  1. A RTRC is permitted in any hazardous location as long as it is listed
  2. B RTRC is fully prohibited in all Class I, Division 2 locations with no exceptions
  3. C RTRC is prohibited except as permitted in 501.10(B)(1)(6)
  4. D RTRC is prohibited only in Class I, Division 1 locations, not Division 2
Show answer & explanation

Correct: C — RTRC is prohibited except as permitted in 501.10(B)(1)(6)

355.12(A)(2) prohibits RTRC in Class I, Division 2 locations except as permitted in 501.10(B)(1)(6) — a narrow carve-back, not a blanket allowance for any listed product. RTRC is also barred from hazardous locations generally under 355.12(A)(1), so the 'all hazardous locations, no exceptions' option and the 'only Division 1' option both misstate the rule.

Where RTRC conduit is permitted to be installed

NEC 355.10

RTRC is permitted concealed, in corrosive or wet locations, in cinder fill, exposed if identified, and underground — but each use has its own conditions.

Q36 NEC 355.10

RTRC is being installed to feed equipment in a laundry facility where the walls are washed down regularly. What does 355.10(D) require for this installation?

  1. A The conduit must be upgraded to Type XW for physical damage protection
  2. B Only the conduit itself needs to be watertight; boxes and fittings are exempt
  3. C RTRC is not permitted in wet locations and a metallic raceway must be used instead
  4. D The entire conduit system, including boxes and fittings, must be installed to keep water out, with corrosion-resistant supports and hardware
Show answer & explanation

Correct: D — The entire conduit system, including boxes and fittings, must be installed to keep water out, with corrosion-resistant supports and hardware

355.10(D) requires the entire conduit system — conduit, boxes, and fittings — to be installed and equipped to prevent water entry, with corrosion-resistant supports, bolts, straps, and screws. RTRC is explicitly permitted in wet locations, so ruling it out is wrong, and Type XW addresses physical damage, not wet-location sealing.

Bushing/adapter protection at RTRC terminations

NEC 355.46

Every RTRC entry into a box or enclosure needs a bushing or adapter to shield conductors from abrasion, unless the enclosure itself already protects them.

Q37 NEC 355.46 Code lookup

An RTRC (Schedule 80 fiberglass) conduit run terminates into a sheet metal junction box. The box's opening does not provide a smooth, rounded edge for the conductors. Which section requires a bushing or adapter at this termination to protect the conductors from abrasion?

  1. A 355.30(A)
  2. B 355.48
  3. C 355.46
  4. D 355.24(A)
Show answer & explanation

Correct: C — 355.46

355.46 requires a bushing or adapter where RTRC enters a box or enclosure unless the enclosure design already gives equivalent protection. 355.48 covers making up joints between conduit lengths, and 355.30(A) covers securing/fastening the raceway, neither of which addresses conductor abrasion at a termination.

Expansion fittings for thermal expansion in RTRC

NEC 355.44

Install expansion fittings in a straight RTRC run whenever the expected length change reaches 6 mm (1/4 in.) or more, per Table 355.44.

Q38 NEC 355.44

Under 355.44, what determines whether an expansion fitting is required in a straight run of RTRC conduit?

  1. A The run contains more than the maximum number of quarter bends
  2. B The run passes through more than one fire-rated wall
  3. C The expected length change from thermal expansion, per Table 355.44, is 6 mm (1/4 in.) or greater
  4. D The conduit trade size exceeds 2 in.
Show answer & explanation

Correct: C — The expected length change from thermal expansion, per Table 355.44, is 6 mm (1/4 in.) or greater

355.44 requires expansion fittings where the length change calculated from Table 355.44 is expected to be 6 mm (1/4 in.) or greater between securely mounted terminations. Trade size, fire-rated wall penetrations, and bend count are not the trigger described in this section.

Equipment grounding conductor requirements in RTRC

NEC 355.60

RTRC conduit is nonmetallic, so it never carries fault current itself — a separate equipment grounding conductor must run inside it whenever grounding is required.

Q39 NEC 355.60

A branch circuit is installed in RTRC conduit and equipment grounding is required. What must be done?

  1. A Grounding is not required if the RTRC is listed for the application
  2. B A metallic bushing at each end of the RTRC satisfies the grounding requirement
  3. C A separate equipment grounding conductor must be installed in the conduit
  4. D The RTRC conduit itself can serve as the equipment grounding conductor
Show answer & explanation

Correct: C — A separate equipment grounding conductor must be installed in the conduit

Per 355.60, where equipment grounding is required, a separate grounding conductor must be installed in the conduit — RTRC is nonmetallic and cannot itself provide an equipment ground, unlike metal raceways. A metallic bushing doesn't change that.

Securing and Supporting LFNC Runs

NEC 356.30

LFNC needs a fastener every 3 ft and within 12 in. of each box, but four common exceptions let you skip support entirely.

Q40 NEC 356.30

A run of LFNC longer than 6 ft is installed between two junction boxes. Per 356.30, how must it be fastened?

  1. A At intervals not exceeding 3 ft, with no fastening required near boxes since it's flexible
  2. B At intervals not exceeding 3 ft, and within 12 in. of each junction box
  3. C At intervals not exceeding 4.5 ft, with no requirement near boxes
  4. D Only within 12 in. of each junction box, with no interval requirement along the run
Show answer & explanation

Correct: B — At intervals not exceeding 3 ft, and within 12 in. of each junction box

356.30(1) requires LFNC runs over 6 ft to be securely fastened at intervals not exceeding 3 ft AND within 12 in. of every outlet box, junction box, cabinet, or fitting — both conditions apply together, not one or the other.

LFNC Minimum and Maximum Trade Sizes

NEC 356.20

LFNC runs from metric designator 16 (trade size 1/2) up to metric designator 103 (trade size 4), with narrow exceptions letting metric designator 12 (trade size 3/8) down to that floor.

Q41 NEC 356.20

Under what condition can trade size 3/8 (metric designator 12) LFNC be used instead of the normal 1/2 in minimum?

  1. A Anywhere in a dwelling unit branch circuit run
  2. B As a 6 ft or shorter tap connection to a luminaire, as part of a listed assembly
  3. C In any length as long as it is supported every 3 ft
  4. D As feeder conduit for a motor control center
Show answer & explanation

Correct: B — As a 6 ft or shorter tap connection to a luminaire, as part of a listed assembly

356.20(A)(2) permits trade size 3/8 LFNC only for tap connections to luminaires (per 410.117(C)) or utilization equipment, limited to 1.8 m (6 ft), as part of a listed assembly. General branch-circuit runs, feeder use, and unlimited lengths are not covered by this exception.

Where LFNC Is Allowed to Be Used

NEC 356.10

LFNC is allowed exposed or concealed wherever flexibility or protection from liquids/vapors is needed, plus outdoor, direct-burial, and concrete-encased uses when listed and marked for it.

Q42 NEC 356.10 Code lookup

An installer wants to route LFNC directly into an underground trench without any additional raceway or encasement, relying only on the product's own listing to justify burial. Which section permits this use?

  1. A 356.10
  2. B 356.42
  3. C 356.30
  4. D 356.12
Show answer & explanation

Correct: A — 356.10

356.10(4) permits LFNC for direct burial where it is listed and marked for that purpose. 356.42 instead covers couplings and connectors, and would only become relevant if the installer were encasing the LFNC in concrete rather than burying it directly in earth.

Bending LFNC: Radius and Cumulative Degrees

NEC 356.24

LFNC bends must not damage the conduit or reduce its inside diameter, and no run can exceed 360 total degrees of bend between pull points.

Q43 NEC 356.24

An electrician is hand-bending a run of LFNC and wants to know the maximum total bend allowed between two pull points. What does 356.24(B) permit?

  1. A No limit, as long as the radius meets Table 2
  2. B 360 degrees total
  3. C 180 degrees total
  4. D 270 degrees total
Show answer & explanation

Correct: B — 360 degrees total

356.24(B) caps the total of all bends in one LFNC run at 360 degrees between pull points. Meeting the Table 2 bend radius is a separate requirement under 356.24(A) and doesn't remove the cumulative-degree limit, and the 180° and 270° figures aren't the code value.

Couplings, Connectors, and Burial Fittings for LFNC

NEC 356.42

Only listed LFNC fittings are allowed, angle connectors can't be used where concealed, and only straight fittings are rated for direct burial or encasement in concrete.

Q44 NEC 356.42

An installer plans to encase a run of LFNC in concrete. Which fitting type may be used at the joint?

  1. A Either a straight or angle connector, since both are listed for LFNC
  2. B Any general-purpose angle connector rated for wet locations
  3. C A straight LFNC fitting listed for the raceway
  4. D An angle connector listed for LFNC
Show answer & explanation

Correct: C — A straight LFNC fitting listed for the raceway

356.42 permits only straight LFNC fittings for direct burial or encasement in concrete. Angle connectors, even if listed for LFNC and rated for wet locations, are not permitted for this use — that rating doesn't extend to burial or concrete encasement.

Grounding Requirements for LFNC Installations

NEC 356.60

LFNC doesn't count as an equipment ground — you must run a separate equipment grounding conductor inside it whenever grounding is required.

Q45 NEC 356.60

An electrician installs LFNC for a branch circuit that requires equipment grounding. What must be done per 356.60?

  1. A Rely on the LFNC's metallic-looking jacket as the grounding path
  2. B Bond the LFNC to a driven ground rod at each box
  3. C Omit grounding since LFNC is a nonmetallic raceway
  4. D Install a separate equipment grounding conductor in the conduit
Show answer & explanation

Correct: D — Install a separate equipment grounding conductor in the conduit

356.60 requires a separate equipment grounding conductor installed in the conduit whenever equipment grounding is required, because LFNC itself is not recognized as an equipment grounding path. Relying on the jacket, bonding to a ground rod, or skipping grounding entirely are not permitted substitutes.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access