Placement, access, and mounting height of RV site supply equipment
NEC 551.77(A) RV site supply equipment must sit in a marked zone on the driver's side, 2 ft to 6 ft 6 in. above grade, with clear access and working space.
Q1 NEC 551.77(A) Code lookup
A back-in RV site's supply equipment is being installed. Which section specifies where along the site (distance from the left edge of the RV stand and how far forward of the rear) the equipment must be located?
- A 551.79
- B 551.77(A)
- C 551.77(D)
- D 551.77(C)
Show answer & explanation
Correct: B — 551.77(A)
551.77(A) gives the exact placement dimensions (1.5-2.1 m from the left edge, distance forward of the rear) for back-in and pull-through sites. 551.77(C) covers the access passageway, not the site-line placement, and 551.79 covers overhead conductor clearance, not equipment location on the stand.
Grounding requirements for RV site supply equipment
NEC 551.76 RV site supply equipment doesn't need its own grounding electrode, but every metal part gets grounded through an equipment grounding conductor — never the grounded (neutral) conductor.
Q2 NEC 551.76
A recreational vehicle site supply panel is not being used as service equipment. Which statement about its grounding electrode is correct?
- A A grounding electrode is required but may be omitted if a secondary distribution transformer is grounded
- B A grounding electrode is required only if the site serves more than one RV
- C No grounding electrode is required, though an auxiliary electrode per 250.54 is permitted
- D A grounding electrode is mandatory at every RV site supply location
Show answer & explanation
Correct: C — No grounding electrode is required, though an auxiliary electrode per 250.54 is permitted
Per 551.76(A), RV site supply equipment that is not service equipment is not required to have a grounding electrode, though an auxiliary grounding electrode under 250.54 is permitted. The other choices invent conditions (mandatory electrode, multi-RV threshold, transformer substitution) that 551.76(A) does not impose.
Distribution system voltage classes and phase configurations for RV parks
NEC 551.72 Every RV site feed must be at least 30 A and use one of the listed single-phase voltage systems; only 50 A receptacles must match their circuit's voltage class exactly.
Q3 NEC 551.72
An RV park is designing feeders from a 208Y/120-volt, 3-phase system to individual RV sites. Which conductor arrangement is correct per 551.72(B)?
- A One ungrounded conductor, one grounded conductor, and one equipment grounding conductor
- B Three ungrounded conductors and one equipment grounding conductor, no neutral
- C Two ungrounded conductors, one grounded conductor, and one equipment grounding conductor
- D Three ungrounded conductors and one grounded conductor, with no equipment grounding conductor required
Show answer & explanation
Correct: C — Two ungrounded conductors, one grounded conductor, and one equipment grounding conductor
551.72(B) permits feeders from a 208Y/120-volt, 3-phase system to include two ungrounded conductors plus one grounded conductor and one equipment grounding conductor. Using three ungrounded conductors would make it a true 3-phase feed to the site, which isn't the permitted arrangement; omitting the neutral or the equipment grounding conductor also fails the rule.
Methods and Identification for Grounding Electrical Equipment
NEC 551.55(C) Every exposed metal part in an RV's electrical system must bond back to the panelboard's grounding terminal, using only bare or green(-striped) conductors and a listed grounding connection method.
Q4 NEC 551.55(C)
In an RV's electrical system, exposed metal parts such as luminaire canopies and enclosure frames must be bonded to what?
- A A separate grounding electrode installed at the RV site
- B The vehicle's chassis frame only
- C The grounding terminals or enclosure of the panelboard
- D The nearest metal water pipe
Show answer & explanation
Correct: C — The grounding terminals or enclosure of the panelboard
551.55(A) requires exposed metal parts to be effectively bonded to the grounding terminals or enclosure of the panelboard. Chassis-only bonding, water pipe bonding, or a separate site electrode are not what this section specifies for interior equipment grounding.
Calculating service and feeder loads for RV park sites
NEC 551.73 Start each RV site at its fixed VA-per-site minimum by supply type, then apply Table 551.73(A)'s demand factor for the total site count before adding other loads.
Q5 NEC 551.73
An RV park service supplies sites equipped only with 20-ampere supply facilities dedicated to tent camping. What minimum VA per site must be used in the load calculation?
- A 12,000 volt-amperes per site
- B 600 volt-amperes per site
- C 3600 volt-amperes per site
- D 2400 volt-amperes per site
Show answer & explanation
Correct: B — 600 volt-amperes per site
Per 551.73(A)(4), sites with only 20-ampere supply facilities dedicated to tent sites use 600 VA per site. The 2400 VA figure applies to general 20-ampere-only sites that aren't tent-dedicated, per 551.73(A)(3).
Panelboard Listing, Grounding Bus, and Dead-Front Construction
NEC 551.45(A) An RV park's panelboard must be listed for the purpose, have an isolated grounded-conductor bar plus a separate equipment grounding bar, and stay dead-front with a main disconnect once fuses or more than two breakers are used.
Q6 NEC 551.45(A)
An RV park panelboard is built with Type S fuseholders. What additional requirement applies because fuses are used?
- A The panelboard must instead use only circuit breakers
- B The enclosure must be dead-front only if more than two branch circuits exist
- C A main disconnecting means must be provided
- D No main disconnect is needed as long as there are two or fewer branch circuits
Show answer & explanation
Correct: C — A main disconnecting means must be provided
551.45(C) requires a main disconnecting means whenever fuses are used, regardless of the branch circuit count. The dead-front requirement applies to the panelboard overall, not conditionally based on circuit count, and fuses do not need to be swapped for breakers.
GFCI-Required Locations for RV Receptacle Outlets
NEC 551.41(C) Every 125-volt, 15- or 20-amp RV receptacle near water, on the exterior, or in the transportation area needs GFCI protection, except for a short list of dedicated-appliance and expandable-room exceptions.
Q7 NEC 551.41(C)
In a recreational vehicle, which receptacle location does NOT require GFCI protection under 551.41(C)?
- A A receptacle in the area occupied by a shower
- B A receptacle within 6 ft of a bathroom lavatory countertop
- C A receptacle on the exterior of the vehicle
- D A receptacle in a dedicated space for a built-in freezer
Show answer & explanation
Correct: D — A receptacle in a dedicated space for a built-in freezer
551.41(C) exempts receptacles installed for appliances in dedicated spaces such as disposals, refrigerators, and freezers. The lavatory-adjacent, exterior, and shower-area receptacles are three of the five locations explicitly requiring GFCI protection.
GFCI protection for RV site receptacles
NEC 551.71(F) In RV site supply equipment, GFCI protection is required only for 125-volt, 15- and 20-ampere receptacles — not the 30- or 50-ampere RV receptacles.
Q8 NEC 551.71(F)
Under 551.71(F)(2), which receptacle installed in a recreational vehicle site's own supply equipment must have GFCI protection?
- A A 125/250-volt, 50-ampere receptacle
- B A 125/250-volt, 30-ampere receptacle
- C A 125-volt, 20-ampere receptacle
- D A 125-volt, 30-ampere receptacle
Show answer & explanation
Correct: C — A 125-volt, 20-ampere receptacle
Per 551.71(F)(2), GFCI protection in RV site equipment is required only for 125-volt, single-phase, 15- and 20-ampere receptacles. The 30-ampere and 50-ampere RV receptacles are excluded because RV appliances can produce leakage current exceeding a Class A GFCI's trip threshold, which would cause nuisance tripping.
Required receptacle ratings and coverage percentages per RV site
NEC 551.71 Every RV site needs at least a 20-amp receptacle, with 70% of sites also getting 30-amp and a minimum 20% (existing) or 40% (new) getting 50-amp, each 50-amp site also getting a 30-amp receptacle.
Q9 NEC 551.71
Under 551.71, what is the minimum receptacle rating required at every recreational vehicle site with electrical supply?
- A 50-ampere, 125/250-volt weather-resistant receptacle
- B 20-ampere, 125-volt tamper-resistant receptacle
- C 20-ampere, 125-volt weather-resistant receptacle
- D 30-ampere, 125-volt weather-resistant receptacle
Show answer & explanation
Correct: C — 20-ampere, 125-volt weather-resistant receptacle
551.71(A) requires at least one 20-ampere, 125-volt weather-resistant receptacle at every site. The 30-ampere and 50-ampere options are additional requirements that apply only to a percentage of sites, not every site, and the 20-ampere receptacle is specifically exempted from the tamper-resistant requirement rather than required to have it.
Bonding Metal Parts to Chassis: Requirement and Conductor Sizing
NEC 551.56(B) Exposed metal that could become energized must bond to the panelboard, and unless the chassis itself is bolted, welded, or riveted to the panelboard, an 8 AWG copper minimum bonding conductor makes that connection.
Q10 NEC 551.56(B)
An RV manufacturer wants to skip running a separate bonding conductor between the panelboard and the chassis. Under what condition is this permitted?
- A The chassis is a unitized metal frame securely bolted, welded, or riveted to the panelboard
- B The chassis is painted with a conductive coating rated for grounding
- C The panelboard is within 6 feet of the chassis frame rail
- D The RV is used only for seasonal, non-full-time occupancy
Show answer & explanation
Correct: A — The chassis is a unitized metal frame securely bolted, welded, or riveted to the panelboard
551.56(B) says a unitized metal chassis-frame construction securely fastened to the panelboard by bolts and nuts, welding, or riveting is considered bonded, so no separate conductor is required. Proximity, coatings, or usage pattern aren't recognized substitutes under this section.
Components Considered Bonded by Construction (Roof, Pipes, Ducts)
NEC 551.56(D) A metal RV roof, gas/water/waste pipe, and furnace ductwork all count as bonded once fastened or connected to the chassis a specific way — no separate bonding jumper needed.
Q11 NEC 551.56(D)
Under 551.56(D), which condition, by itself, is enough to consider an RV's metal roof and exterior covering bonded?
- A Both the panel overlap/fastener condition and the lower-panel-to-chassis connection are satisfied together
- B The panels overlap and are fastened with metal fasteners, with no other connection
- C The roof is painted with a conductive coating connecting it to the frame
- D The lower panel is secured to the chassis at each cross member, with no requirement on panel overlap
Show answer & explanation
Correct: A — Both the panel overlap/fastener condition and the lower-panel-to-chassis connection are satisfied together
551.56(D) requires both conditions to apply: panels overlapping with metal fasteners AND the lower panel secured to the chassis at each cross member (or strapped to it). Satisfying only the panel-overlap condition or only the chassis-connection condition is not sufficient on its own.
Outlet Box Material, Flush Mounting, and Securing
NEC 551.47(D) In RVs and RV parks, nonmetallic boxes only pair with nonmetallic-sheathed cable or raceway, boxes must be flush with combustible wall/ceiling surfaces, and mounting must meet 314.23 or use a listed bracket or backing plate.
Q12 NEC 551.47(D) Code lookup
A manufactured home has walls constructed of wood paneling. During rough-in, the electrician wants to know how a device outlet box must be positioned relative to the finished wall surface in that combustible wall. Which section specifies this requirement?
- A 551.47(E)
- B 551.47(D)
- C 551.47(K)
- D 551.47(C)
Show answer & explanation
Correct: B — 551.47(D)
551.47(D) requires boxes in combustible walls or ceilings to be flush with or project from the finished surface. 551.47(C) only addresses nonmetallic box compatibility with wiring methods, and 551.47(E) addresses mounting methods, not surface flushness.
Branch-Circuit Overcurrent Device Rating Rules
NEC 551.43(A) RV branch-circuit overcurrent devices must match the conductors, cap single-appliance loads at 150% of 13.3 A or more, and never exceed a motor-appliance's marked protection size.
Q13 NEC 551.43(A)
An individual branch circuit in an RV supplies a single appliance rated 13.3 amperes or more. Under 551.43(A), what overcurrent device rating is permitted?
- A Up to 200% of the appliance's rating
- B Up to 125% of the appliance's rating, matching standard continuous-load sizing
- C Exactly 100% of the appliance's rating, no rounding up
- D Up to 150% of the appliance's rating
Show answer & explanation
Correct: D — Up to 150% of the appliance's rating
551.43(A)(2) permits overcurrent protection up to 150% of the rating of a single appliance rated 13.3 amperes or more on an individual branch circuit. The 125% figure is a common continuous-load rule from elsewhere in the NEC but isn't the figure this section sets, and 100% or 200% aren't the permitted values here.
Cable Bend Radius and Support Spacing
NEC 551.47(I) Bends can't be tighter than 5x cable diameter, and cables need securing within 300 mm of most boxes — but only 200 mm for clampless nonmetallic boxes.
Q14 NEC 551.47(I) Code lookup
A mobile home manufacturer connects branch-circuit cables to appliances using cable connectors. Aside from the securing required near outlet boxes and splice boxes, which section specifies the maximum interval for supporting and securing the cable at other points along its run?
- A 551.47(H)
- B 551.47(K)
- C 551.47(J)
- D 551.47(I)
Show answer & explanation
Correct: D — 551.47(I)
551.47(I) sets the 1.4 m (4 1/2 ft) maximum support interval for cables secured with connectors or clamps, plus the 300 mm (12 in.) rule near boxes. 551.47(J) is a different rule that applies only to nonmetallic-sheathed cable at nonmetallic boxes lacking cable clamps, with its own 200 mm (8 in.) distance.
Cable/Raceway Continuity and Protection from Damage or Moisture
NEC 551.47(G) In RV wiring, raceways and cable sheaths must run unbroken between boxes, and cable through studs, wet areas, or damage zones needs specific mechanical protection.
Q15 NEC 551.47(G)
Line-voltage wiring is exposed under the chassis of a recreational vehicle. Per 551.47(N), what is required?
- A Any nonmetallic-sheathed cable, since it's factory-installed
- B Conduit or raceway identified for wet locations, with conductors listed for wet locations
- C A steel tube with 1.35 mm (0.053 in.) wall thickness
- D Guard strips only, since it is not exposed to moisture
Show answer & explanation
Correct: B — Conduit or raceway identified for wet locations, with conductors listed for wet locations
551.47(N)(1) requires exposed outdoor or under-chassis line-voltage wiring (120V nominal or higher) to be protected by wet-location-identified conduit or raceway, with wet-location-listed conductors. Guard strips address physical damage under 551.47(K)/(N)(2), and the steel tube spec is for stud penetrations under 551.47(G), not moisture exposure.
Wiring Connections for Expandable Room Sections
NEC 551.47(P) Expandable (slide-out) units connect to the main RV body by listed cord-and-plug or by direct-wired flexible cord meeting strict protection and wet-location rules.
Q16 NEC 551.47(P)
A recreational vehicle slide-out is wired using a cord-and-plug connection. The receptacle for the main circuit connection is located on the outside of the vehicle. What is required?
- A The receptacle must be GFCI-protected for personnel and listed for wet locations
- B The receptacle only needs a weatherproof-while-in-use cover, since the cord itself is rated for outdoor use
- C The receptacle must be AFCI-protected and located at least 150 mm (6 in.) above the floor
- D The receptacle must be listed for wet locations only, since it is protected by the vehicle's main disconnect
Show answer & explanation
Correct: A — The receptacle must be GFCI-protected for personnel and listed for wet locations
Per 551.47(P)(1)(b), an exterior-located receptacle for the cord connection must be protected with a GFCI for personnel and be listed for wet locations. GFCI protection cannot be substituted with just a wet-location listing or an in-use cover, and AFCI is not the requirement specified here.
Receptacle Faceplate Requirements in RVs
NEC 551.47(L) In an RV, a metal receptacle faceplate must meet 406.6(A) and be grounded per 404.9(B) and 404.6(B); a nonmetallic one only has to meet 406.6(C).
Q17 NEC 551.47(L)
Which statement correctly describes RV receptacle faceplate rules under 551.47(L) and (M)?
- A Metal faceplates must comply with 406.6(A) and be grounded per 404.9(B) and 404.6(B); nonmetallic faceplates need only meet 406.6(C).
- B Nonmetallic faceplates must comply with 406.6(A); metal faceplates must comply with 406.6(C).
- C Article 551 sets its own faceplate material standard independent of Article 406.
- D Metal and nonmetallic faceplates must both comply with 406.6(A) and be grounded per 404.9(B) and 404.6(B).
Show answer & explanation
Correct: A — Metal faceplates must comply with 406.6(A) and be grounded per 404.9(B) and 404.6(B); nonmetallic faceplates need only meet 406.6(C).
551.47(L) splits the rule by material: metal faceplates comply with 406.6(A), nonmetallic with 406.6(C). 551.47(M) adds a grounding duty only for metal faceplates, citing 404.9(B) and 404.6(B) — it doesn't apply to nonmetallic ones, and Article 551 doesn't replace Article 406, it cross-references it.
Required factory dielectric, continuity, and GFCI tests for RV electrical systems
NEC 551.60 Every 120V or 120/240V RV must pass a factory dielectric strength test plus continuity, operational, polarity, and GFCI checks before it leaves the line.
Q18 NEC 551.60
A manufacturer is dielectric-testing a 120/240-volt recreational vehicle using the 1-second test option. What voltage and current type is required for this shorter test?
- A 600 volts ac or 850 volts dc
- B 1080 volts ac or 1530 volts dc
- C 1500 volts ac or 2000 volts dc
- D 900 volts ac or 1280 volts dc
Show answer & explanation
Correct: B — 1080 volts ac or 1530 volts dc
Per 551.60, the 1-second dielectric test uses 1080 volts ac or 1530 volts dc. The 900 volts ac / 1280 volts dc figures belong to the longer 1-minute version of the same test, not the 1-second one.
RV generator mounting, bonding, and transfer protection
NEC 551.30(A) An RV generator must be bonded to the chassis for a ground-fault return path, and its output must never connect to a vehicle circuit at the same time as shore power.
Q19 NEC 551.30(A)
In an RV generator installation, what condition is the transfer equipment specifically designed to prevent?
- A The generator running longer than the manufacturer's duty cycle rating
- B The generator being mounted too close to the fuel tank
- C The generator and an outside power source both being connected to a vehicle circuit at the same time
- D The generator operating below its rated frequency
Show answer & explanation
Correct: C — The generator and an outside power source both being connected to a vehicle circuit at the same time
551.30(B) requires equipment to ensure the current-carrying conductors from the generator and from an outside source are never connected to a vehicle circuit simultaneously, preventing a dangerous backfeed condition. Duty cycle, frequency, and fuel tank clearance aren't addressed by this section.
Wiring generator supply conductors to the RV
NEC 551.30(E) Generator supply conductors must be stranded, run in listed flexible or liquidtight flexible conduit, and land at their first termination point within 450 mm (18 in.) of where they enter the vehicle.
Q20 NEC 551.30(E) Code lookup
A technician is running the supply conductors from an RV's onboard engine generator to the point where they first terminate inside the vehicle. Which section specifies that these conductors must be stranded and installed in listed flexible conduit or liquidtight flexible conduit, and lists the permitted points of first termination?
- A 551.30(B)
- B 551.30(A)
- C 551.30(E)
- D 551.30(D)
Show answer & explanation
Correct: C — 551.30(E)
551.30(E) covers the supply conductors themselves — stranded conductor type, required flexible/liquidtight conduit, and the five acceptable points of first termination. 551.30(A) addresses generator mounting and 551.30(B) covers overcurrent protection for the generator, neither of which govern the supply conductor wiring method.
Multi-Circuit Branch Arrangements and Energy Management
NEC 551.42(C) An RV can have up to five 15/20 A circuits on a 30 A system freely, but a sixth circuit requires either an energy management system or that it serve only the power converter.
Q21 NEC 551.42(C)
An RV manufacturer wants to add a sixth 15- or 20-ampere branch circuit to a 30-ampere system without installing a listed energy management system. Under what condition is this permitted?
- A If appliance isolation switching is installed on the first five circuits
- B If the sixth circuit serves only lighting outlets
- C If the sixth circuit serves only the power converter and total load stays within the original five-circuit design
- D If the panelboard is upgraded to 40-ampere rated
Show answer & explanation
Correct: C — If the sixth circuit serves only the power converter and total load stays within the original five-circuit design
Per 551.42(C), a sixth circuit is allowed without an energy management system only if it serves solely the power converter and the combined load of all six circuits doesn't exceed what the original five circuits were designed for. Restricting the sixth circuit to lighting, upgrading to a 40-ampere panelboard, or adding isolation switching to the existing five circuits are not the exception described in the section.
Neutral conductor sizing and surge protection on RV feeders
NEC 551.72(D) RV feeder neutrals can only be downsized below the ungrounded conductors for 240-volt line-to-line permanent loads, and each RV gets power from just one 30-amp or 50-amp cord.
Q22 NEC 551.72(D)
According to 551.72(F), how may a recreational vehicle be powered?
- A By one 30-ampere or one 50-ampere external power supply cord only
- B By a 15- or 20-ampere convenience receptacle cord in place of the rated supply cord
- C By any combination of 30-ampere and 50-ampere cords needed to meet the load
- D By one external power supply cord, plus a second cord for air conditioning loads
Show answer & explanation
Correct: A — By one 30-ampere or one 50-ampere external power supply cord only
551.72(F) requires each recreational vehicle to be powered by only one 30-ampere or one 50-ampere external power supply cord — not a combination, and not a second cord for specific loads. The informational note clarifies the 15/20-ampere convenience receptacle on the RV supply equipment is still allowed, but it doesn't substitute for the single rated supply cord.
Neutral Conductor Isolation from Ground at RV Panelboard
NEC 551.54(C) In an RV, the neutral must stay fully isolated from ground and the equipment enclosure — no bonding jumpers, no bonding screws, no shared terminals.
Q23 NEC 551.54(C)
During an RV panelboard inspection, the electrician finds a bonding screw connecting the neutral bus to the enclosure. What should be done?
- A Tighten it to ensure a low-impedance ground-fault path
- B Leave it in place since RV panelboards are treated like a service
- C Replace it with a bonding jumper rated for the panel
- D Remove and discard the bonding screw
Show answer & explanation
Correct: D — Remove and discard the bonding screw
Per 551.54(C), bonding screws, straps, or buses in the panelboard or in appliances shall be removed and discarded, because the RV panelboard is not a service — the neutral-ground bond exists only at the shore supply. Treating it like a service panel or reinforcing the bond creates an improper parallel neutral-ground path.
Panelboard Location and Working Clearance
NEC 551.45(B) The RV panelboard needs 24 in. wide by 30 in. deep working clearance in setup mode, reducible to 22 in. on one dimension only if the cover sits in the aisle.
Q24 NEC 551.45(B)
An RV panelboard cover sits flush with the aisle wall, within 40 mm of the finished aisle surface. What working clearance rule applies?
- A No reduction is allowed because the panelboard is enclosed
- B One dimension of working clearance may be reduced to 550 mm (22 in.)
- C Both dimensions may be reduced to 550 mm (22 in.)
- D The full 750 mm (30 in.) depth must still be met on all sides
Show answer & explanation
Correct: B — One dimension of working clearance may be reduced to 550 mm (22 in.)
Per 551.45(B), a panelboard is considered exposed when its cover is within 50 mm (2 in.) of the aisle's finished surface, which is the case here at 40 mm. That allows only one of the two working clearance dimensions to be reduced to 550 mm (22 in.) — not both, and not a blanket exemption from clearance.
Minimum Power-Supply Cord Length
NEC 551.46(B) RV shore power cords need at least 7.5 m (25 ft) for side entry or 9.0 m (30 ft) for rear entry, measured plug-face to plug-face, with extra length added for entry points above 900 mm (3 ft).
Q25 NEC 551.46(B)
Under 551.46(B), how is the exposed usable length of an RV power-supply cord measured?
- A From the point of entrance on the vehicle exterior to the face of the attachment plug at the supply end
- B From the main panelboard inside the vehicle to the face of the attachment plug
- C From the point of entrance to the nearest receptacle outlet inside the vehicle
- D From the cord's overall manufactured length label, regardless of routing
Show answer & explanation
Correct: A — From the point of entrance on the vehicle exterior to the face of the attachment plug at the supply end
551.46(B) defines usable length as measured from the point of entrance to the vehicle (or the flanged surface inlet face) to the face of the attachment plug at the supply end. Measuring from an interior panelboard, a receptacle, or relying on a manufactured length label doesn't reflect the actual usable reach of the cord.
Required Warning Label at Power-Supply Entrance
NEC 551.46(D) Every RV needs a WARNING label at the power-cord entrance point, in specified letter sizes, with the exact ampere rating filled in.
Q26 NEC 551.46(D)
Where does 551.46(D) require the RV power-supply warning label to be located?
- A On the exterior skin, at or near the power-supply cord entrance point
- B Inside the main distribution panel cover
- C Inside the cord storage compartment only
- D Next to the RV's data/rating plate at the front bulkhead
Show answer & explanation
Correct: A — On the exterior skin, at or near the power-supply cord entrance point
551.46(D) requires the label be affixed to the exterior skin, at or near the point of entrance of the power-supply cord(s). The panel cover, data plate location, and cord storage compartment are not the specified placement under this section.
Power-Supply Entrance Point Location on the Vehicle
NEC 551.46(E) The power-supply assembly enters within 15 ft of the rear on the left (road) side, within 18 in. of the outside wall, unless a listed drain exception or livestock design applies.
Q27 NEC 551.46(E)
Under 551.46(E), where is the default location for an RV's power-supply assembly entrance point?
- A Within 10 ft of the rear, on either side, within 18 in. of the outside wall
- B Within 15 ft of the front, on the right (curb) side, within 18 in. of the outside wall
- C Within 15 ft of the rear, on the left (road) side, within 18 in. of the outside wall
- D Anywhere along the left side, provided it is within 24 in. of the floor line
Show answer & explanation
Correct: C — Within 15 ft of the rear, on the left (road) side, within 18 in. of the outside wall
551.46(E) sets the default entrance point within 4.5 m (15 ft) of the rear, on the left (road) side, within 450 mm (18 in.) of the outside wall. The front-right option and the 10 ft/either-side option reverse or shrink these specific dimensions.
Prewiring Provisions for Future AC, Generator, or Appliance Circuits
NEC 551.47(Q) Spare circuits left prewired for future AC, generator, or appliance use must have finished overcurrent protection, capped conductors in a covered box, and a WARNING label stating the max amperage.
Q28 NEC 551.47(Q)
An RV manufacturer prewires a circuit for a future air-conditioning installation per 551.47(Q). Which of the following is required?
- A The conductors may be left uncapped inside the junction box as long as the cover is blank
- B The circuit may also power a spare receptacle outlet as long as it's labeled
- C The overcurrent protective device is installed and wired in the panelboard even though no air conditioner is connected yet
- D The marked ampere rating on the label may equal the full circuit rating
Show answer & explanation
Correct: C — The overcurrent protective device is installed and wired in the panelboard even though no air conditioner is connected yet
551.47(Q)(1) requires the overcurrent protective device to be installed in the panelboard with wiring connections completed, even before the air conditioner exists. The circuit must serve no other purpose per 551.47(Q)(4), free conductor ends must be capped or taped per 551.47(Q)(2), and the marked rating cannot exceed 80% of the circuit rating per 551.47(Q)(3).
Required Receptacle Outlet Spacing and Locations
NEC 551.41(A) In RVs, no floor point along a wall space 2 ft or wider can be more than 6 ft from a receptacle, plus specific receptacles are required at counters, the fridge/range, and rooftop decks.
Q29 NEC 551.41(A) Code lookup
You're wiring an RV and laying out receptacles along a living-area wall that runs continuously for 10 ft with no cabinets or built-in furniture. Which section tells you the maximum distance along the floor line between receptacle outlets in that wall space?
- A 551.41(B)
- B 551.40(A)
- C 551.42(C)
- D 551.41(A)
Show answer & explanation
Correct: D — 551.41(A)
551.41(A) sets the 1.8 m (6 ft) spacing rule so no point on a qualifying wall space is more than 6 ft from an outlet. 551.41(B) instead lists specific required locations like countertops and the refrigerator space, which is a different requirement than general spacing.
Switch Placement Restriction in Wet Locations
NEC 551.51(B) A switch can't be mounted in the wet location of an RV tub or shower space unless it's built into a listed tub or shower assembly.
Q30 NEC 551.51(B)
Under 551.51(B), when is a switch permitted to be installed within the wet location of an RV tub or shower space?
- A When the switch is mounted on the wall opposite the showerhead
- B When the switch is listed for wet locations
- C When the switch is GFCI-protected
- D When the switch is installed as part of a listed tub or shower assembly
Show answer & explanation
Correct: D — When the switch is installed as part of a listed tub or shower assembly
551.51(B) allows a switch in the wet location of a tub or shower space only when it's installed as part of a listed tub or shower assembly — the assembly itself is tested and certified as a unit. A wet-location-rated switch alone doesn't meet this, GFCI protection addresses shock risk but not the location restriction, and there's no exception based on wall placement relative to the showerhead. See 551.51(B).
Underground conductor installation and physical protection
NEC 551.80 Direct-buried conductors at RV sites must be insulated and identified for the use, spliced only in approved boxes, and sleeved in rigid protection for at least 18 in. above grade wherever they leave the trench.
Q31 NEC 551.80
An aluminum equipment grounding conductor is being direct-buried to serve an RV site feeder circuit. What does 551.80(A) require of it?
- A It must be upsized one wire gauge in lieu of insulation
- B It must be insulated and identified for the use, the same as any other direct-burial conductor
- C It may be bare, since equipment grounding conductors are exempt from insulation requirements
- D It only needs insulation if run in the same trench as ungrounded conductors
Show answer & explanation
Correct: B — It must be insulated and identified for the use, the same as any other direct-burial conductor
551.80(A) specifically calls out that the equipment grounding conductor, if aluminum, must be insulated and identified for the use — closing off the common assumption that grounding conductors can be bare underground.
Sizing alternate/external power feeders above and at 30A
NEC 551.31(C) Above 30 A the alternate source can be wired 120V, 208Y/120V, or 120/240V with a properly rated feeder OCPD; the external feeder assembly itself can be undersized for the calculated load but never below 30 A.
Q32 NEC 551.31(C)
A calculated load for an external feeder assembly comes out to 42 amperes, but the installer wants to use a smaller assembly to save cost. Per 551.31(D), what is the smallest ampacity permitted?
- A 30 amperes
- B The assembly must always match the full 42-ampere calculated load
- C 20 amperes
- D 15 amperes, matching the smallest standard OCPD
Show answer & explanation
Correct: A — 30 amperes
551.31(D) allows the external feeder assembly to be sized below the calculated load, but never less than 30 amperes. 20 A and 15 A fall below that floor, and the section explicitly permits going under the calculated load, so matching the full 42 A figure isn't required.
Preventing simultaneous connection of alternate and outside AC sources
NEC 551.33 Transfer equipment must make it physically impossible for shore power and an onboard AC source to feed the RV's wiring at the same time.
Q33 NEC 551.33
Under 551.33, what is the core function transfer equipment must ensure in an RV's ac supply system?
- A That the generator always starts before shore power is disconnected
- B That a ground-fault circuit interrupter is installed ahead of the transfer switch
- C That shore power and an alternate ac source are never connected to the vehicle circuit at the same time
- D That both ac sources can supply the vehicle circuit together to prevent power loss
Show answer & explanation
Correct: C — That shore power and an alternate ac source are never connected to the vehicle circuit at the same time
551.33 requires transfer equipment to ensure that current-carrying conductors from another ac source and from an outside source are not connected to the vehicle circuit at the same time. Allowing both sources to feed the circuit together, or sequencing generator start-up, does not address the core hazard this section targets; GFCI protection is a separate requirement not covered here.
Grounding of Cord-and-Plug-Connected Appliances
NEC 551.55(F) Cord-connected appliances in RVs and parks — washers, dryers, refrigerators, gas range electrical systems — must ground through the cord's equipment grounding conductor and a grounding-type plug.
Q34 NEC 551.55(F) Code lookup
A homeowner's clothes dryer is cord-and-plug connected in a laundry room. Which section specifies how this cord-connected appliance must be grounded?
- A 551.55(A)
- B 551.56(A)
- C 551.55(F)
- D 551.54(A)
Show answer & explanation
Correct: C — 551.55(F)
551.55(F) specifically addresses cord-connected appliances like washing machines and clothes dryers, requiring an approved cord with equipment grounding conductor and grounding-type attachment plug. 551.55(A) covers exposed metal parts generally, and 551.54(A) covers power-supply grounding for the RV's electrical system, not individual cord-connected appliances.
Attachment Plug Type Required by System Amperage
NEC 551.46(C) The RV's branch-circuit setup fixes its attachment plug: 15 A and 20 A units use 2-pole 3-wire 125 V plugs, five-circuit units use a 30 A 125 V plug, and 50 A units need a 3-pole 4-wire 125/250 V plug.
Q35 NEC 551.46(C)
Why does 551.46(C)(4) require a 3-pole, 4-wire attachment plug for a 50-ampere RV power-supply assembly, unlike the 2-pole plugs used at lower amperages?
- A Because 50-ampere loads always require a four-wire feeder regardless of voltage
- B Because NEMA WD 6 requires all plugs rated above 20 amperes to use four wires
- C Because the 30-ampere plug configuration cannot physically be rated above 30 amperes
- D Because the plug is rated 125/250 volts and must carry both ungrounded conductors plus a neutral and equipment ground
Show answer & explanation
Correct: D — Because the plug is rated 125/250 volts and must carry both ungrounded conductors plus a neutral and equipment ground
551.46(C)(4) specifies a 3-pole, 4-wire grounding-type plug rated 50 A, 125/250 V because that supply provides two ungrounded conductors, a grounded (neutral) conductor, and an equipment grounding conductor — the 125/250 V dual-voltage supply is what drives the extra pole and wire, not amperage alone or a blanket NEMA rule.
Combination AC/DC systems: general wiring rules
NEC 551.20(A) DC vehicle wiring can share a system with a 120-volt source only if the whole system meets the 120-volt Part I–V rules, and transformer-fed AC circuits can never feed DC appliances.
Q36 NEC 551.20(A)
Under 551.20(A), when is dc vehicle wiring permitted to be connected to a 120-volt source?
- A Only when a licensed electrician certifies the DC wiring separately
- B When the DC system is rated for at least 120 volts
- C When the entire wiring system and equipment are rated and installed in full conformity with the 120-volt requirements of Parts I through V of Article 551
- D When the DC and 120-volt systems are installed in separate compartments of the vehicle
Show answer & explanation
Correct: C — When the entire wiring system and equipment are rated and installed in full conformity with the 120-volt requirements of Parts I through V of Article 551
551.20(A) permits connecting dc vehicle wiring to a 120-volt source only if the entire wiring system and equipment conform fully to Parts I–V of Article 551 covering 120-volt electrical systems. Separate compartments, a higher DC voltage rating, or electrician sign-off are not the conditions the rule sets — the requirement is full conformity of the whole system to the 120-volt rules.
Bonding the voltage converter enclosure to the chassis
NEC 551.20(C) The converter's metal enclosure needs its own minimum 8 AWG copper bonding conductor to the vehicle frame, and that conductor can never double as a current-carrying conductor.
Q37 NEC 551.20(C)
In a recreational vehicle, what is the minimum size and material required for the conductor bonding a voltage converter's metal enclosure to the vehicle frame?
- A 8 AWG aluminum
- B 10 AWG copper
- C 12 AWG copper
- D 8 AWG copper
Show answer & explanation
Correct: D — 8 AWG copper
551.20(C) requires a minimum 8 AWG copper conductor to bond the voltage converter's non-current-carrying metal enclosure to the vehicle frame. The 10 AWG and 12 AWG copper options are undersized, and the rule specifies copper, not aluminum.