Free NEC practice test · Article 552

Park Trailers practice questions

A free NEC Article 552 practice test for the journeyman exam: 37 questions on Park Trailers, each with the answer and the why behind it.

37 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 37 journeyman-exam practice questions cover NEC Article 552 across 37 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Cable Securing & Physical Protection

NEC 552.48(H)

Support cable within 300 mm (12 in.) of boxes and every 1.4 m (4 1/2 ft) after that, and armor it with steel plates or tubing anywhere a stud leaves less than 32 mm (1 1/4 in.) of cover.

Q1 NEC 552.48(H)

Cable is secured with a cable clamp entering a splice box on an appliance. How close to the box must the cable be secured, per 552.48(H)?

  1. A Within 1.4 m (4 1/2 ft)
  2. B No specific distance, only the 1.4 m (4 1/2 ft) general interval applies
  3. C Within 300 mm (12 in.)
  4. D Within 200 mm (8 in.)
Show answer & explanation

Correct: C — Within 300 mm (12 in.)

552.48(H) sets the 300 mm (12 in.) securing distance for cable connected with clamps or connectors at outlet boxes, panelboards, and splice boxes on appliances. The 200 mm (8 in.) distance is a separate rule under 552.48(I) for nonmetallic boxes without clamps, and 1.4 m (4 1/2 ft) is the general interval for support elsewhere along the run.

Physical protection and splicing of low-voltage wiring

NEC 552.10(C)(1)

Secure and shield every conductor from damage, and make every splice mechanically sound before it's ever soldered or covered.

Q2 NEC 552.10(C)(1)

An insulated conductor is clamped directly to a structural member. Per 552.10(C)(1), what is required?

  1. A Replacing the clamp with a jacketed-cable-rated clamp only
  2. B A minimum 6 in. slack loop at every clamp point
  3. C Nothing extra, since the clamp itself provides adequate protection
  4. D An additional wrap or layer of equivalent insulating material at the clamp
Show answer & explanation

Correct: D — An additional wrap or layer of equivalent insulating material at the clamp

552.10(C)(1) requires that where insulated conductors are clamped to the structure, the insulation be supplemented with an additional wrap or layer of equivalent material — because the clamp point is a wear spot. This doesn't apply to jacketed cable, which is specifically exempted, and there's no slack-loop requirement in this section.

Standard Load Calculation Method

NEC 552.47(B)

Park trailer feeder and cord sizing uses its own demand method — lighting/small-appliance load plus nameplate motor and appliance loads, not the Article 220 dwelling method.

Q3 NEC 552.47(B)

Which calculation procedure applies when sizing the supply cord and distribution panelboard for a park trailer?

  1. A The optional method in Article 220
  2. B The standard method in Article 220
  3. C Whichever of the Article 220 methods yields the lower demand
  4. D The dedicated method in 552.47, in lieu of Article 220
Show answer & explanation

Correct: D — The dedicated method in 552.47, in lieu of Article 220

552.47 states its method is used 'in lieu of the procedure shown in Article 220' for park trailer feeder assemblies — Article 220's standard and optional methods don't apply here.

Additional Small-Appliance Circuits

NEC 552.46(B)(2)

A park trailer's small-appliance branch circuits must meet the same dwelling-unit standard as a house — at least two dedicated 20-ampere circuits under 210.11(C)(1), as required by 552.46(B)(2).

Q4 NEC 552.46(B)(2)

A park trailer's kitchen wiring is being inspected. Which arrangement satisfies the small-appliance branch-circuit requirement referenced in 552.46(B)(2)?

  1. A Two 15-ampere circuits split between the kitchen and the bathroom
  2. B One 20-ampere circuit serving both the kitchen countertop receptacles and the kitchen ceiling light
  3. C Two dedicated 20-ampere circuits serving only the kitchen countertop and dining receptacles
  4. D One 15-ampere circuit serving the kitchen countertop receptacles
Show answer & explanation

Correct: C — Two dedicated 20-ampere circuits serving only the kitchen countertop and dining receptacles

552.46(B)(2) requires park trailer small-appliance circuits to meet 210.11(C)(1): at least two 20-ampere circuits dedicated to kitchen/dining-area receptacles, with no lighting or other outlets sharing the circuit. Mixing in a ceiling light, dropping to 15 amperes, or routing one circuit to the bathroom all fail that standard.

Base Allowance: Up to Five 15/20A Circuits

NEC 552.46(A)

A park trailer gets up to five 15- or 20-ampere circuits on a 30-ampere feeder without any load calculation — go past that and you need an energy management system or the special sixth-circuit exception.

Q5 NEC 552.46(A)

Under 552.46(A), what is the maximum number of 15- or 20-ampere branch circuits permitted to supply lights, receptacle outlets, and fixed appliances in a park trailer, without invoking any special exception?

  1. A Three
  2. B Four
  3. C Five
  4. D Six
Show answer & explanation

Correct: C — Five

552.46(A) sets the base allowance at a maximum of five 15- or 20-ampere circuits. Six circuits are only permitted under the specific power-converter exception, not as the general base rule.

Box Material & Mounting Requirements

NEC 552.48(E)

Nonmetallic boxes in park trailers are only allowed with nonmetallic-sheathed cable or nonmetallic raceway, and boxes in combustible walls must sit flush or proud of the surface.

Q6 NEC 552.48(E) Code lookup

A manufactured home wall is finished with combustible wood paneling, and there's no framing member behind the desired outlet location. The electrician plans to attach a wooden mounting plate directly to the wall panel to serve as backing for the outlet box. Which section specifies the minimum width and thickness this wooden plate must have to be an approved mounting method?

  1. A 552.48(C)
  2. B 552.48(D)
  3. C 552.48(E)
  4. D 552.48(J)
Show answer & explanation

Correct: C — 552.48(E)

552.48(E) sets the wooden-plate backing method (38 mm minimum width, 13 mm minimum thickness) as an approved way to mount outlet boxes without direct framing support. 552.48(D) only addresses how flush boxes must sit relative to combustible wall/ceiling surfaces, not backing/mounting hardware.

Branch-Circuit Overcurrent Device Sizing

NEC 552.42(A)

Park trailer branch-circuit protection follows conductor ampacity by default, but a single 13.3 A+ appliance can go up to 150%, and motor-driven equipment follows its own nameplate marking.

Q7 NEC 552.42(A)

A park trailer appliance rated 13.3 amperes is supplied by its own individual branch circuit. Per 552.42(A), what is the maximum branch-circuit overcurrent device rating allowed relative to the appliance's rating?

  1. A 125 percent of the appliance rating
  2. B 200 percent of the appliance rating
  3. C 150 percent of the appliance rating
  4. D 100 percent of the appliance rating
Show answer & explanation

Correct: C — 150 percent of the appliance rating

552.42(A)(2) permits branch-circuit overcurrent devices up to 150 percent of the rating for a single appliance rated 13.3 A or more supplied by an individual branch circuit. Matching the conductor ampacity exactly (100 percent) is the general default rule, not the exception for this scenario, and 200 percent or 125 percent are not the figure this section specifies.

Bonding to the Park Trailer Chassis

NEC 552.57(B)

Every park trailer needs a minimum 8 AWG copper bonding conductor from the panelboard to an accessible chassis terminal, unless the chassis is already bolted, welded, or riveted to the panelboard.

Q8 NEC 552.57(B)

A park trailer has a bolt-on metal chassis-frame, and the panelboard is fastened to it with bolts and nuts. What is the minimum bonding conductor required between the panelboard and the chassis?

  1. A 8 AWG copper minimum, insulated only
  2. B 6 AWG copper minimum, bare or insulated
  3. C 10 AWG copper minimum, solid only
  4. D No separate bonding conductor is required because the bolted connection is considered bonded
Show answer & explanation

Correct: D — No separate bonding conductor is required because the bolted connection is considered bonded

Per 552.57(B), a park trailer with a unitized metal chassis-frame construction where the panelboard is securely fastened with bolts and nuts, welding, or riveting is considered to be bonded — no additional bonding conductor is required. The 8 AWG copper minimum requirement in 552.57(C) applies only when a separate bonding conductor is installed.

Sizing and listing requirements for 120V-to-low-voltage converters

NEC 552.20(B)

Size a 12-volt converter with the tiered rule — first 20 A at 100%, next 20 A at 50%, everything above 40 A at 25% — and it must be listed with over-temperature protection.

Q9 NEC 552.20(B)

When sizing a 120-volt to 12-volt dc converter under 552.20(B), what percentage of connected load applies to the portion between 20 and 40 amperes?

  1. A 25 percent
  2. B 100 percent
  3. C 80 percent
  4. D 50 percent
Show answer & explanation

Correct: D — 50 percent

552.20(B) applies 100 percent to the first 20 amperes, 50 percent to the second 20 amperes (the 20-40 A band), and 25 percent to everything above 40 amperes. 100 percent and 25 percent belong to the other two tiers, and 80 percent isn't part of this method at all.

Power-Supply Cord Length Rules

NEC 552.44(B)

A park trailer's power-supply cord must be at least 7.0 m (23 ft) for side entry or 8.5 m (28 ft) for rear entry, capped at 11 m (36 ft), with extra length added for high entry points.

Q10 NEC 552.44(B) Code lookup

A park trailer's power-supply cord enters the unit at the rear, at a point 900 mm (3 ft) above ground. Which section specifies the minimum exposed usable cord length required for this installation?

  1. A 552.44(E)
  2. B 552.44(C)(2)
  3. C 552.44(B)
  4. D 552.43(B)
Show answer & explanation

Correct: C — 552.44(B)

552.44(B) sets the minimum exposed usable cord length (7.0 m side entry, 8.5 m rear entry) and how to measure it, including the added length required when entry height exceeds 900 mm. 552.43(B) only addresses general power-supply cord requirements, not the length measurement rules, and 552.44(C)(2) covers attachment plug ratings, not cord length.

Electrical Entrance Warning Label

NEC 552.44(D)

Every park trailer needs a WARNING label at the feeder entrance point stating the exact voltage, wire configuration, and ampere rating of the supply.

Q11 NEC 552.44(D)

Where does 552.44(D) require the electrical entrance safety label to be affixed on a park trailer?

  1. A On the tongue jack near the hitch
  2. B Inside the entrance door on the interior wall
  3. C Inside the main electrical panel cover
  4. D On the exterior skin, at or near the point of entrance of the feeder assembly
Show answer & explanation

Correct: D — On the exterior skin, at or near the point of entrance of the feeder assembly

552.44(D) requires the label on the exterior skin, at or near the point of entrance of the feeder assembly, so it's visible before the connection is made. The panel cover, hitch area, and interior wall are not the required location.

Expandable Unit: Cord-and-Plug Connection

NEC 552.48(O)(1)

A park trailer's expandable (slide-out) unit may connect to the main body's branch circuit with a listed hard-usage cord and plug, but outdoor receptacles need GFCI and wet-location listing, and no live plug pins can ever be exposed.

Q12 NEC 552.48(O)(1)

The receptacle used to connect an expandable unit's cord to the main circuit is mounted on the outside of the park trailer. What does 552.48(O)(1)(b) require?

  1. A GFCI protection for personnel and a wet-locations listing
  2. B A wet-locations listing only, since park trailors don't require GFCI outdoors
  3. C AFCI protection for personnel and a damp-locations listing
  4. D GFCI protection only, with no specific location listing required
Show answer & explanation

Correct: A — GFCI protection for personnel and a wet-locations listing

552.48(O)(1)(b) requires the outdoor receptacle to be GFCI-protected for personnel and listed for wet locations — both conditions together, not one or the other. AFCI and damp-location listing are not what this section specifies.

GFCI Protection for RV Receptacles

NEC 552.41(C)

In a recreational vehicle, every 125-volt 15- or 20-amp receptacle at the countertop, near water, or outside needs GFCI protection, with one narrow access-panel exception.

Q13 NEC 552.41(C)

In a recreational vehicle, which receptacle location is NOT required to have GFCI protection under 552.41(C)?

  1. A A receptacle located inside an exterior access panel that supplies an installed appliance
  2. B A receptacle on the exterior of the unit
  3. C A receptacle serving a kitchen countertop surface
  4. D A receptacle within 6 ft of a bathroom lavatory
Show answer & explanation

Correct: A — A receptacle located inside an exterior access panel that supplies an installed appliance

552.41(C) carves out one exception: receptacles behind an exterior access panel that supply an installed appliance. Countertop, exterior, and within-6-ft-of-lavatory receptacles are all on the required list with no such carve-out.

Grounded Conductor Insulation & Bonding Screw Removal

NEC 552.55(C)

In a park trailer, the grounded conductor must stay fully isolated from grounding conductors and enclosures, so panelboard bonding screws come out and range/dryer cords need 4 wires.

Q14 NEC 552.55(C)

Per 552.55(C), what must be done with bonding screws, straps, or buses found in a park trailer's panelboard?

  1. A Removed and discarded
  2. B Removed only if the trailer has a sub-panel
  3. C Replaced with insulated bonding jumpers rated for the panel
  4. D Left in place to bond the neutral and ground, as required at a service disconnect
Show answer & explanation

Correct: A — Removed and discarded

552.55(C) requires bonding screws, straps, or buses in the panelboard or in appliances to be removed and discarded, since the park trailer panelboard is not service equipment. The neutral-to-ground bond happens upstream at the service, so treating the trailer panel like a service disconnect (where bonding is required) is the wrong-rule confusion here.

Approved Equipment Grounding Connection Methods

NEC 552.56(C)

In park trailers and RVs, equipment grounding relies on approved metal-to-metal connections or a dedicated grounding screw — never a shared mounting screw.

Q15 NEC 552.56(C)

An electrician is bonding an equipment grounding conductor inside a metal outlet box. Which method is acceptable per 552.56(C)?

  1. A Securing the conductor under the same screw that holds the device mounting strap
  2. B Twisting the conductor around a cover screw before the cover is installed
  3. C Using a grounding screw dedicated to that purpose only, or a listed grounding device
  4. D Relying on friction contact between the conductor and the box wall
Show answer & explanation

Correct: C — Using a grounding screw dedicated to that purpose only, or a listed grounding device

552.56(C)(2) requires a grounding screw used for no other purpose, or a listed grounding device. Using a mounting or cover screw for double duty, or relying on friction contact, does not meet this requirement.

Kitchen Countertop Receptacle Location

NEC 552.41(B)

Every 12-inch-or-larger park trailer countertop needs a receptacle within a 6-ft cord reach that doesn't cross the sink, a cooking appliance, or a traffic area.

Q16 NEC 552.41(B) Code lookup

A residential kitchen has a long run of countertop on both sides of the sink, each section at least 15 inches wide and deep. Which section specifies that a receptacle outlet must be located on each side of the sink under these conditions?

  1. A 552.41(C)
  2. B 552.41(F)
  3. C 552.41(B)
  4. D 552.41(A)
Show answer & explanation

Correct: C — 552.41(B)

552.41(B) is the Location subsection listing the specific placements required, including a receptacle on each side of the sink when countertops of 12 in. or more in width and depth flank it. 552.41(A) only governs spacing between receptacles, not where the sink-adjacent ones must go, and 552.41(F) covers where receptacles are prohibited.

Luminaires in Shower & Outdoor Locations

NEC 552.54(B)

A luminaire over a shower or tub must be enclosed, gasketed, listed, and GFCI-protected; an outdoor luminaire just needs a listing for outdoor or wet locations.

Q17 NEC 552.54(B)

Which set of requirements applies to a luminaire installed over a bathtub or within a shower stall?

  1. A Listed for damp locations only, with no GFCI protection required
  2. B GFCI-protected only, with no specific enclosure requirement
  3. C Listed for outdoor use, matching the requirement for exterior luminaires
  4. D Enclosed and gasketed, listed for the installation, and GFCI-protected
Show answer & explanation

Correct: D — Enclosed and gasketed, listed for the installation, and GFCI-protected

552.54(B) requires all three together: enclosed and gasketed construction, a listing for that installation, and GFCI protection. The outdoor-use listing belongs to exterior equipment under 552.54(C), not to shower or tub luminaires.

Low-voltage conductor material and type requirements

NEC 552.10(B)(2)

Low-voltage conductors must be stranded copper of a listed SAE type (GXL, HDT, SXL, SGT, SGR) or equivalent Table 310.4(1) insulation.

Q18 NEC 552.10(B)(2)

Per 552.10(B)(1), which conductor material is required for low-voltage circuits?

  1. A Either copper or aluminum, contractor's choice
  2. B Aluminum, provided it is properly terminated
  3. C Copper
  4. D Copper-clad aluminum
Show answer & explanation

Correct: C — Copper

552.10(B)(1) states copper conductors shall be used for low-voltage circuits — no allowance for aluminum or copper-clad aluminum is given in this section.

Overcurrent protection rating and device type for LV circuits

NEC 552.10(E)(1)

Overcurrent protection for low-voltage park trailer wiring must be rated no higher than the copper conductor's ampacity per Table 552.10(E)(1), using approved breakers or fuses — automotive types included.

Q19 NEC 552.10(E)(1)

A park trailer's 12-volt DC circuit uses copper conductors. Per 552.10(E)(1), how must the overcurrent protective device be rated relative to those conductors?

  1. A Rated to match the AC service disconnect rating
  2. B Rated at least 125% of the conductor ampacity
  3. C Rated not in excess of the conductor ampacity
  4. D Rated per the appliance nameplate only, regardless of conductor size
Show answer & explanation

Correct: C — Rated not in excess of the conductor ampacity

552.10(E)(1) requires the OCPD rating to not exceed the copper conductor's ampacity from Table 552.10(E)(1). The 125% figure is a continuous-load/motor sizing rule that doesn't apply here, and matching the AC service disconnect or relying only on the appliance nameplate ignores the conductor-based sizing this section requires.

Outdoor Equipment Listing Requirements

NEC 552.59(A)

Every outdoor fixture and piece of equipment on a park trailer must be listed for outdoor use, and receptacles and switches/breakers each carry their own extra rule on top of that.

Q20 NEC 552.59(A) Code lookup

A mobile home has an exterior wall-mounted luminaire installed on the outside of the unit. Which section requires that this fixture be listed specifically for outdoor use?

  1. A 552.59(A)
  2. B 552.54(A)
  3. C 552.59(B)
  4. D 552.57(D)
Show answer & explanation

Correct: A — 552.59(A)

552.59(A) is the section that requires outdoor fixtures, luminaires, and equipment to be listed for outdoor use. 552.54(A) covers luminaires generally (not specifically the outdoor-listing requirement), and 552.57(D) deals with bonding of the metallic roof/exterior, not fixture listing.

Outdoor HVAC Branch Circuit & Warning Label

NEC 552.59(B)

A park trailer's branch circuit for outside heating or A/C equipment must end in a listed outdoor box or disconnect, with a specific warning label mounted within 150 mm (6 in.) of it.

Q21 NEC 552.59(B)

A park trailer has a branch circuit running outside to a separate air-conditioning unit (not a room air conditioner). Per 552.59(B), where must the branch-circuit conductors terminate?

  1. A In the park trailer's main service panel only
  2. B In a junction box inside the park trailer's utility closet
  3. C In a listed outlet box or disconnecting means located outside the park trailer
  4. D Spliced directly to the equipment's whip with no box or disconnect
Show answer & explanation

Correct: C — In a listed outlet box or disconnecting means located outside the park trailer

552.59(B) requires the conductors to terminate in a listed outlet box or disconnecting means located outside the park trailer, near the equipment — not inside at a utility closet, spliced bare, or back at the main panel.

Panelboard Working Clearance

NEC 552.45(B)

A park trailer panelboard needs 600 mm (24 in.) wide by 750 mm (30 in.) deep working clearance, reducible to 550 mm (22 in.) on one dimension only if the cover sits exposed to the aisle.

Q22 NEC 552.45(B)

Under 552.45(B), what is the minimum required working clearance in front of a park trailer panelboard when no exception applies?

  1. A 600 mm (24 in.) wide by 600 mm (24 in.) deep
  2. B 550 mm (22 in.) wide by 550 mm (22 in.) deep
  3. C 600 mm (24 in.) wide by 750 mm (30 in.) deep
  4. D 750 mm (30 in.) wide by 900 mm (36 in.) deep
Show answer & explanation

Correct: C — 600 mm (24 in.) wide by 750 mm (30 in.) deep

552.45(B) sets the baseline working clearance at 600 mm (24 in.) wide by 750 mm (30 in.) deep. The 750 mm (30 in.) by 900 mm (36 in.) option resembles general dwelling working-space figures but isn't what this section specifies. The 550 mm (22 in.) options only apply under the exposed-cover exception, and even then only one dimension reduces, not both.

Panelboard Main Disconnect Requirement

NEC 552.45(C)

A park trailer panelboard needs a main disconnect once it uses fuses or has more than two circuit breakers, and a main OCPD once it feeds more than two branch circuits.

Q23 NEC 552.45(C)

A park trailer panelboard has three circuit breakers and no fuses. Per 552.45(C), what is required?

  1. A A surge protective device ahead of the panelboard
  2. B A main disconnecting means
  3. C A ground-fault circuit interrupter on the feeder
  4. D No additional equipment, since fuses are not used
Show answer & explanation

Correct: B — A main disconnecting means

552.45(C) requires a main disconnecting means where more than two circuit breakers are employed, regardless of whether fuses are used. Three breakers exceeds that threshold, so a main disconnect is required.

Factory dielectric, continuity, and operational tests for park trailers

NEC 552.60(A)

Before it leaves the factory, every park trailer's 120/240-volt system must pass a dielectric test plus continuity, polarity, operational, and GFCI checks — and low-voltage circuits get their own late-stage operational test.

Q24 NEC 552.60(A)

During the required 1-minute dielectric strength test on a park trailer's 120/240-volt system, what voltage must be applied?

  1. A 1080 volts
  2. B 600 volts
  3. C 900 volts
  4. D 1200 volts
Show answer & explanation

Correct: C — 900 volts

Section 552.60(A) permits either a 1-minute test at 900 volts or a 1-second test at 1080 volts — the 1080-volt figure belongs to the shorter 1-second test, not the 1-minute test, so pairing it with 1 minute is a common mix-up.

Pipe heating cable outlet placement and circuit rules

NEC 552.41(D)

A park trailer's pipe heating cable outlet must sit within 2 ft of the cold water inlet, run on a GFCI-protected interior branch circuit, and can never double as the required outdoor receptacle.

Q25 NEC 552.41(D)

Which circuit is a pipe heating cable outlet in a park trailer permitted to be connected to?

  1. A The small-appliance branch circuit serving the kitchen
  2. B The same exterior circuit as the required outdoor receptacle
  3. C A dedicated feeder tapped ahead of the main disconnect
  4. D An interior branch circuit other than a small-appliance branch circuit
Show answer & explanation

Correct: D — An interior branch circuit other than a small-appliance branch circuit

552.41(D)(2) requires connection to an interior branch circuit other than a small-appliance branch circuit. The kitchen small-appliance circuit is specifically excluded, and the rule does not call for tying it to the outdoor receptacle circuit or a separate feeder ahead of the disconnect.

Power-Supply Cord Type & Construction

NEC 552.43(B)

A park trailer's power-supply cord must be a listed 30-A or 50-A cord, permanently attached at the panelboard with strain relief, ending in a molded-on cap — no pigtails, adapters, or extension cords.

Q26 NEC 552.43(B)

Which power-supply arrangement is permitted for a park trailer under 552.43(A)?

  1. A An extension cord rated for wet locations, in place of a listed power-supply cord
  2. B Two listed 30-ampere power-supply cords bundled together for redundancy
  3. C One listed 30-ampere or 50-ampere park trailer power-supply cord, or a permanently installed feeder
  4. D A listed power-supply cord fitted with an adapter to match the site receptacle
Show answer & explanation

Correct: C — One listed 30-ampere or 50-ampere park trailer power-supply cord, or a permanently installed feeder

552.43(A) permits not more than one listed 30-ampere or 50-ampere power-supply cord, or a permanently installed feeder. Using two cords, adding an adapter, or substituting an extension cord all violate the single-listed-cord requirement and the prohibition on adapters/extension cords in 552.43(B).

Prewiring for Future A/C or Appliance Circuits

NEC 552.48(P)

Prewired circuits in park trailers need a terminated OCPD, a capped junction box, and a WARNING label marked at 80% of circuit rating — and no other use.

Q27 NEC 552.48(P)

A park trailer is built with prewiring for a future air-conditioning installation. Which of the following is required at the load end of that circuit?

  1. A A switch box wired to the nearest lighting circuit as a temporary measure
  2. B The conductors left free inside the wall cavity for the installer to locate later
  3. C A receptacle outlet so the space can be used for other appliances until the A/C is installed
  4. D A junction box with a blank cover, with the conductor ends capped or taped
Show answer & explanation

Correct: D — A junction box with a blank cover, with the conductor ends capped or taped

552.48(P)(2) requires the load end of the prewired circuit to terminate in a junction box with a blank cover (or other listed enclosure), with the free conductor ends adequately capped or taped. Using the space for a receptacle or another circuit violates the requirement that the circuit serve no other purpose, and leaving conductors loose and uncapped is not permitted.

Receptacle Faceplate Requirements

NEC 552.48(K)

In a park trailer, metal receptacle faceplates must be grounded; nonmetallic ones don't carry that requirement.

Q28 NEC 552.48(K)

In a park trailer, a metal receptacle faceplate is being installed. Per 552.48(L), what additional requirement applies to it?

  1. A It must be bonded to the trailer chassis structural steel, separate from the equipment grounding conductor
  2. B It must be listed for wet locations
  3. C It must be secured with tamper-resistant cover screws
  4. D It must be grounded
Show answer & explanation

Correct: D — It must be grounded

552.48(L) requires that any metal faceplate installed on a park trailer receptacle be grounded — an unconditional rule. There's no separate wet-location listing requirement or distinct chassis-bonding path called out here; those are different requirements found elsewhere in the code.

General Receptacle Spacing (2-ft Wall Rule)

NEC 552.41(A)

In a park trailer, every wall space 2 ft or wider needs a receptacle within 6 ft of any point along the floor line, except bath and hallway areas.

Q29 NEC 552.41(A) Code lookup

You're wiring a manufactured home and checking the living room wall spaces for required receptacle outlets. One wall space is 30 in. (760 mm) wide. Which section tells you whether this wall space must have a receptacle outlet and, if so, how far any point along its floor line can be from that outlet?

  1. A 552.41(F)
  2. B 552.41(A)
  3. C 552.41(E)
  4. D 552.41(B)
Show answer & explanation

Correct: B — 552.41(A)

552.41(A) sets the 2 ft (600 mm) minimum wall-space width that triggers the requirement and the 6 ft (1.8 m) maximum floor-line distance to an outlet. 552.41(B) only addresses where outlets must be located once required, and 552.41(E)/(F) cover outdoor receptacles and prohibited locations, not general spacing.

Switch Ratings for Lighting & Motor Loads

NEC 552.52(A)

Lighting switches need a flat 10 A, 120/125 V minimum (never less than the connected load), while motor or other-load switches must have an ampere or horsepower rating that actually matches the load.

Q30 NEC 552.52(A) Code lookup

A manufactured home has a single-pole switch controlling a lighting circuit. The switch is rated 10 amperes at 120 volts, and the connected lighting load draws 8 amperes. Which section sets the minimum rating requirements for this switch?

  1. A 552.52(A)
  2. B 552.53
  3. C 552.52(C)
  4. D 552.52(B)
Show answer & explanation

Correct: A — 552.52(A)

552.52(A) specifically sets the minimum rating for switches on lighting circuits (10 A, 120/125 V, not less than the connected load). 552.52(B) instead covers switches for motors or other loads, and 552.53 covers receptacles, not switches.

Switch Location Restriction (Wet Areas)

NEC 552.52(C)

A switch can never sit inside a park trailer's tub or shower wet location unless it's built into a listed tub or shower assembly.

Q31 NEC 552.52(C) Code lookup

A tub/shower combo unit is being installed in a manufactured home bathroom. The electrician wants to mount a wall switch inside the tub/shower space itself. Under what condition, if any, is this permitted, and which section governs switch placement relative to wet tub or shower spaces?

  1. A 552.54(B)
  2. B 552.52(C)
  3. C 552.52(A)
  4. D 552.53
Show answer & explanation

Correct: B — 552.52(C)

552.52(C) is the specific rule prohibiting switches within wet locations in tub or shower spaces unless part of a listed tub/shower assembly. 552.52(A) only addresses switches controlling lighting circuits generally, not location within wet tub/shower spaces, and 552.54(B) governs shower luminaires, not switches.

Permitted Wiring Methods & Conduit Install

NEC 552.48(A)

Park trailer wiring uses standard cable and raceway articles with an equipment grounding means, and rigid/IMC conduit at a locknut-and-bushing termination always needs two locknuts.

Q32 NEC 552.48(A)

Under 552.48(A), how are cables and raceways from Articles 320, 322, 330–340, 342–362, 386, and 388 permitted to be installed in a park trailer?

  1. A In accordance with their applicable article, except as otherwise specified in Article 552
  2. B Only if double-insulated regardless of the method's own article requirements
  3. C Only when installed in a continuous metal raceway with no exceptions permitted
  4. D Only if reduced to 80% of their normal ampacity for mobile applications
Show answer & explanation

Correct: A — In accordance with their applicable article, except as otherwise specified in Article 552

552.48(A) permits these cables and raceways in accordance with their own applicable article, except as otherwise specified in Article 552. There is no blanket ampacity derating, no requirement to use only metal raceway, and no blanket double-insulation mandate imposed by this section.

Lighting circuit load formula for park trailers needing more than five circuits

NEC 552.46(B)(1)

Once a park trailer needs more than five branch circuits, lighting circuits are sized by 3 VA/ft² times outside dimensions (coupler excluded), divided by 120 volts.

Q33 NEC 552.46(B)(1)

Under 552.46(B)(1), which dimension of the park trailer is used in the lighting load formula?

  1. A The gross floor area including all built-in appliances
  2. B The interior floor area only
  3. C The outside dimensions of the park trailer, excluding the coupler
  4. D The outside dimensions of the park trailer, including the coupler
Show answer & explanation

Correct: C — The outside dimensions of the park trailer, excluding the coupler

552.46(B)(1) bases the lighting load on the park trailer's outside dimensions with the coupler excluded. Including the coupler, using interior floor area, or using gross floor area with appliances are not what the section specifies.

Attachment Plug Configuration by Ampacity

NEC 552.44(C)

A park trailer's attachment plug rating must match its feeder: 30 A units get a 2-pole 3-wire 125V plug, 50 A units get a 3-pole 4-wire 125/250V plug.

Q34 NEC 552.44(C)

A park trailer is wired with three 20-ampere branch circuits per 552.46(A). What attachment plug does 552.44(C)(1) require?

  1. A 2-pole, 3-wire grounding type, rated 30 amperes, 125 volts
  2. B 3-pole, 3-wire grounding type, rated 30 amperes, 125/250 volts
  3. C 2-pole, 3-wire grounding type, rated 20 amperes, 125 volts
  4. D 3-pole, 4-wire grounding type, rated 50 amperes, 125/250 volts
Show answer & explanation

Correct: A — 2-pole, 3-wire grounding type, rated 30 amperes, 125 volts

552.44(C)(1) requires a 2-pole, 3-wire grounding-type plug rated 30 amperes, 125 volts for units with two to five 15- or 20-ampere branch circuits. The 50-ampere 125/250-volt option applies only to units with a 50-ampere feeder assembly under 552.44(C)(2), and there's no 20-ampere or 125/250V variant of the 30-ampere plug.

Cable Sheath/Armor Continuity

NEC 552.48(F)

Nonmetallic sheath and metal-clad/AC armor must run unbroken between boxes — no exposed, cut, or spliced sheath in between.

Q35 NEC 552.48(F) Code lookup

A mobile home installer runs nonmetallic-sheathed cable from a junction box to an outlet box. Which section requires that the cable sheath remain unbroken and continuous between the two boxes?

  1. A 552.48(F)
  2. B 552.48(H)
  3. C 552.48(D)
  4. D 552.48(J)
Show answer & explanation

Correct: A — 552.48(F)

552.48(F) directly requires the sheath of NM cable (and the armor of AC/MC cable) to be continuous between outlet boxes and other enclosures. 552.48(H) covers cable supports and 552.48(J) covers physical damage protection — neither addresses sheath continuity.

Dual-voltage fixture listing and the ban on autotransformers

NEC 552.20(D)

Dual-voltage luminaires and appliances must be listed for both voltages, and autotransformers are never allowed in these systems.

Q36 NEC 552.20(D)

A luminaire in a park trailer has both a 120-volt connection and a low-voltage connection. Per 552.20(D), what must be true of this luminaire?

  1. A It must be wired as two separate independent fixtures
  2. B It must be supplied through an autotransformer
  3. C It must be listed for dual voltage
  4. D It only needs a standard 120-volt listing
Show answer & explanation

Correct: C — It must be listed for dual voltage

552.20(D) requires that fixtures or appliances with both 120-volt and low-voltage connections be listed for dual voltage. A standard 120-volt-only listing doesn't cover the combined-voltage hazard, and autotransformers are separately banned outright under 552.20(E), not required.

Keeping low-voltage and 120V receptacles/plugs non-interchangeable

NEC 552.20(F)

In park trailers, low-voltage and 120/240V receptacles and plug caps must use different configurations so they can never be cross-plugged.

Q37 NEC 552.20(F)

A park trailer has both a 120/240-volt ac system and a low-voltage system. Per 552.20(F), what is required of the receptacles and plug caps for each system?

  1. A Only the plug caps need differ; receptacles may be identical
  2. B They may be identical as long as each circuit is labeled
  3. C The low-voltage system's receptacles and plug caps must differ in configuration from the 120/240-volt system's
  4. D They must be color-coded but may share the same configuration
Show answer & explanation

Correct: C — The low-voltage system's receptacles and plug caps must differ in configuration from the 120/240-volt system's

552.20(F) requires that receptacles and plug caps of the low-voltage system differ in configuration from those of the 120-volt or 120/240-volt system, so they cannot be cross-plugged. Labeling or color-coding alone, per the option limiting the requirement to plug caps only, or the option allowing identical configurations, are all insufficient — the rule requires a physical, non-interchangeable configuration for both receptacles and plug caps.

Loomi · NEC exam prep