Portable supply cord types and permitted exceptions
NEC 520.68(A) Portable stage equipment defaults to extra-hard usage cord; hard usage (junior) cord is only allowed under specific protected exceptions like stand lamps, luminaire whips, and short breakouts.
Q1 NEC 520.68(A)
Under 520.68(A)(2), which condition is NOT one of the requirements for using listed hard usage (junior hard service) cord in a protected application?
- A The cord does not exceed 30 m (100 ft) in length
- B The cord is listed for extra-hard usage rather than hard usage
- C The cord is connected to a branch circuit protected at not over 20 amperes
- D The cord is protected from physical damage over its entire length by attachment to a support structure
Show answer & explanation
Correct: B — The cord is listed for extra-hard usage rather than hard usage
520.68(A)(2) permits junior hard-usage cord itself (not extra-hard usage) when all three listed conditions are met: physical protection over its entire length, overcurrent protection not over 20 A, and a 30 m (100 ft) length cap. Requiring extra-hard usage cord would contradict the whole point of this exception, which is to allow the lighter-duty junior hard-usage cord under protected conditions.
Single-conductor supply cable sets: sizing and identification
NEC 520.54(C) Portable single-conductor supply cables for theater/stage equipment must be 2 AWG or larger with a 6 AWG minimum equipment grounding conductor, grouped (not bundled), and color-identified per 200.6, 250.119, and 310.6.
Q2 NEC 520.54(C)
Under 520.54(C), what is the minimum permitted size for single-conductor portable supply cables?
- A 4 AWG
- B 6 AWG
- C 8 AWG
- D 2 AWG
Show answer & explanation
Correct: D — 2 AWG
520.54(C) sets the floor for single-conductor portable supply cable sets at 2 AWG. The 6 AWG value is the minimum for the equipment grounding conductor, not the supply conductors, and 4 AWG and 8 AWG are not the specified minimums.
Wiring for low-voltage, signaling, and communications systems in 520 spaces
NEC 520.5(B) In theaters and similar assembly spaces, low-voltage and signal wiring still follows its own dedicated article — 520 just tells you where to look.
Q3 NEC 520.5(B)
An electrician is wiring a Class 2 remote-control circuit for stage curtain automation in a theater covered by Article 520. Which article's Part III governs this wiring?
- A Article 800
- B Article 640
- C Article 760
- D Article 725
Show answer & explanation
Correct: D — Article 725
Per 520.5(B)(3), Class 2 and Class 3 remote control and signaling circuits are wired per Part III of Article 725. Article 760 governs fire alarm circuits, Article 800 governs communications systems, and Article 640 governs audio equipment — all separate references within the same section.
Adapters and two-fers — rating and cord requirements
NEC 520.69 A two-fer or adapter's receptacle and cable must match the supply plug's current and voltage rating exactly, and its cord is limited to two listed hard-usage types.
Q4 NEC 520.69
A stage electrician wants to use a two-fer rated 15 A to split power from a 20 A stage circuit outlet, keeping the actual load under 15 A. Is this permitted under 520.69(A)?
- A Yes — as long as the two-fer has its own supplemental overcurrent protection
- B Yes — a lower-rated two-fer is fine on a larger circuit as long as the actual load stays under its rating
- C No — the two-fer's receptacle and cable must match the plug's rating exactly, and it can't be used on a circuit with a greater rating
- D No — two-fers are restricted to circuits rated 10 A or less regardless of the plug
Show answer & explanation
Correct: C — No — the two-fer's receptacle and cable must match the plug's rating exactly, and it can't be used on a circuit with a greater rating
520.69(A) requires the receptacle and cable to carry the same current and voltage rating as the supply plug, and bars using the device on a stage circuit with a greater rating. A 15 A two-fer doesn't match a 20 A plug's rating, so it's not permitted — even though the measured load stays under 15 A. There's no exception in this section for keeping the load low, adding supplemental protection, or a blanket 10 A cutoff.
Conductor insulation and temperature ratings for strip lighting
NEC 520.42 Strip and border light conductors need at least 125°C insulation, but you still size them using the 60°C ampacity column.
Q5 NEC 520.42
A strip light conductor is insulated for 125°C. Which ampacity value must be used to size that conductor per 520.42?
- A The 60°C ampacity
- B The 125°C ampacity, matching its insulation rating
- C The 75°C ampacity, since it splits the difference
- D The 90°C ampacity, per Table 310.4(1)
Show answer & explanation
Correct: A — The 60°C ampacity
520.42 specifically states that the ampacity of the 125°C conductors shall be that of 60°C conductors, not the 125°C or any intermediate value, despite the higher insulation rating.
Cords and cables for border lights, drop boxes, and connector strips
NEC 520.44(C)(1) Only listed extra-hard-usage cords and cables may feed border lights, drop boxes, and connector strips, and only where flexibility is actually needed.
Q6 NEC 520.44(C)(1)
A theatrical lighting designer wants to run flexible cord to a connector strip simply because it was easier to route than rigid conduit. Per 520.44(C)(1), is this permitted?
- A No, extra-hard-usage cords and cables may only be used where flexible conductors are necessary
- B Yes, extra-hard-usage cord may always be substituted for fixed wiring methods on stage equipment
- C No, cords and cables are never permitted to supply connector strips
- D Yes, as long as the cord is listed for hard usage rather than extra-hard usage
Show answer & explanation
Correct: A — No, extra-hard-usage cords and cables may only be used where flexible conductors are necessary
520.44(C)(1) permits extra-hard-usage cords and cables for border lights, drop boxes, and connector strips only where flexible conductors are necessary — not as a routing convenience. A merely-hard-usage listing doesn't meet the extra-hard-usage requirement, and cords are permitted when flexibility is actually needed, so a blanket ban is also wrong.
Autotransformer vs. Solid-State Dimmer Voltage & Grounding Limits
NEC 520.25(B) Both dimmer types cap the supply at 150 volts between conductors (unless a solid-state unit is listed for higher voltage), and both require the grounded conductor to stay common between input and output.
Q7 NEC 520.25(B)
A solid-state stage dimmer is being installed on a circuit supplying 208 volts between conductors. Under what condition is this permitted?
- A The dimmer is listed specifically for higher voltage operation
- B Only if an autotransformer is added ahead of the dimmer to step down voltage first
- C Only if the dimmer chassis is left unbonded to avoid ground loops
- D Never — solid-state dimmers are capped at 150 volts with no exceptions
Show answer & explanation
Correct: A — The dimmer is listed specifically for higher voltage operation
520.25(C) permits a solid-state dimmer's supply to exceed 150 volts between conductors only when the dimmer is listed specifically for higher voltage operation. The 'never' option ignores this listed exception, and chassis bonding is a separate, unrelated requirement under the same section that is not optional.
Wall switch and pilot light control for dressing/makeup room lighting
NEC 520.73 Mirror lights, mirror-adjacent receptacles, and makeup-counter fixtures need a wall switch in the room, and that switch needs an outside pilot light.
Q8 NEC 520.73
In a theater dressing room, which outlet is required by 520.73 to be controlled by a wall switch?
- A A receptacle installed adjacent to the makeup mirror
- B A general-purpose receptacle on the wall opposite the mirror
- C A floor receptacle used for vacuum cleaners
- D A receptacle inside a storage closet within the room
Show answer & explanation
Correct: A — A receptacle installed adjacent to the makeup mirror
520.73 requires wall-switch control only for luminaires, lampholders, and receptacles adjacent to the mirror or above the makeup counter. The general-purpose wall receptacle, the floor receptacle, and the closet receptacle are all 'other outlets' in the room, which 520.73 explicitly does not require to be switched.
Multipole branch-circuit cable connectors
NEC 520.67 Stage connectors must keep cord tension off the contacts, keep the female half on the load side, and stay polarized so mismatched ratings can't mate.
Q9 NEC 520.67
A stagehand needs to connect a 15-ampere attachment plug into a device connector on a lighting circuit. Under what condition is this permitted per 520.67?
- A Only if an adapter is used to step up the plug's rating to 20 amperes
- B Never — differently rated devices can never be connected together under any condition
- C Only if the plug is connecting into a 20-ampere T-slot receptacle of the same voltage rating
- D Only if the circuit is protected by GFCI protection
Show answer & explanation
Correct: C — Only if the plug is connecting into a 20-ampere T-slot receptacle of the same voltage rating
520.67 generally requires connectors to be designed so differently rated devices cannot connect, but it carves out one specific exception: a 20-ampere T-slot receptacle is permitted to accept a 15-ampere attachment plug of the same voltage rating. There's no adapter provision or GFCI-based exception in this section, and it isn't an absolute never — the T-slot exception exists.
Portable conductor ampacity and overcurrent protection
NEC 520.68(B) Portable cord ampacity normally follows 400.5, but listed extra-hard usage multiconductor cord away from heat-producing equipment can instead use Table 520.44(C)(2)(1), and overcurrent protection always follows 240.5.
Q10 NEC 520.68(B) Code lookup
A studio is running a multiconductor, listed, extra-hard usage portable cord to feed stage equipment, and the cord is not in direct contact with any heat-producing equipment. Which section allows the ampacity of that cord to be determined using Table 520.44(C)(2)(1) instead of the standard 400.5 ampacity rule?
- A 520.68(D)
- B 520.68(B)
- C 520.68(A)(2)
- D 520.68(A)(5)
Show answer & explanation
Correct: B — 520.68(B)
520.68(B) sets the default ampacity rule of 400.5 for portable conductors and carves out the exception permitting extra-hard usage multiconductor cords to use Table 520.44(C)(2)(1). 520.68(A)(2) covers protected-application conductor types, and 520.68(A)(5) covers alternate conductors for high-temperature use, not ampacity determination.
Portable strip lighting construction
NEC 520.64 Portable strips must be built like border lights and proscenium sidelights, with bushings anywhere the supply cable passes through metal and strain relief so cable tension never hits the connections.
Q11 NEC 520.64
Under 520.64, portable strip lighting must be constructed in accordance with the requirements for which other equipment?
- A Receptacle-type stage connector strips
- B Footlights
- C Portable stage-lighting equipment enclosures generally
- D Border lights and proscenium sidelights
Show answer & explanation
Correct: D — Border lights and proscenium sidelights
520.64 requires portable strips to be built to the same construction requirements as border lights and proscenium sidelights in 520.44(A). Footlights and connector strips are separate equipment categories with their own provisions elsewhere in Article 520, not the ones 520.64 points to.
Reducing supply conductor size for short runs (10 ft and 20 ft rules)
NEC 520.54(D) Short supply taps to portable switchboards can be undersized — 1/4 ampacity at 10 ft, 1/2 at 20 ft — but only if they're unspliced, unbundled, protected from damage, and never pass through a wall, floor, or ceiling.
Q12 NEC 520.54(D)
An electrician runs a 4 m (13 ft) supply conductor from the supply to a portable switchboard's overcurrent device. Which reduction rule applies?
- A Neither rule applies because the run exceeds 3 m
- B The 3 m (10 ft) rule, since it is the more conservative sizing
- C The 6 m (20 ft) rule, since the run exceeds 3 m but not 6 m
- D Either rule may be chosen at the installer's discretion
Show answer & explanation
Correct: C — The 6 m (20 ft) rule, since the run exceeds 3 m but not 6 m
520.54(E) governs runs up to 6 m (20 ft); a 4 m run exceeds the 3 m (10 ft) threshold in 520.54(D) but qualifies under the 20 ft rule, which requires ampacity of at least one-half the supply OCPD rating, not one-quarter. The rules aren't interchangeable by choice — each has its own length ceiling and minimum ampacity fraction.
Road show connection panel and supplementary circuits
NEC 520.50 A road show connection panel links portable stage switchboards to fixed lighting outlets through permanently installed supplementary circuits, each protected by its own branch-circuit overcurrent device in the panel.
Q13 NEC 520.50
Where does 520.50(C) require the branch-circuit overcurrent protective device for each supplementary circuit to be located?
- A At the fixed lighting outlet itself
- B Within the road show connection panel
- C On the portable stage switchboard only
- D At the venue's main service equipment only
Show answer & explanation
Correct: B — Within the road show connection panel
520.50(C) states each supplementary circuit shall be protected by branch-circuit overcurrent protective devices installed within the road show connection panel — protection at the service, the portable switchboard alone, or the outlet doesn't satisfy this in-panel requirement.
Smoke ventilator control circuit requirements
NEC 520.49 The smoke ventilator release circuit must be normally closed, run at full circuit voltage with no resistance, and be operable from two switches, one on stage and one where the AHJ designates.
Q14 NEC 520.49
Per 520.49, a stage smoke ventilator release circuit operated by an electrical device shall be:
- A Normally open, so the device only energizes to release the ventilator
- B Interlocked with the stage lighting dimmer circuit
- C Supervised by a signaling line circuit rated for Class 2 power only
- D Normally closed, so the ventilator releases on loss of circuit continuity
Show answer & explanation
Correct: D — Normally closed, so the ventilator releases on loss of circuit continuity
520.49 requires the circuit operating the release device to be normally closed, a fail-safe design so a circuit fault or power loss releases the ventilator rather than preventing release. A normally open arrangement would fail unsafe, and the section does not mention dimmer interlocks or Class 2 signaling line supervision.
Special-purpose multicircuit cable systems
NEC 520.68(D) Special-purpose multicircuit trunk cables carry multiple 20 A, 150 V-to-ground branch circuits, but only through listed hardware and only under qualified hands.
Q15 NEC 520.68(D)
Under 520.68(D), what is the maximum rating permitted for a branch circuit within a special-purpose multicircuit cable system?
- A 20 amperes, 300 volts to ground
- B 20 amperes, 150 volts to ground
- C 30 amperes, 150 volts to ground
- D 15 amperes, 120 volts to ground
Show answer & explanation
Correct: B — 20 amperes, 150 volts to ground
520.68(D)(1) caps each branch circuit in a special-purpose multicircuit cable system at not more than 20 amperes and not more than 150 volts to ground. The 300-volt option confuses this with general wiring methods, the 30-ampere option exceeds the stated cap, and 15 A/120 V is more restrictive than the code actually requires.
Stage Switchboard Feeder Configurations
NEC 520.27(A) Stage switchboards can be fed one of three ways — single feeder, multiple feeders on one system, or separate feeders with separate disconnects — and each has its own labeling or sizing rule.
Q16 NEC 520.27(A)
Under 520.27(A), which of the following is NOT a permitted feeder arrangement for a stage switchboard?
- A Separate feeders to a single primary stage switchboard, each with its own disconnecting means
- B A single feeder disconnected by a single disconnect device
- C Multiple feeders of unlimited quantity to an intermediate stage switchboard, all part of one system
- D Multiple feeders from unrelated systems combined at a single primary stage switchboard without individual disconnects
Show answer & explanation
Correct: D — Multiple feeders from unrelated systems combined at a single primary stage switchboard without individual disconnects
520.27(A) permits exactly three arrangements: a single feeder (520.27(A)(1)), multiple feeders to an intermediate patch panel provided they're part of a single system (520.27(A)(2)), and separate feeders to a primary switchboard each with its own disconnect (520.27(A)(3)). Combining unrelated systems without individual disconnects fits none of these.
Neutral Conductor Ampacity for Dimming System Feeders
NEC 520.27(B) Phase-control dimming feeders always count the neutral as current-carrying; pure sine wave feeders don't; mixed-capable systems default to current-carrying.
Q17 NEC 520.27(B)
A 3-phase, 4-wire feeder supplies a solid-state, phase-control dimming system. For ampacity adjustment purposes, how must the neutral conductor be classified?
- A As an equipment grounding conductor
- B As current-carrying only if the connected load exceeds 50% of the dimmer's rating
- C As a current-carrying conductor
- D As a non-current-carrying conductor, the same as a balanced linear load
Show answer & explanation
Correct: C — As a current-carrying conductor
520.27(B)(1) requires the neutral of a feeder supplying a solid-state, phase-control 3-phase, 4-wire dimming system to be considered current-carrying, with no load-percentage exception. It also isn't functioning as a grounding conductor here.
Fixed Stage Switchboard General Requirements
NEC 520.21 Every fixed stage switchboard must be listed, readily accessible, and hold its own branch-circuit overcurrent protection.
Q18 NEC 520.21
Which statement about overcurrent protection on a fixed stage switchboard is correct per 520.21?
- A Overcurrent protection is only required when the switchboard is not readily accessible
- B Overcurrent protection is only required for nonstage branch circuits
- C Overcurrent protection may be omitted if the branch circuits are individually fused elsewhere in the venue
- D The switchboard must contain overcurrent protective devices for all branch circuits it supplies
Show answer & explanation
Correct: D — The switchboard must contain overcurrent protective devices for all branch circuits it supplies
520.21(3) requires a fixed stage switchboard to contain overcurrent protective devices for all branch circuits supplied by that switchboard — there's no carve-out for circuits fused elsewhere, for nonstage-only coverage, or tied to accessibility.
Types of Stage Switchboards (Manual, Remote, Intermediate, Constant Power)
NEC 520.26 Stage switchboards fall into four types — manual, remotely controlled, intermediate, and constant power — and a real installation can combine them.
Q19 NEC 520.26
According to 520.26, how many distinct types of stage switchboard are recognized, and can they be combined in one installation?
- A Four types, but only one type may be used per installation
- B Four types, and they may be combined
- C Three types, and they may be combined
- D Two types, manual and remote only
Show answer & explanation
Correct: B — Four types, and they may be combined
520.26 states a stage switchboard shall be either one or a combination of the types specified in (A) manual, (B) remotely controlled, (C) intermediate, and (D) constant power — four types total, and combining them is explicitly permitted.
Protecting supply conductors and limiting connector interconnections
NEC 520.54(G) Supply conductors and connectors need physical protection (no raceway required), and cap-and-pig-tail runs are limited to 3 mated connector pairs per 30 m (100 ft), plus locking single-pole connectors when used.
Q20 NEC 520.54(G)
A supply conductor run from the power source to a portable switchboard is 45 m (about 148 ft). What is the maximum number of mated connector pair interconnections permitted?
- A 4
- B 5
- C 3
- D 6
Show answer & explanation
Correct: A — 4
Per 520.54(H), the base allowance is 3 interconnections for the first 30 m (100 ft), plus one additional interconnection for each additional 30 m (100 ft) or portion thereof. A 45 m run exceeds the first 30 m increment, adding one more interconnection for a total of 4. The base-only count of 3 ignores the additional length, and 5 or 6 overcounts the additional increments.
Supply cords/cables to portable switchboards: general and conductor sizing
NEC 520.54(A) Portable stage switchboards must be fed by extra-hard usage cord terminating in a fused disconnect, and the neutral counts as current-carrying with phase control dimmers but not with sine wave dimmers.
Q21 NEC 520.54(A)
A portable stage switchboard uses only solid-state sine wave dimmers. How should the neutral conductor be treated when sizing the power supply conductors for ampacity adjustment?
- A As a current-carrying conductor only if the load exceeds 200 A
- B As a non-current-carrying conductor
- C As a current-carrying conductor, the same as with phase control dimmers
- D It may be omitted from the ampacity calculation entirely
Show answer & explanation
Correct: B — As a non-current-carrying conductor
520.54(B) distinguishes dimmer types: with only solid-state sine wave dimmers, the neutral is considered non-current-carrying for ampacity adjustment. Treating it as current-carrying is the rule for phase control dimmers, not sine wave; there's no load-based threshold and the neutral can't simply be dropped from consideration.
Portable switchboard internal connectors and conductor requirements
NEC 520.53(C) Listed single-pole separable connectors follow 406.13 instead of the usual cord-and-plug rules, feed-throughs matching the inlet rating skip overcurrent protection, and all interior conductors except busbars must be stranded.
Q22 NEC 520.53(C)
A portable stage switchboard uses listed single-pole separable connectors for its supply input. Which statement about applicable requirements is correct?
- A The connectors must comply with 406.13, and 400.14, 406.7, and 406.8 do not apply to them
- B The connectors must comply with 406.7 and 406.8 but not 406.13
- C The connectors must comply with 400.14 in addition to 406.13
- D The connectors are exempt from 406.13 because they are listed
Show answer & explanation
Correct: A — The connectors must comply with 406.13, and 400.14, 406.7, and 406.8 do not apply to them
Per 520.53(C), listed single-pole separable connectors must comply with 406.13, while 400.14, 406.7, and 406.8 specifically do not apply to them or to single-conductor cable assemblies using them. Requiring 400.14 in addition, exempting 406.13, or applying 406.7/406.8 instead all misstate which sections apply.
Portable switchboard construction: listing, pilot light, neutral sizing
NEC 520.53 Portable stage switchboards must be listed, need a pilot light per ungrounded feeder conductor, and their neutral terminal must carry at least twice the ampacity of the largest ungrounded terminal.
Q23 NEC 520.53
A portable switchboard is designed for 3-phase, 4-wire with ground supply and is NOT field-convertible. How must the neutral terminal's ampacity compare to the largest ungrounded supply terminal?
- A At least twice the ampacity of the largest ungrounded supply terminal
- B At least 125% of the ampacity of the largest ungrounded supply terminal
- C At least half the ampacity of the largest ungrounded supply terminal
- D At least equal to the ampacity of the largest ungrounded supply terminal
Show answer & explanation
Correct: A — At least twice the ampacity of the largest ungrounded supply terminal
520.53(B) requires the supply neutral terminal, busbar, and wiring to have ampacity at least twice the largest ungrounded supply terminal for standard 3-phase, 4-wire with ground portable switchboards. The 'equal to' rule only applies after a unit has been field-converted to single-phase, 3-wire per the second paragraph of 520.53(B); the other ratios don't appear in this section.
Conductor fill limits in raceways and wireways for stage circuits
NEC 520.6 Stage-circuit conductors in conduit or EMT follow Chapter 9 Table 1 fill percentages, but in auxiliary gutters or wireways they're capped at 20% cross-sectional fill with no 30-conductor limit.
Q24 NEC 520.6 Code lookup
A theatrical rigging contractor is pulling multiple stage circuit conductors into a section of auxiliary wireway feeding a dimmer bank. Which section limits the total cross-sectional area of the conductors as a percentage of the wireway's interior cross-sectional area?
- A 520.27(C)
- B 520.9
- C 520.5(A)
- D 520.6
Show answer & explanation
Correct: D — 520.6
520.6 sets the 20 percent fill limit for conductors in an auxiliary gutter or wireway on stage circuits and also references Table 1 of Chapter 9 for raceway fill. 520.27(C) instead addresses supply capacity of stage switchboard feeders, not conductor fill, so it doesn't answer a fill-limit question.
Grounding requirements for theater/stage equipment
NEC 520.81 Every metal raceway, metal-sheathed cable, and equipment frame or enclosure on stage — including border lights and portable luminaires — must connect to an equipment grounding conductor.
Q25 NEC 520.81 Code lookup
A stage rigger is landing a portable dimmer's feeder in metal conduit and wants to confirm that the raceway and the metal frame of the connected border lights both terminate to grounding. Which section requires this connection?
- A 520.68(C)
- B 520.81
- C 520.62
- D 520.69(B)
Show answer & explanation
Correct: B — 520.81
520.81 is the section that requires metal raceways, metal-sheathed cables, and the metal frames/enclosures of equipment (including border lights and portable luminaires) to connect to an equipment grounding conductor. 520.68(C) only addresses overcurrent protection for portable conductors, not grounding.
Approved fixed wiring methods for assembly/theater spaces
NEC 520.5(A) In assembly and theater spaces, fixed wiring must be metal raceway, nonmetallic raceway with 2 in. of concrete encasement, or MI/MC/AC cable with a sized insulated equipment grounding conductor.
Q26 NEC 520.5(A) Code lookup
You're wiring the fixed lighting circuits backstage in a theater assembly space. The nonmetallic raceway you want to use is encased in 2 in. of concrete. Which section lists this as an approved fixed wiring method for the space?
- A 520.5(C)
- B 520.5(A)
- C 520.5(B)
- D 520.6
Show answer & explanation
Correct: B — 520.5(A)
520.5(A) lists the approved fixed wiring methods — metal raceways, nonmetallic raceways encased in 2 in. of concrete, or MI/MC/AC cable with a sized equipment grounding conductor. 520.5(B) only covers communications/signaling/low-voltage systems, not the fixed power wiring method.
Wiring methods allowed in non-fire-rated construction
NEC 520.5(D) In theaters and similar assembly spaces, NM cable, AC cable, ENT, and rigid nonmetallic conduit are only allowed where the building code doesn't require fire-rated construction.
Q27 NEC 520.5(D) Code lookup
A theater's dressing room is located in a portion of the building that the applicable building code does NOT require to be of fire-rated construction. Which section permits nonmetallic-sheathed cable, Type AC cable, ENT, and rigid nonmetallic conduit to be used there?
- A 520.5(C)
- B 520.5(B)
- C 520.5(A)
- D 520.5(D)
Show answer & explanation
Correct: D — 520.5(D)
520.5(D) specifically permits NM cable, AC cable, ENT, and rigid nonmetallic conduit in buildings or portions not required to be fire-rated construction. 520.5(A) is the general wiring methods rule tied to fire-rated construction, 520.5(B) covers low-voltage/signal systems, and 520.5(C) covers portable equipment — none address the nonrated-construction exception.