Two different conductors, two different roles
Article 100 defines the terms the exam uses, and the two terms here are easy to confuse
because they sound nearly identical. The grounded conductor is a system or
circuit conductor that is intentionally connected to ground. In a standard single-phase or
three-phase system, this is the neutral — the conductor that completes the circuit by
returning current from the load back to the source under normal operating conditions. Current
flows through it every time a light switch is flipped.
The equipment grounding conductor (EGC) is a grounding conductor — note
the different word order — that connects the non-current-carrying metal parts of equipment
and enclosures back to the source. Under normal, fault-free conditions the EGC carries no
current. It exists so that if a phase conductor contacts a metal enclosure, the fault current
has a low-impedance path back to the source and the overcurrent device clears quickly. The
two conductors have completely different functions, and the NEC treats them accordingly.
Where neutral and ground are bonded — and why only there
In a grounded system, the grounded conductor (neutral) and the equipment grounding conductors
must be connected at exactly one point: the service. This connection is made by the
main bonding jumper, which bonds the neutral bus to the equipment grounding
bus (and the enclosure) at the main service equipment. The grounding electrode conductor then
ties both to the grounding electrode in the earth. From this single point, current that
returns on the neutral is referenced to earth, and the equipment grounding conductors have a
return path to the source through that same bus.
The single-point bonding requirement is intentional and critical. If neutral and ground were
bonded at more than one location, there would be multiple parallel paths for normal neutral
current: the intended neutral conductor and also the equipment grounding conductors and metal
raceways. Normal load current would flow on the EGCs and metal equipment, energizing
surfaces that are meant to be at zero volts under normal conditions. That is a shock hazard,
and it is exactly what a bootleg ground creates.
Subpanels: the most common downstream-bond mistake
At a subpanel — a distribution panel fed by a feeder rather than directly from the utility —
the neutral bar must be isolated from the metal enclosure. The feeder brings in
four conductors: two ungrounded (hot) conductors in a typical 120/240 V single-phase system,
one grounded (neutral) conductor, and one equipment grounding conductor. At the subpanel, the
neutral conductor terminates on an isolated neutral bar, and the EGC terminates on a ground
bar that bonds directly to the enclosure. The neutral and ground bars are kept separate.
Bonding the neutral to the enclosure at the subpanel — whether by using the wrong type of
terminal bar or by running a jumper between the two bars — creates a second neutral-to-ground
bond downstream of the service. The result is that normal neutral return current finds two
paths back to the source: the neutral conductor and the parallel path through the EGC and
metal enclosures. The EGC becomes current-carrying, which is a violation of Article 250 and
creates the same hazards as a bootleg ground.
The bootleg ground — what it is and why it fails the exam
A bootleg ground is the field shortcut of jumping the ground terminal to the neutral terminal
at a receptacle or device, usually to make an ungrounded outlet read "correct" on a
receptacle tester. The tester sees a voltage difference between the neutral and the newly
jumped ground terminal and reports "correct ground," but the connection is fraudulent. There
is no low-impedance fault path back to the source through a dedicated EGC; there is only a
neutral connection dressed up as a ground.
A bootleg ground is a code violation under Article 250 and a shock hazard. Because the
"ground" is actually the neutral, any imbalance or break in the neutral conductor can push
voltage onto the grounded metal parts of connected equipment. The exam tests this scenario
because it requires understanding why the single-point bond rule exists — not just
that it exists.
How to keep the terminology straight on the exam
When an exam question uses the word "grounded," it almost always means the neutral —
a conductor intentionally connected to ground that carries normal circuit current. When it
says "grounding," it means the equipment grounding conductor or the act of connecting to
earth — a conductor or path that normally carries no current. The grammatical distinction
(adjective vs. participle) is the NEC's way of signaling two entirely different conductors.
| Term | NEC name | Normal current? | Bonded at service? |
| Neutral wire | Grounded conductor | Yes — return current | Yes, via main bonding jumper |
| Ground wire (green/bare) | Equipment grounding conductor | No — fault current only | Yes, via main bonding jumper |
Pair this with the grounding electrode system
article to understand what the service bond connects to in the earth, and review
EGC sizing under 250.122 to see how the equipment
grounding conductor is sized for each circuit once it leaves the service.