Shielding removal, stress cones, and bending radius for MV cables
NEC 305.10 Cut back shielding needs a stress cone at every termination, and shielded MV cable can't bend tighter than 12 times its overall diameter.
Q1 NEC 305.10
At a termination where factory-applied shielding on an MV cable is cut back, what does the NEC require?
- A Re-application of factory shielding over the terminated end
- B A minimum 3 in. air gap between shield end and termination lug
- C A stress reduction means
- D An additional layer of semiconducting tape only, with no other device
Show answer & explanation
Correct: C — A stress reduction means
305.10 requires stress reduction means (such as a stress cone) at all terminations of factory-applied shielding to control the electrical stress created where the shield ends. Re-wrapping the cut end in tape or leaving an air gap doesn't address that stress concentration and isn't the code's requirement.
General underground conductor identification and cover-depth requirements
NEC 305.15(A) Direct-buried conductors must be listed for the job and installed per one of three methods, all meeting the cover depths in Table 305.15(A).
Q2 NEC 305.15(A) Code lookup
A contractor is direct-burying single-conductor cable and needs to know the minimum cover depth required based on wiring method and location. Which section provides the table for this?
- A 305.15(E)
- B 305.15(C)
- C 305.15(B)
- D 305.15(A)
Show answer & explanation
Correct: D — 305.15(A)
Table 305.15(A), Minimum Cover Requirements, is located at 305.15(A) and governs burial depth. 305.15(B) covers wet-location conductor use, not cover depth, and 305.15(C) addresses physical damage protection rather than burial depth.
Protecting underground conductors where they emerge from the ground
NEC 305.15(C) Wherever underground conductors come up out of the ground, they need a listed raceway from below grade up to 8 ft above grade (on poles) or to the point of entry (into a building).
Q3 NEC 305.15(C)
Underground conductors run up the side of a wood pole to feed a floodlight. Per 305.15(C), how far above finished grade must the protective raceway extend?
- A 1.5 m (5 ft) above finished grade
- B 2.5 m (8 ft) above finished grade
- C 3.0 m (10 ft) above finished grade
- D 1.8 m (6 ft) above finished grade
Show answer & explanation
Correct: B — 2.5 m (8 ft) above finished grade
305.15(C) requires pole-mounted raceway to extend from the minimum cover depth in Table 305.15(A) up to 2.5 m (8 ft) above finished grade. The shorter heights are common confusions with other clearance rules but don't match this section's stated distance.
Keeping over-1000V conductors separate from lower-voltage circuits
NEC 305.4 Conductors over 1000V ac / 1500V dc can't share an enclosure, cable, or raceway with conductors at or below that threshold unless a specific exception applies.
Q4 NEC 305.4 Code lookup
A job has a 4160V feeder and a 480V control circuit that need to land in the same manhole. The electrician wants to know under what condition conductors of these two systems can share the space without separate enclosures, which section covers this?
- A 305.4
- B 305.6
- C 305.15(A)(2)
- D 305.11
Show answer & explanation
Correct: A — 305.4
305.4 lists the specific exceptions permitting different voltage systems to share an enclosure, including item (4) covering manholes where conductors are permanently separated and secured to supports. 305.15(A)(2) instead addresses industrial establishment cable assembly requirements for underground installations, not enclosure-sharing rules.
Direct-burial splicing and shield continuity requirements
NEC 305.15(D) Direct-buried cables can be spliced without a box if watertight and mechanically protected, and shield continuity must be maintained or, in engineered systems, each interrupted shield section grounded at one point.
Q5 NEC 305.15(D)
An electrician wants to splice a direct-buried medium-voltage cable underground. Per 305.15(D), what is required?
- A Suitable materials with a watertight, mechanically protected splice
- B The splice must be located above grade for inspection access
- C A listed underground splice box enclosing the joint
- D A concrete-encased duct bank around the splice point
Show answer & explanation
Correct: A — Suitable materials with a watertight, mechanically protected splice
305.15(D) permits direct-buried cables to be spliced or tapped without a splice box, provided suitable materials are used and the splice is watertight and protected from mechanical damage. A splice box, above-grade location, or duct encasement is not the code requirement here.
Wet-location listing for underground enclosures and raceways
NEC 305.15(B) Any enclosure or raceway run underground is a wet location inside, no matter how dry the soil looks — conductors, cables, connections, and splices must all be listed for wet locations.
Q6 NEC 305.15(B) Code lookup
A crew is running underground PVC conduit from a pad-mounted transformer to a building, with conductor splices made in a below-grade handhole. Which section specifies that the interior of the underground raceway is considered a wet location, requiring the conductors and any splices to be listed for wet locations?
- A 305.15(C)
- B 305.15(B)
- C 305.8
- D 305.15(D)
Show answer & explanation
Correct: B — 305.15(B)
305.15(B) is the rule that classifies the interior of underground enclosures and raceways as a wet location and sets the wet-location listing requirement for conductors, cables, and splices. 305.15(D) only covers splice methods/materials, not the wet-location classification itself, and 305.8 addresses raceways in wet locations above grade, not underground.
Raceways and cables in wet locations above grade
NEC 305.8 Any raceway installed in a wet location above grade is treated as a wet location inside, so conductors must be moisture-impervious metal-sheathed or listed for wet locations.
Q7 NEC 305.8 Code lookup
An installer runs EMT above grade on the exterior of a building where it will be exposed to rain, and pulls THHN conductors (not wet-rated) through it. Which section addresses whether the raceway interior counts as a wet location and what conductor type is required?
- A 305.15(B)
- B 305.9
- C 305.8
- D 305.11
Show answer & explanation
Correct: C — 305.8
305.8 states that raceways installed in wet locations above grade have interiors considered wet locations, requiring moisture-impervious metal-sheathed conductors or conductors listed for wet locations. 305.11 addresses moisture/mechanical protection specifically for metal-sheathed cables, not general raceway wiring, and 305.15(B) covers wet locations for underground installations, not above grade.
Wire-bending space at terminals, incl. opposite-wall entry
NEC 312.6(B) A conductor entering or leaving an enclosure through the wall opposite its terminal needs the larger Table 312.6(B)(2) spacing, not Table 312.6(A), unless a specific exception applies.
Q8 NEC 312.6(B) Code lookup
A panelboard has 500 kcmil feeder conductors that terminate at lugs on the wall of an enclosure, but the conductors actually enter the cabinet through the wall directly opposite those terminals. Which section tells you the minimum wire-bending space required at the terminals for this arrangement?
- A 312.6(A)
- B 312.6(B)(1)
- C 312.6(B)(2)
- D 312.6(C)
Show answer & explanation
Correct: C — 312.6(B)(2)
312.6(B)(2) governs wire-bending space when a conductor enters or leaves the enclosure through the wall opposite its terminal, directing the installer to Table 312.6(B)(2). 312.6(B)(1) instead applies Table 312.6(A) only when the conductor does NOT enter/leave opposite its terminal, so it doesn't fit this scenario.
Feed-through conductors, splices, and taps in switch/OCPD enclosures
NEC 312.8(A) In a switch or overcurrent device enclosure, feed-through conductors are allowed only if fill stays under 40% (conductors alone) and 75% (conductors plus splices and taps), with proper bending space and a warning label.
Q9 NEC 312.8(A)
An electrician wants to run feed-through conductors, with no splices, across the wiring space of a panelboard enclosure. What is the maximum allowable fill at any cross section?
- A 60 percent of the cross-sectional area
- B 40 percent of the cross-sectional area
- C 75 percent of the cross-sectional area
- D There is no fill limit as long as a warning label is applied
Show answer & explanation
Correct: B — 40 percent of the cross-sectional area
Per 312.8(A)(1), conductors alone at any cross section of the wiring space are limited to 40 percent fill. The 75 percent figure applies only when splices and taps are included with the conductors under 312.8(A)(2); a label alone does not remove the fill limit.
General wire spacing requirements inside cabinets
NEC 312.101(A) Cabinets and cutout boxes need minimum airspace around devices: 1/16 in. at the base, 1 in. at the door (1/2 in. if the door is lined or thick metal), and 1/2 in. to 1 in. around live parts depending on voltage.
Q10 NEC 312.101(A)
A panel operates at 480V nominal and does not meet the door-lining exception referenced in 312.101(A)(2). Per 312.101(A)(3), what airspace is required between live parts and the cabinet walls or door?
- A 0.0625 in.
- B No airspace requirement applies above 250V
- C 1.00 in.
- D 0.500 in., the same as for 250V or less
Show answer & explanation
Correct: C — 1.00 in.
312.101(A)(3) increases the live-part airspace to at least 1.00 in. for nominal voltages of 251 to 1000, compared to 0.500 in. at 250V or below. The 0.500 in. spacing only carries over to higher voltage (up to 600V) if the 312.101(A)(2) exception conditions are met, which this scenario rules out.
Cabinet and cutout box material requirements
NEC 312.100 Metal enclosures need corrosion protection inside and out, sheet steel must be at least 0.053 in. thick, and nonmetallic cabinets must be listed or pre-approved.
Q11 NEC 312.100
A manufacturer builds a cutout box from uncoated sheet steel. What is the minimum permitted metal thickness?
- A 0.79 mm (0.031 in.)
- B 1.35 mm (0.053 in.)
- C 2.0 mm (0.079 in.)
- D 1.6 mm (0.063 in.)
Show answer & explanation
Correct: B — 1.35 mm (0.053 in.)
312.100(B) sets the minimum uncoated sheet steel thickness at 1.35 mm (0.053 in.) to ensure ample strength and rigidity. The other values are not the code-specified threshold.
Securing cables and the surface-enclosure raceway exception
NEC 312.5(C) Cables must be secured to the enclosure, but nonmetallic-sheathed cable can reach a surface-mounted enclosure through a short, sealed nipple instead — only if all seven conditions in 312.5(C) are met.
Q12 NEC 312.5(C) Code lookup
A branch circuit is wired with NM cable that enters the top of a surface-mounted panelboard through a nonflexible raceway (nipple) that is 4 ft long, so the cable sheath can transition into the box. Which section lists the conditions that must all be met for this nonflexible-raceway nipple installation to be permitted?
- A 312.5(C)
- B 312.5(B)
- C 312.6(C)
- D 312.5(A)
Show answer & explanation
Correct: A — 312.5(C)
312.5(C) is the cable section that spells out the seven conditions permitting nonmetallic-sheathed cable to enter a surface-mounted enclosure through a short nonflexible raceway nipple. 312.5(A) covers closing unused openings and 312.5(B) covers metal cabinet installation generally — neither addresses the raceway-nipple exception, and 312.6(C) deals with bending space for 4 AWG and larger conductors, not cable entry method.
Cabinets and cutout boxes in damp or wet locations
NEC 312.2 Wet-location enclosures must be weatherproof, use wet-rated fittings above live parts, and sit on a 1/4-in. airspace unless nonmetallic on masonry.
Q13 NEC 312.2
A metallic cutout box is being surface-mounted on an exterior masonry wall in a wet location. What must the installer do regarding airspace?
- A Provide at least 6 mm (1/4 in.) of airspace between the box and the wall
- B Embed the box directly into the masonry with no gap
- C Skip the airspace requirement since the wall is masonry
- D Provide at least 25 mm (1 in.) of airspace between the box and the wall
Show answer & explanation
Correct: A — Provide at least 6 mm (1/4 in.) of airspace between the box and the wall
Per 312.2, surface enclosures in damp or wet locations need at least a 6-mm (1/4-in.) airspace off the mounting surface. The airspace exception for mounting directly on masonry, concrete, or tile applies only to nonmetallic enclosures, not metallic ones, so this metallic box still needs the airspace. There's no 25-mm threshold in this section.
Closing openings and bushing conductors entering enclosures
NEC 312.5(A) Every unused opening in a cabinet or cutout box must be closed, and metal enclosures fed by messenger, open, or knob-and-tube wiring need insulating bushings (or dry-location tubing) where conductors enter.
Q14 NEC 312.5(A) Code lookup
A metal cutout box on a job site has a knockout that was removed for a conduit run that was later abandoned, leaving the opening unused and exposed. Which section requires that this unused opening be closed in an approved manner?
- A 312.5(B)
- B 312.5(A)
- C 312.4
- D 312.7
Show answer & explanation
Correct: B — 312.5(A)
312.5(A) requires all openings through which conductors enter to be closed in an approved manner. 312.5(B) only addresses bushing requirements for messenger-supported, open, or knob-and-tube wiring entering metal enclosures, not general unused openings, and 312.4 covers repairing noncombustible surfaces after cabinet removal, not closing knockouts.
Field-installed screws and fasteners entering wiring spaces
NEC 312.10 Field-installed screws or fasteners entering a wiring space must be blunt-ended and can't project more than 6 mm into the enclosure unless protected or within 10 mm of a wall, where 11 mm is allowed.
Q15 NEC 312.10 Code lookup
An electrician is field-drilling and installing a self-tapping sheet metal screw through the side of a panelboard cabinet to mount an add-on accessory bracket, with the screw tip projecting into the wiring space. Which section specifies the requirements for field-installed fasteners that enter wiring spaces like this?
- A 312.10
- B 312.8
- C 312.6(A)
- D 312.5(A)
Show answer & explanation
Correct: A — 312.10
312.10 governs field-installed screws or other fasteners entering wiring spaces, requiring blunt ends and limiting penetration depth. 312.5(A) covers closing unused openings in cabinets, not fastener protrusion into wiring space, and 312.8 addresses usable space in switch and overcurrent device enclosures, not fastener design.
Power monitoring/energy management equipment sharing OCPD wiring space
NEC 312.8(B) Power monitoring or energy management gear can share a switch or OCPD enclosure's wiring space only if it's listed for that use, the space stays under 75% fill, and control conductors meet strict sizing and securing rules.
Q16 NEC 312.8(B)
An electrician wants to install an energy monitoring device inside the wiring space of a panelboard's overcurrent device enclosure. What must be true about the device per 312.8(B)?
- A It must be UL listed for general use only, with no enclosure-specific evaluation required
- B It must be installed by the panelboard manufacturer at the factory only
- C It must be identified as a field-installable accessory or a listed kit evaluated for that installation
- D It must be approved by the local AHJ on a case-by-case basis with no listing requirement
Show answer & explanation
Correct: C — It must be identified as a field-installable accessory or a listed kit evaluated for that installation
312.8(B)(1) requires the power monitoring or energy management equipment to be identified as a field-installable accessory of the listed equipment, or be a listed kit evaluated for field installation in that enclosure. General UL listing without enclosure-specific evaluation, factory-only installation, and AHJ discretion without a listing requirement are not what the rule specifies.
Determining AC cable ampacity, including insulation and tray derating
NEC 320.80 Type AC cable ampacity follows 310.14, but conductors buried in thermal insulation are capped at the 60°C column even though they must be rated 90°C.
Q17 NEC 320.80
Type AC cable is installed in contact with thermal insulation. The conductors are rated 90°C. What ampacity must be used?
- A The 90°C rated ampacity, since that's the required conductor rating
- B The 60°C rated ampacity, even though the conductors are 90°C rated
- C Whichever ampacity the installer selects, since 310.14 allows either
- D The 75°C rated ampacity as a compromise value
Show answer & explanation
Correct: B — The 60°C rated ampacity, even though the conductors are 90°C rated
Per 320.80(A), conductors in thermal insulation must be rated 90°C, but the ampacity used still cannot exceed that of a 60°C rated conductor. The 90°C rating is only usable for adjustment and correction calculations, not for picking a higher final ampacity — ruling out the 90°C option. There is no 75°C compromise or installer's choice under this section.
Securing and supporting AC cable runs
NEC 320.30 Type AC cable needs a strap, staple, or similar support within 12 in. of every box and every 4½ ft after that, unless it's fished, short, or feeding a ceiling fixture.
Q18 NEC 320.30
In general, at what maximum interval must Type AC cable be supported along its run?
- A 1.8 m (6 ft)
- B 600 mm (2 ft)
- C 300 mm (12 in.)
- D 1.4 m (4½ ft)
Show answer & explanation
Correct: D — 1.4 m (4½ ft)
320.30(C) requires Type AC cable to be supported at intervals not exceeding 1.4 m (4½ ft). The 300 mm figure is the securing distance from boxes under 320.30(B), not the general support interval, and the 1.8 m and 600 mm figures are the unsupported-length allowances under 320.30(D) for ceiling drops and flexible terminals, not general support spacing.
Protecting AC cable in accessible attics
NEC 320.23 AC cable crossing the top of framing near the attic access needs guard strips as tall as the cable; cable run parallel to framing members needs no protection at all.
Q19 NEC 320.23 Code lookup
An electrician is running Type AC cable across the top of ceiling joists in an accessible attic that has no permanent stairs or ladder to it, more than 6 ft from the scuttle hole opening. Which section determines whether guard strips are required at that location?
- A 320.23(B)
- B 320.17
- C 320.23(A)
- D 320.30(D)
Show answer & explanation
Correct: C — 320.23(A)
320.23(A) governs cable run across the top of framing members and limits the guard-strip requirement to within 6 ft of the scuttle hole when the attic is not accessible by permanent stairs or ladder — beyond that distance no guard strips are required. 320.23(B) instead covers cable run parallel to framing members, a different installation method with no guard-strip requirement.
Terminating AC cable at boxes and fittings
NEC 320.40 Every AC cable termination needs an anti-short bushing between conductors and armor, and it must stay visible for inspection.
Q20 NEC 320.40
An electrician terminates Type AC cable in a metal box using a standard cable connector. An inspector wants to verify the termination meets code. What must be visible without disturbing the installation?
- A The box fill calculation label
- B The number of current-carrying conductors in the cable
- C The cable's manufacturer marking
- D The insulating bushing between conductors and armor
Show answer & explanation
Correct: D — The insulating bushing between conductors and armor
320.40 requires the connector or clamp to be designed so the insulating bushing (anti-short bushing) is visible for inspection. Manufacturer markings, conductor counts, and box fill labels aren't inspection points under this section.
Where Type AC cable is prohibited
NEC 320.12 Type AC cable is barred from wet or damp locations, corrosive areas, damp masonry voids or plaster, and anywhere it faces physical damage.
Q21 NEC 320.12
Under 320.12, in which location is Type AC cable prohibited?
- A An accessible attic with headroom clearance
- B A damp or wet location
- C A dry, unfinished basement ceiling
- D Concealed within a dry wood-framed wall
Show answer & explanation
Correct: B — A damp or wet location
320.12(2) prohibits Type AC cable in damp or wet locations because its armor and internal paper wrap don't protect against moisture intrusion. Dry basements, dry framed walls, and accessible attics aren't damp or wet locations, so none of them trigger this prohibition.
Where Type AC cable can be used
NEC 320.10 Type AC cable is permitted for feeders, branch circuits, cable trays, and dry locations, plus embedded-in-plaster and fished-in-masonry-void installs — but never in damp or wet spots.
Q22 NEC 320.10
Under 320.10, which installation of Type AC cable is NOT permitted?
- A Installed in a cable tray
- B Embedded in plaster finish on brick in a wet location
- C Feeders in a concealed installation
- D Branch circuits in an exposed installation
Show answer & explanation
Correct: B — Embedded in plaster finish on brick in a wet location
320.10(4) permits AC cable embedded in plaster finish on brick or masonry, but specifically excepts damp or wet locations. Feeders and branch circuits (exposed or concealed) and cable tray installations are all listed as permitted uses under 320.10.
Type FC grounded conductor and terminal block color coding
NEC 322.120(B) Type FC's grounded conductor is white or gray for its full length, and terminal blocks add a fixed white-black-red-blue sequence from grounded to outermost section.
Q23 NEC 322.120(B)
On a terminal block identified for use with Type FC cable, which color marks the section immediately adjacent to the grounded conductor section?
- A Gray
- B Blue
- C Red
- D Black
Show answer & explanation
Correct: D — Black
Per 322.120(C), the terminal block sequence runs white (grounded conductor), then black for the next adjacent section, then red, then blue for the final outer section. Red and blue belong to later sections, and gray is not part of the terminal block sequence at all — it relates to conductor marking under 322.120(B), not terminal blocks.
Boxes, fittings, dead ends, hangers, and extensions for FCA
NEC 322.40 Every dead end, hanger, and fitting used with flat cable assembly must be identified for that use, and extensions leave the run only through junction boxes.
Q24 NEC 322.40
An installer needs to extend a flat cable assembly run into standard NM cable to reach a remote outlet. Where must this transition occur?
- A Only at the panelboard feeding the flat cable assembly
- B Inside the enclosing surface metal raceway itself, without a box
- C In a junction box installed at either end of the flat cable assembly run
- D Anywhere along the run, provided the splice is taped and supported
Show answer & explanation
Correct: C — In a junction box installed at either end of the flat cable assembly run
322.40(D) requires all extensions from flat cable assemblies to be made by approved wiring methods within junction boxes installed at either end of the FCA run — not mid-run splices, not at the panelboard, and not inside the raceway without a box.
Type FC flat cable assembly construction
NEC 322.100 Type FC flat cable assembly is built with 2 to 5 conductors, always 10 AWG special stranded copper.
Q25 NEC 322.100
Under 322.100, what is the maximum number of conductors permitted in a Type FC flat cable assembly?
- A Six
- B Five
- C Three
- D Four
Show answer & explanation
Correct: B — Five
322.100 limits Type FC flat cable assemblies to two, three, four, or five conductors — five is the maximum. Three and four are within the permitted range but not the maximum, and six exceeds it.
Splicing and tapping flat cable assembly conductors
NEC 322.56 Splices in flat cable assembly (Type FC) go only in listed junction boxes; taps use identified devices rated at least 15 A and not more than 300 volts to ground.
Q26 NEC 322.56
An electrician needs to splice two Type FC flat cable assembly conductors together. Where is this splice permitted?
- A Inside a tap device identified for the use
- B At any accessible point along the cable run, with tape insulation
- C At the panelboard terminal bar only
- D Inside a listed junction box
Show answer & explanation
Correct: D — Inside a listed junction box
322.56(A) requires that splices be made in listed junction boxes. Tap devices identified for the use are for taps, not splices (322.56(B)), and open-air taping or terminal-bar splicing isn't a listed junction box.
FCC Systems: Permitted Circuit Types, Voltage, and Current Limits
NEC 324.10(A) FCC (flat conductor cable) can serve general-purpose, appliance, or individual branch circuits, but voltage tops out at 300V/150V and current at 20A or 30A depending on circuit type.
Q27 NEC 324.10(A) Code lookup
An installer wants to run flat conductor cable (FCC) as a general-purpose branch circuit feeding several floor receptacle outlets in an open office. Which section confirms that FCC systems are permitted for general-purpose and appliance branch circuits?
- A 324.42
- B 324.12
- C 324.10(A)
- D 324.10(B)(2)
Show answer & explanation
Correct: C — 324.10(A)
324.10(A) is the specific provision stating FCC systems are permitted for general-purpose, appliance, and individual branch circuits; 324.10(B)(2) instead sets the ampere ratings for those circuits, and 324.12 covers uses NOT permitted.
Where FCC Can Be Installed: Floors, Walls, Damp Locations, Heat & Height
NEC 324.10(C) FCC goes on hard smooth floors or on walls inside surface metal raceway, is fine in damp locations, but needs heat-rated materials over 30°C floors and tapered edges above 0.090 in.
Q28 NEC 324.10(C)
An installer wants to run FCC up a wall to reach a workstation. Under what condition is this permitted?
- A Only when the FCC is enclosed in a surface metal raceway
- B Only in damp locations
- C Only when the wall surface is concrete or composition material
- D FCC is never permitted on walls under any condition
Show answer & explanation
Correct: A — Only when the FCC is enclosed in a surface metal raceway
Per 324.10(D), FCC on wall surfaces is permitted only inside surface metal raceways. The damp-location allowance in 324.10(E) is a separate permission that doesn't apply to wall mounting, and the hard/smooth/sound floor requirement in 324.10(C) applies to floors, not walls.
FCC Metal Shield System: Top/Bottom Shields and Shield Connectors
NEC 324.40(C) Flat Type FCC cable on a floor needs both a top and a bottom metal shield, and every shield-to-shield or shield-to-box joint must use a metal-shield connector.
Q29 NEC 324.40(C)
Under 324.40(C)(1), what must a metal top shield do in a Type FCC cable installation?
- A Completely cover all cable runs, corners, connectors, and ends
- B Cover the cable only where it crosses a doorway threshold
- C Cover the bottom shield to keep it from shifting
- D Cover only the splice points between cable runs
Show answer & explanation
Correct: A — Completely cover all cable runs, corners, connectors, and ends
324.40(C)(1) requires the top shield to completely cover all cable runs, corners, connectors, and insulating ends, not just splices or transition points. Partial coverage options like splice-only or threshold-only protection don't meet this requirement.
FCC Systems: Prohibited Locations and Uses
NEC 324.12 Flat conductor cable (FCC) is an under-carpet system for finished, protected indoor spaces only — it's barred outdoors, in wet or corrosive areas, hazardous locations, homes, and most school and hospital rooms.
Q30 NEC 324.12 Code lookup
A contractor wants to install a flat conductor cable (FCC) system in a hospital, running it through the corridor floors serving patient care areas. Which section addresses whether this installation is allowed?
- A 324.1
- B 324.10(G)
- C 324.10(E)
- D 324.12
Show answer & explanation
Correct: D — 324.12
324.12 lists the locations where FCC systems are prohibited, including school and hospital buildings other than administrative office areas. 324.10(E) only addresses damp locations for permitted installations, and 324.1 is just the article's scope statement, neither of which lists the prohibited-use categories.
Altering Existing FCC Installations
NEC 324.56(A) You can alter an FCC system with new connectors at new tap points, and unused runs may stay in place energized as long as the exposed ends are insulated.
Q31 NEC 324.56(A)
An electrician is altering an existing FCC (Flat Conductor Cable) floor system to add a new tap point. Per 324.56(A), what must be used at the new connection point?
- A A new cable connector
- B A field-fabricated splice covered with tape only
- C The same connector removed from the abandoned run
- D No connector is needed if the run stays de-energized
Show answer & explanation
Correct: A — A new cable connector
324.56(A) requires new cable connectors at new connection points when altering FCC systems. Reusing an old connector, taping a field splice, or skipping a connector entirely are not what the section permits.
FCC Cable Construction: Conductors and Shields
NEC 324.100 Type FCC cable is 3-5 flat copper conductors (one always an EGC) sandwiched under a metal top shield and a metal-or-nonmetal bottom shield.
Q32 NEC 324.100
A Type FCC cable installation uses a cable with four flat copper conductors. Which statement about those conductors is required by the NEC?
- A At least one of the four conductors must be an equipment grounding conductor
- B Two of the four conductors must be equipment grounding conductors
- C All four conductors must be sized identically with no grounding conductor required
- D The cable must be relisted as Type FC before an equipment grounding conductor is added
Show answer & explanation
Correct: A — At least one of the four conductors must be an equipment grounding conductor
324.100(A) requires Type FCC cable to consist of three, four, or five flat copper conductors, one of which is an equipment grounding conductor — not two, and not zero.
FCC Cable Connectors, Insulating Ends, and Polarization
NEC 324.40(A) Every FCC cable connection needs an identified connector that seals against moisture, and bare cable ends must always get insulated ends — polarity has to stay correct throughout.
Q33 NEC 324.40(A)
A bare end of Type FCC cable is exposed after termination. What does 324.40(A) require?
- A Wrapping the end with electrical tape rated for wet locations
- B Sealing it with a listed insulating end
- C Covering it with the floor covering material only
- D Leaving it exposed if the cable is under carpet squares
Show answer & explanation
Correct: B — Sealing it with a listed insulating end
324.40(A) specifically requires bare cable ends to be insulated and sealed against dampness and liquid spillage using listed insulating ends. Tape or floor covering alone doesn't meet this identified-product requirement, and being under carpet squares doesn't exempt the end from needing a listed insulating end.
Covering FCC Cable with Carpet Squares
NEC 324.41 Type FCC cable under carpet must be covered with carpet squares no larger than 39.37 in. square, and glued-down squares need release-type adhesive.
Q34 NEC 324.41
An installer is covering floor-mounted Type FCC cable with carpet squares. Per 324.41, what is the maximum permitted size of each carpet square?
- A 1.2 m (47.2 in.) square
- B 0.5 m (19.7 in.) square
- C 1.0 m (39.37 in.) square
- D Any size, provided the cable is fully covered
Show answer & explanation
Correct: C — 1.0 m (39.37 in.) square
324.41 caps carpet squares over Type FCC cable at 1.0 m (39.37 in.) square. The smaller 0.5 m and larger 1.2 m options are plausible but don't match the code text, and unlimited size is not permitted since oversized squares are excluded by the rule.
IGS cable conduit type and fill requirements
NEC 326.116 IGS cable must run in MDPE conduit sized 53, 78, or 103 (trade size 2, 3, or 4), with fill checked against both Table 326.116 and Table 1, Chapter 9.
Q35 NEC 326.116
An electrician is sizing conduit for IGS cable conductors. Which table sets the maximum percent fill those conductors may occupy?
- A Table 310.16
- B Table 1, Chapter 9
- C Table 326.116, since it's the section's own table
- D Table 300.5
Show answer & explanation
Correct: B — Table 1, Chapter 9
326.116 splits the job into two tables: Table 326.116 gives the conduit's own fill dimensions, while the percent-fill cap the conductors can't exceed comes from Table 1, Chapter 9 — the same fill limits used across other raceway types. Table 310.16 covers ampacity, not fill, and Table 300.5 covers underground burial depths.
Bending radius and bend-count limits for Type IGS cable
NEC 326.24 Type IGS cable bends can't be tighter than Table 326.24's minimum radius, and a run between pull points can't exceed four quarter bends total.
Q36 NEC 326.24
A run of Type IGS cable is installed between two pull boxes. How is the maximum allowable bending measured for this run under 326.26?
- A No more than four quarter bends, not counting any bends located at the pull boxes
- B No more than the equivalent of four quarter bends (360 degrees total), including bends at the pull boxes
- C Unlimited bends as long as the minimum radius in Table 326.24 is maintained at each one
- D No more than 360 degrees of bend per 100 feet of run
Show answer & explanation
Correct: B — No more than the equivalent of four quarter bends (360 degrees total), including bends at the pull boxes
326.26 caps a run between pull boxes or terminations at the equivalent of four quarter bends (360 degrees total), and explicitly includes bends located immediately at the pull box or terminations. Excluding those bends, applying a per-100-foot allowance, or assuming radius compliance alone is sufficient are all misreadings of 326.26.
Where Type IGS cable can and can't be used
NEC 326.10 Type IGS cable is strictly an underground/direct-burial cable — it's never allowed as interior wiring or exposed on a building.
Q37 NEC 326.10 Code lookup
A contractor wants to run Type IGS cable as the underground service-entrance conductors for a commercial building, direct buried in the earth. Which NEC section lists this as a permitted use for Type IGS cable?
- A 326.12
- B 326.1
- C 326.10
- D 326.116
Show answer & explanation
Correct: C — 326.10
326.10 (Uses Permitted) lists underground service-entrance, feeder/branch-circuit, and underground service conductors as permitted applications for Type IGS cable. 326.1 is only the scope statement, not the list of permitted uses.
MC Cable — Securing and Supporting Methods and Intervals
NEC 330.30(B) MC cable must be secured and supported every 6 ft and within 12 in. of every termination, unless it's small conductors, vertical runs, or framing-member support.
Q38 NEC 330.30(B)
A run of Type MC cable with two 12 AWG conductors enters a junction box. Per 330.30(B), how close to the box must the cable be secured?
- A No specific distance is required near boxes
- B Within 3 m (10 ft), since it qualifies for the vertical exception
- C Within 300 mm (12 in.) of the box
- D Within 1.8 m (6 ft) of the box, same as the general interval
Show answer & explanation
Correct: C — Within 300 mm (12 in.) of the box
Under 330.30(B), cable with four or fewer conductors sized no larger than 10 AWG must be secured within 300 mm (12 in.) of every box, cabinet, fitting, or termination — not just the general 6-ft interval. The 10-ft spacing only applies to listed vertical runs with 250 kcmil+ ungrounded conductors, which doesn't fit this smaller cable.
MC Cable — Ampacity Determination (General and Cable Tray)
NEC 330.80 MC cable ampacity comes from 310.14 (or 315.60 for larger sizes, Table 402.5 for 18/16 AWG) — but in cable tray, switch to 392.80 instead.
Q39 NEC 330.80
A calculated ampacity for a Type MC cable conductor exceeds the temperature rating of the equipment it terminates on. What does 330.80 require?
- A The higher calculated ampacity always governs since it comes from 310.14
- B The installation must not exceed the equipment's temperature rating, regardless of the conductor's calculated ampacity
- C The cable must be rerouted through cable tray so 392.80 applies instead
- D The conductor must be reclassified as Table 402.5 sized to resolve the conflict
Show answer & explanation
Correct: B — The installation must not exceed the equipment's temperature rating, regardless of the conductor's calculated ampacity
330.80 is explicit: the installation shall not exceed the temperature ratings of terminations and equipment, even if 310.14 or 315.60 would otherwise permit a higher ampacity. Switching tables or routing methods doesn't override this termination limit.
MC Cable — Minimum Bending Radius by Sheath Type
NEC 330.24 Minimum bend radius for MC cable depends on sheath type and, for smooth sheath, on cable diameter — never bend tighter than the multiplier allows.
Q40 NEC 330.24
An installer is bending a run of smooth-sheath Type MC cable with a 25 mm (1 in.) external diameter. Which multiplier of the external diameter sets the minimum bend radius?
- A 10 times
- B 12 times
- C 15 times
- D 7 times
Show answer & explanation
Correct: B — 12 times
Per 330.24(A)(2), smooth-sheath cable more than 19 mm (3/4 in.) but not more than 38 mm (1-1/2 in.) in external diameter uses 12 times the diameter. The 10 times multiplier applies only to cable at or under 19 mm, 15 times applies only above 38 mm, and 7 times is the interlocked/corrugated rule, not smooth sheath.
MC Cable — General Permitted Uses
NEC 330.10(A) Type MC cable is permitted almost everywhere — services, feeders, branch circuits, indoors, outdoors, direct burial, and even hazardous locations when another article allows it.
Q41 NEC 330.10(A)
Type MC cable is installed in a damp location with a corrosion-resistant jacket over the metallic covering. Which additional condition satisfies 330.10(A)(11)?
- A The cable is installed in a cable tray identified for wet locations
- B The cable is supported by a messenger wire
- C The metallic covering is impervious to moisture
- D The cable is embedded in plaster finish on masonry
Show answer & explanation
Correct: C — The metallic covering is impervious to moisture
Per 330.10(A)(11), a corrosion-resistant jacket alone isn't enough in a damp or wet location — one of three extra conditions must also be met, including a moisture-impervious metallic covering. Messenger support and cable tray relate to other permitted uses in 330.10(A)(6) and (8), and embedding in plaster applies to dry locations only under 330.10(A)(10).
MC cable sheath types and corrosion protection
NEC 330.116 MC cable's metallic sheath must be continuous, close-fitting, and one of three approved types — but it can never be used as the current-carrying conductor.
Q42 NEC 330.116
Which of the following is NOT a permitted metallic sheath type for Type MC cable under 330.116?
- A Perforated metallic sheath
- B Corrugated metallic sheath
- C Smooth metallic sheath
- D Interlocking metal tape armor
Show answer & explanation
Correct: A — Perforated metallic sheath
330.116 lists only three permitted metallic covering types: smooth metallic sheath, corrugated metallic sheath, and interlocking metal tape armor. A perforated sheath is not one of the recognized types.
MC Cable — Specific Installation Scenarios (Cable Tray, Direct Buried, SE, Outdoor/Aerial)
NEC 330.10(B) MC cable's 'Uses Permitted' list isn't complete — cable tray, direct burial, service-entrance, and outdoor/aerial runs each kick you out to a different governing article.
Q43 NEC 330.10(B)
An electrician is routing Type MC cable through a cable tray in an industrial facility. Which article's requirements govern this installation?
- A Article 392, Cable Trays
- B Article 725, Class 1 and Class 2 circuits
- C Article 300 general wiring methods only
- D Article 330 exclusively, since it is MC cable
Show answer & explanation
Correct: A — Article 392, Cable Trays
Per 330.10(B)(1), MC cable installed in cable tray must comply with specific subsections of Article 392 (392.10, 392.12, 392.18, 392.20, 392.22, 392.30, 392.46, 392.56, 392.60(C), and 392.80). Relying on Article 330 alone misses the tray-specific fill and support rules, and Article 300 and Article 725 don't govern cable tray installations.
MC Cable — When Support Is Not Required
NEC 330.30(D) MC cable normally needs support, but fished cable, short 6 ft drops to accessible-ceiling luminaires, and short 3 ft flexible whips to vibrating equipment can run unsupported.
Q44 NEC 330.30(D)
Under what condition may Type MC cable run unsupported when connecting to a luminaire in an accessible ceiling?
- A The unsupported length does not exceed 900 mm (3 ft) from the last point of support
- B The unsupported length does not exceed 1.8 m (6 ft) from the last point of support
- C The cable is interlocked-armor type regardless of length
- D The luminaire is located in a concealed space and cannot be reached
Show answer & explanation
Correct: B — The unsupported length does not exceed 1.8 m (6 ft) from the last point of support
330.30(D)(2) permits up to 1.8 m (6 ft) of unsupported MC cable from the last support point to the luminaire connection, provided both are within an accessible ceiling. The 900 mm (3 ft) limit applies instead to the interlocked-armor flexibility exception in 330.30(D)(3), and a concealed, unreachable space is the basis for the fished-cable exception in 330.30(D)(1), not this one.
MC Cable — Ampacity for Grouped Single Conductors
NEC 330.80(B) Single Type MC conductors grouped in a triangle or square get full table ampacity only if free airspace between conductors is at least 2.15 times the largest conductor's diameter.
Q45 NEC 330.80(B)
An installer is running single Type MC conductors grouped together on a messenger. Per 330.80(B), what spacing must be maintained for the conductors to use the standard ampacity tables rather than derated values?
- A Free airspace of not less than 2.15 times the diameter of the smallest conductor in the configuration
- B Free airspace of not less than 2.15 times the diameter of the largest conductor in the configuration
- C Free airspace equal to the diameter of one conductor between each pair
- D A minimum of 1 inch between adjacent cable groups regardless of conductor size
Show answer & explanation
Correct: B — Free airspace of not less than 2.15 times the diameter of the largest conductor in the configuration
330.80(B) requires maintained free airspace of not less than 2.15 times the diameter (2.15 × O.D.) of the largest conductor in the configuration, not the smallest, and not a flat 1-inch or single-diameter spacing rule.
Minimum conductor sizes for Type MC cable
NEC 330.104 Type MC power conductors bottom out at 14 AWG copper or 12 AWG aluminum; control/signal conductors can go smaller, down to 18 AWG copper.
Q46 NEC 330.104 Code lookup
A residential job spec calls for Type MC cable with copper conductors feeding a lighting circuit. The apprentice wants to pull 16 AWG copper conductors to save money on materials. Which section states the minimum conductor size for ungrounded, grounded, and equipment grounding conductors in Type MC cable?
- A 330.80
- B 330.108
- C 330.112
- D 330.104
Show answer & explanation
Correct: D — 330.104
330.104 sets the minimum conductor sizes for MC cable (14 AWG copper, 12 AWG aluminum/copper-clad aluminum). 330.108 only addresses what qualifies as the equipment grounding conductor, not minimum sizing, and 330.112 covers insulation types rather than conductor size.