Free NEC practice test · Article 770

Optical Fiber Cables practice questions

A free NEC Article 770 practice test for the journeyman exam: 23 questions on Optical Fiber Cables, each with the answer and the why behind it.

23 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 23 journeyman-exam practice questions cover NEC Article 770 across 23 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Where to connect the entrance cable bonding conductor (intersystem bonding termination vs. alternatives)

NEC 770.100(B)

Always check for an intersystem bonding termination first — only fall back to the grounding-means list or a made electrode if one doesn't exist.

Q1 NEC 770.100(B)

A building has a properly installed intersystem bonding termination. Where must the communications circuit bonding conductor be connected?

  1. A To the nearest accessible point on the grounding electrode system
  2. B To the nonflexible metal power service raceway
  3. C To the intersystem bonding termination
  4. D To a dedicated driven ground rod installed for the communications system
Show answer & explanation

Correct: C — To the intersystem bonding termination

Per 770.100(B)(1), when an intersystem bonding termination exists, the bonding conductor must connect there. The grounding electrode system, service raceway, and dedicated rod are all 770.100(B)(2)/(B)(3) fallback options used only when no intersystem bonding termination is present.

Unlisted fiber cables entering buildings

NEC 770.48

An unlisted outside-plant fiber cable can run only 50 ft into a building before terminating in an enclosure, and it must stay out of risers and air-handling spaces unless routed in RMC or IMC.

Q2 NEC 770.48

An unlisted outside-plant optical fiber cable enters a building and is not enclosed in a raceway. What is the maximum length it may run inside the building from the point of entrance?

  1. A 15 m (50 ft)
  2. B 15 m (50 ft), but only if it terminates inside a riser
  3. C 3 m (10 ft)
  4. D There is no length limit as long as the cable is nonconductive
Show answer & explanation

Correct: A — 15 m (50 ft)

Under 770.48(A), an unlisted outside-plant fiber cable may run up to 15 m (50 ft) from its point of entrance before it must terminate in an enclosure. The no-limit option confuses this with 770.48(B)'s raceway permission, and the riser-termination option is wrong because 770.48(A) specifically excludes risers from this installation method.

Entrance cable bonding/grounding conductor: material, size, length, routing, protection

NEC 770.100(A)

The optical fiber entrance cable bonding/grounding conductor must be copper (or corrosion-resistant), 14 AWG to 6 AWG, as short and straight as practicable, and protected from physical damage.

Q3 NEC 770.100(A)

An electrician is selecting a bonding conductor for the metallic member of an optical fiber cable entering a dwelling. Which size is acceptable per 770.100(A)(3)?

  1. A 12 AWG aluminum
  2. B 4 AWG copper
  3. C 10 AWG copper
  4. D 16 AWG copper
Show answer & explanation

Correct: C — 10 AWG copper

770.100(A)(3) requires the bonding/grounding conductor to be not smaller than 14 AWG and never required larger than 6 AWG, so 10 AWG copper fits within that window. The 16 AWG option is smaller than the 14 AWG minimum, and while 4 AWG isn't prohibited outright, it's outside the typically expected sizing since the rule caps the requirement at 6 AWG (making anything larger unnecessary to specify as the 'required' answer here). 770.100(A)(2) also limits material to copper or other corrosion-resistant conductive material, which rules out aluminum-only options in this context.

Overhead fiber cable clearances and pole attachment rules

NEC 770.44(A)

Aerial fiber shares poles and spans with power conductors only if it stays below them, off the cross-arm, clear of climbing space, and separated by the 770.44(A)(4) minimums.

Q4 NEC 770.44(A)

Per 770.44(A)(4), what is the minimum separation required between a 0-750 volt overhead service conductor and an optical fiber cable service drop at any point in the span?

  1. A 1.0 m (40 in.)
  2. B 600 mm (24 in.)
  3. C 300 mm (12 in.)
  4. D 150 mm (6 in.)
Show answer & explanation

Correct: C — 300 mm (12 in.)

770.44(A)(4) requires a minimum of 300 mm (12 in.) separation in the span, including at the building attachment point. The 1.0 m (40 in.) figure is the separate, larger clearance required at the pole, not in the span.

Neat and workmanlike installation of optical fiber cable

NEC 770.24(A)

Exposed optical fiber cable must be supported by the building structure and secured with fittings that won't damage it, with listed low-smoke ties required in plenums.

Q5 NEC 770.24(A)

An installer is securing optical fiber cable exposed on a ceiling surface in a plenum used for environmental air. What does 770.24(A) require for the nonmetallic cable ties used?

  1. A They must be spaced no more than 300 mm (12 in.) apart
  2. B They must be listed as having low smoke and heat release properties
  3. C They must be rated for wet locations only
  4. D They must be metallic to prevent fiber degradation
Show answer & explanation

Correct: B — They must be listed as having low smoke and heat release properties

770.24(A) requires plenum cable ties and other nonmetallic cable accessories used to secure and support optical fiber cable in plenums to be listed for low smoke and heat release properties. There is no metallic requirement, no wet-location requirement, and no specific spacing dimension given in this section.

Optical fiber with Class 2/3 and other compatible communications circuits

NEC 770.133(C)

Optical fiber cables — conductive or nonconductive — can share a raceway, box, or cable tray with Class 2/3, fire alarm, communications, CATV, and network-powered broadband circuits.

Q6 NEC 770.133(C)

Under 770.133(C), which of the following circuit types is permitted in the same cable tray as optical fiber cable?

  1. A Power-limited fire alarm circuits per Parts I and III of Article 760
  2. B Class 1 power circuits per Part II of Article 725
  3. C General branch-circuit conductors per Article 210
  4. D Non-power-limited fire alarm circuits per Part II of Article 760
Show answer & explanation

Correct: A — Power-limited fire alarm circuits per Parts I and III of Article 760

770.133(C)(2) permits power-limited fire alarm systems complying with Parts I and III of Article 760. Class 1 circuits and non-power-limited fire alarm circuits are not on the compatible list, and general branch-circuit (Article 210) power conductors are excluded entirely — this section only addresses limited-power/communications-type circuits.

General-Purpose Optical Fiber Cable Types & Substitution Hierarchy

NEC 770.179(C)

OFNG/OFCG and OFN/OFC are both general-purpose fiber cables, but only OFNG/OFCG can go in cable trays — OFN/OFC cannot substitute upward for a tray-rated cable.

Q7 NEC 770.179(C)

An installer needs to run optical fiber cable through a cable tray. Which general-purpose cable type is suitable?

  1. A OFNG
  2. B OFN
  3. C A plenum-rated cable is always required in cable trays
  4. D OFC
Show answer & explanation

Correct: A — OFNG

Per 770.179(C), OFNG (and OFCG) are resistant to the spread of fire in cable trays per the vertical-tray flame tests. OFN and OFC, per 770.179(D), are general-purpose but not tested or suitable for cable trays. Plenum cable is a separate, higher-rated class not addressed by these sections.

Cables allowed in metal raceways vs. fireproof shafts for risers

NEC 770.113(E)

Optical fiber risers need either a metal raceway or a fireproof shaft, firestopped at every floor — cable routing assemblies are only recognized inside a fireproof shaft, not a metal raceway.

Q8 NEC 770.113(E)

An installer wants to run cable routing assemblies for optical fiber cable between floors. Which installation method allows this?

  1. A A metal raceway with firestops at each floor
  2. B A general-purpose communications raceway with no floor firestops
  3. C A fireproof riser shaft with firestops at each floor
  4. D Any riser cable run without firestopping, since fiber is nonconductive
Show answer & explanation

Correct: C — A fireproof riser shaft with firestops at each floor

Per 770.113(F), plenum, riser, and general-purpose cable routing assemblies are permitted in fireproof riser shafts firestopped at each floor. 770.113(E) covers metal raceways but only recognizes cable and communications innerduct there, not routing assemblies. Firestopping at each floor is required either way per 770.26.

Sharing cable trays/raceways with electric light, power, and other circuits

NEC 770.133(A)

Nonconductive fiber cable and armored/metal-clad conductive fiber cable can share a tray or raceway with power conductors; bare conductive fiber cable needs a barrier or listed divider.

Q9 NEC 770.133(A) Code lookup

A designer wants to run nonconductive optical fiber cable in the same cable tray as Class 1 power-limited... no, non-power-limited fire alarm circuit conductors, with no barrier separating them. Which section addresses whether this shared cable tray installation is permitted?

  1. A 770.113(H)
  2. B 770.133(B)
  3. C 770.133(C)
  4. D 770.133(A)
Show answer & explanation

Correct: D — 770.133(A)

770.133(A) specifically governs optical fiber cables sharing a cable tray or raceway with electric light, power, Class 1, non-power-limited fire alarm, or medium-power network-powered broadband circuits, and states nonconductive cables are permitted without a barrier while unarmored conductive cables are not. 770.133(B) covers cabinets and outlet boxes, not cable trays, and 770.113(H) only lists what cable types are permitted in cable trays generally, not the co-occupancy rule with power conductors.

Optical Fiber Cable Minimum Temperature Rating & Marking

NEC 770.179

Every optical fiber cable needs at least a 60°C (140°F) rating, and only cables rated higher than that must show the rating on the jacket.

Q10 NEC 770.179

Per 770.179, what is the minimum temperature rating permitted for an optical fiber cable?

  1. A 90°C (194°F)
  2. B 60°C (140°F)
  3. C 30°C (86°F)
  4. D 75°C (167°F)
Show answer & explanation

Correct: B — 60°C (140°F)

770.179 sets 60°C (140°F) as the minimum temperature rating for all optical fiber cables. The other values are common conductor/equipment temperature ratings elsewhere in the NEC, but they are not the floor set for optical fiber cable in this section.

Optical fiber in cable trays, cross-connect frames, and other building locations

NEC 770.113(H)

Cable trays, distributing frames/cross-connect arrays, and general building locations all accept the full family of listed optical fiber cable types — bare or in a qualifying raceway.

Q11 NEC 770.113(H)

An installer wants to support optical fiber cable in a cable tray without any raceway. Per 770.113(H), which is true?

  1. A Bare Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, or OFC are permitted directly in the tray
  2. B Only plenum-rated OFNP or OFCP may be used bare in a cable tray
  3. C Only riser-rated OFNR or OFCR are listed as tray-permitted types
  4. D Optical fiber cable must always be enclosed in a communications raceway when placed in a tray
Show answer & explanation

Correct: A — Bare Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, or OFC are permitted directly in the tray

770.113(H)(1) permits Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC to be supported by cable trays with no raceway required; a raceway is only an additional option under (H)(2), not a mandate.

Grounding, bonding, or interrupting metallic members of optical fiber cable

NEC 770.93

If an optical fiber cable's metallic members can contact power conductors, ground/bond them per 770.100 or break the path with an insulating joint — as close as practicable to entry or termination.

Q12 NEC 770.93

An optical fiber cable with a metallic strength member enters a building and is exposed to contact with electric light or power conductors. Per 770.93(A), what is required?

  1. A Install the cable in rigid metal conduit for its entire length inside the building
  2. B Bond the metallic member only if the cable run inside the building exceeds 15 m (50 ft)
  3. C Ground or bond the metallic member per 770.100, or interrupt it with an insulating joint, as close as practicable to the point of entrance
  4. D No action is required as long as the cable run is continuous with no splices
Show answer & explanation

Correct: C — Ground or bond the metallic member per 770.100, or interrupt it with an insulating joint, as close as practicable to the point of entrance

770.93(A) requires the non-current-carrying metallic member to be grounded or bonded per 770.100, or interrupted with an insulating joint or equivalent device, located as close as practicable to the point of entrance. There is no conduit substitute, no exemption for a continuous run, and no length-based threshold in the section.

Making the electrode connection and bonding separate electrodes together

NEC 770.100(C)

The optical fiber cable grounding electrode connects like any other per 250.70, and if it's a separate electrode, a 6 AWG copper bonding jumper must tie it to the power grounding electrode system.

Q13 NEC 770.100(C)

A technician installs optical fiber cable at a building and uses a grounding electrode separate from the building's power grounding electrode system. Per 770.100(D), what is required?

  1. A The separate electrode must be removed and the power electrode used instead
  2. B No connection is required since optical fiber cable carries no current
  3. C A bonding jumper not smaller than 6 AWG copper or equivalent between the two electrodes
  4. D A bonding jumper not smaller than 8 AWG copper between the two electrodes
Show answer & explanation

Correct: C — A bonding jumper not smaller than 6 AWG copper or equivalent between the two electrodes

770.100(D) requires a bonding jumper of at least 6 AWG copper or equivalent between the grounding electrode and the power grounding electrode system when separate electrodes are used. The no-connection option ignores the potential-difference hazard the rule exists to prevent, the 8 AWG option understates the minimum size, and reusing the power electrode isn't what the rule requires — separate electrodes are permitted as long as they're bonded.

Bonding the grounding electrode to a mobile home's metal frame

NEC 770.106(B)

A mobile home's grounding electrode must bond to its metal frame or grounding terminal with at least a 12 AWG copper (or equivalent) conductor when there's no service equipment or disconnect, or when the home is cord-and-plug connected.

Q14 NEC 770.106(B)

Under 770.106(B), what is the minimum size for the copper conductor bonding the grounding electrode to a mobile home's metal frame?

  1. A 6 AWG
  2. B 12 AWG
  3. C 8 AWG
  4. D 10 AWG
Show answer & explanation

Correct: B — 12 AWG

770.106(B) sets the minimum at 12 AWG copper or an equivalent corrosion-resistant material. The 8 AWG, 10 AWG, and 6 AWG options are all larger than what the rule actually requires as a minimum.

Grounding optical fiber cable entrance at mobile homes without nearby service/disconnect

NEC 770.106(A)

If no mobile home service equipment or grounded disconnecting means sits within 30 ft of the mobile home, the fiber cable's metallic members still need grounding per 770.100(B)(3).

Q15 NEC 770.106(A)

An optical fiber cable enters a mobile home. There is no mobile home service equipment within 30 ft of the exterior wall. What must happen to the cable's non-current-carrying metallic members?

  1. A No grounding is required since optical fiber carries no current
  2. B They must be grounded in accordance with 770.100(B)(3)
  3. C Grounding is only required if the cable enters through a metal raceway
  4. D They must be bonded to the nearest metallic water pipe only
Show answer & explanation

Correct: B — They must be grounded in accordance with 770.100(B)(3)

Per 770.106(A)(1), when no mobile home service equipment is within 30 ft (9.0 m) of the exterior wall, the metallic members must still be grounded per 770.100(B)(3). The 'no current, no grounding needed' distractor confuses current-carrying conductors with metallic strength/armor members, which need grounding regardless of current.

Removing or tagging abandoned optical fiber cable

NEC 770.25

Abandoned accessible optical fiber cable must be removed unless it's tagged for future use with a tag durable enough for its environment.

Q16 NEC 770.25 Code lookup

A telecom contractor is retiring old fiber runs in a commercial building's ceiling space. Some accessible optical fiber cables are no longer in use and will not be tagged for future use. Which section governs what must be done with the accessible portion of these abandoned cables?

  1. A 770.25
  2. B 770.26
  3. C 770.24
  4. D 770.3
Show answer & explanation

Correct: A — 770.25

770.25 requires the accessible portion of abandoned optical fiber cables to be removed unless tagged for future use. 770.24 covers mechanical execution of work (installation practices, not abandonment), and 770.26 covers spread of fire/products of combustion, not removal requirements — neither addresses abandoned cable disposition.

Keeping electrical equipment behind panels accessible

NEC 770.21

Optical fiber cable slack or bundling can never build up enough to block removal of a panel — including a suspended ceiling tile — that provides access to electrical equipment.

Q17 NEC 770.21

A junction box sits above a suspended ceiling and is normally reached by lifting a ceiling tile. Per 770.21, what governs how nearby optical fiber cable is left?

  1. A The rule only restricts rigid access doors, not suspended ceiling tiles.
  2. B The rule only applies if the box serves communications equipment rather than power equipment.
  3. C Slack and bundled cable must not accumulate enough to prevent lifting the tile to reach the box.
  4. D Fiber cable is exempt from access rules because it carries no electrical current.
Show answer & explanation

Correct: C — Slack and bundled cable must not accumulate enough to prevent lifting the tile to reach the box.

770.21 bars fiber cable accumulation from blocking removal of panels that provide access to electrical equipment, and it names suspended ceiling panels specifically as covered. Being non-conductive doesn't exempt fiber cable, and the equipment behind the panel isn't limited to communications gear.

Bonding metal entrance conduit for fiber cable

NEC 770.49

Metal conduit that carries optical fiber entrance cable must be bonded to a grounding electrode, even though the fiber itself carries no current.

Q18 NEC 770.49

A metal conduit carries optical fiber entrance cable into a building. Per 770.49, what must be done with this conduit?

  1. A Nothing, since optical fiber carries no electrical current
  2. B Connect it to a grounding electrode or the building grounding electrode system with a bonding or grounding electrode conductor
  3. C Install it in nonmetallic conduit instead
  4. D Bond it only if the fiber cable is installed alongside power conductors
Show answer & explanation

Correct: B — Connect it to a grounding electrode or the building grounding electrode system with a bonding or grounding electrode conductor

770.49 requires metal conduit containing optical fiber entrance cable to be connected by a bonding conductor or grounding electrode conductor to a grounding electrode, or the building grounding electrode system if present, per 770.100(B). This applies regardless of whether the fiber carries current or shares a path with power conductors; the concern is the metal raceway itself, not the cable inside it.

Firestopping to prevent spread of fire through penetrations

NEC 770.26

Any opening where optical fiber cable or communications raceway passes through a fire-rated wall, floor, or ceiling must be firestopped to restore that rating.

Q19 NEC 770.26

An optical fiber cable passes through a fire-resistance-rated floor. Per 770.26, what must be done at the penetration?

  1. A The opening must be firestopped using an approved method to maintain the fire resistance rating
  2. B The cable must be replaced with a metallic communications raceway before passing through the floor
  3. C The opening may be left as-is if the cable is listed as riser-rated
  4. D The opening must be sealed only if the space above is occupied
Show answer & explanation

Correct: A — The opening must be firestopped using an approved method to maintain the fire resistance rating

770.26 requires that openings around penetrations of optical fiber cables and communications raceways through fire-resistance-rated assemblies be firestopped with approved methods. A riser listing addresses flame/smoke spread along the cable itself, not the fire rating of the penetrated assembly, so it doesn't substitute for firestopping. The requirement applies regardless of occupancy, and swapping cable types doesn't remove the need to firestop the opening.

Classifying hybrid optical fiber cables

NEC 770.3(C)

A hybrid cable combining fiber and electrical conductors is classified, listed, and marked by the type of its electrical conductors — not as a fiber cable.

Q20 NEC 770.3(C)

A single-jacket cable contains both optical fibers and Class 2 power-limited conductors. Per 770.3(C), how must this hybrid cable be classified?

  1. A As an electrical cable, in accordance with the type of electrical conductors it contains
  2. B As a communications cable regardless of the electrical conductor type present
  3. C As an optical fiber cable, since the fiber content takes precedence
  4. D It is exempt from classification because fiber cables fall outside Chapter 7
Show answer & explanation

Correct: A — As an electrical cable, in accordance with the type of electrical conductors it contains

770.3(C) states hybrid optical fiber cables are classified as electrical cables according to the type of electrical conductors they contain — the fiber content doesn't set the classification, and there's no blanket exemption or default communications classification.

Overhead fiber cable clearance above roofs

NEC 770.44(B)

Outside plant optical fiber cable needs 8 ft of vertical clearance above roofs, with narrow exceptions down to 3 ft or 18 in.

Q21 NEC 770.44(B) Code lookup

An outside plant optical fiber service drop is being installed over a dwelling's main roof, which has no overhang and a flat slope. What minimum vertical clearance must the cable maintain above all points of the roof it passes over, and which section governs this clearance?

  1. A 770.24(A)
  2. B 770.44(A)(4)
  3. C 770.47(B)
  4. D 770.44(B)
Show answer & explanation

Correct: D — 770.44(B)

770.44(B) sets the 2.5 m (8 ft) vertical clearance for optical fiber cables passing above roofs, with the reduced-clearance exceptions for overhangs and sloped roofs; 770.44(A)(4) instead covers clearance for cables on poles and in-span, not above roofs.

Underground fiber separation from power conductors

NEC 770.47

Direct-buried conductive optical fiber cable needs 12 in. of separation from power conductors, unless one side is in a raceway or protected cable.

Q22 NEC 770.47

A direct-buried conductive optical fiber cable runs parallel to underground power conductors that are direct-buried with no raceway or metal armor. What separation does 770.47(B) require?

  1. A 600 mm (24 in.)
  2. B 300 mm (12 in.)
  3. C No separation is required for direct-buried cables
  4. D 150 mm (6 in.)
Show answer & explanation

Correct: B — 300 mm (12 in.)

Section 770.47(B) sets the default separation for direct-buried conductive optical fiber cable from electric light, power, Class 1, or non-power-limited fire alarm conductors at 300 mm (12 in.). The 6 in. and 24 in. options aren't the code figure, and separation is only waived under the specific raceway/cable-type exceptions in 770.47(B), not for all direct burial.

Permitted applications and cable substitutions for optical fiber cable

NEC 770.154

Table 770.154(a) sets where each optical fiber cable type can be installed, and Table 770.154(b) lists which higher-rated cables can substitute for a lower-rated one.

Q23 NEC 770.154

An installer confirms a listed optical fiber cable type is a 'permitted application' per Table 770.154(a) for a given location. What else must be verified before the installation is code-compliant?

  1. A Nothing further; the table listing alone satisfies the Code
  2. B That the cable also appears in Table 770.154(b) as a substitute cable
  3. C That the installation also meets 770.110 and 770.113
  4. D That a licensed low-voltage contractor performs the pull
Show answer & explanation

Correct: C — That the installation also meets 770.110 and 770.113

770.154 states permitted applications are subject to the installation requirements of 770.110 and 770.113 — the table only establishes where a cable type is allowed, not that the installation is automatically compliant. Table 770.154(b) covers substitutions, a separate question, and the code text does not condition compliance on who performs the work.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access