Free NEC practice test · Article 760

Fire Alarm Systems practice questions

A free NEC Article 760 practice test for the journeyman exam: 27 questions on Fire Alarm Systems, each with the answer and the why behind it.

27 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 27 journeyman-exam practice questions cover NEC Article 760 across 27 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Selecting NPLFA cable type by space: plenums, risers, and general building locations

NEC 760.53(B)

The space sets the cable: NPLFP for plenums, NPLFR for risers and shafts, NPLF for general use — and none of them go exposed in a fabricated environmental air duct.

Q1 NEC 760.53(B)

An installer wants to run non-power-limited fire alarm cable exposed inside a duct specifically fabricated for environmental air. Which cable type is permitted?

  1. A Type NPLFR, since it is rated for risers and general plenum spaces
  2. B Type NPLF, since it is the general-purpose type
  3. C None of the listed NPLFA types
  4. D Type NPLFP, since it is rated for plenum use
Show answer & explanation

Correct: C — None of the listed NPLFA types

Per 760.53(B)(1), Types NPLFP, NPLFR, and NPLF shall not be installed exposed in ducts specifically fabricated for environmental air. Plenum-rated NPLFP is for other air-handling spaces, not fabricated ducts themselves, which is a common point of confusion.

Listing, ratings, and markings for insulated line-type fire detectors

NEC 760.179

Line-type fire detector cable must carry a listed 300-volt, 60°C minimum rating marked as FPLP/FPLR/FPL — but never marked with its voltage, to avoid confusion with power wiring.

Q2 NEC 760.179

How must an insulated continuous line-type fire detector cable be marked for fire resistance, per 760.179(C)?

  1. A Type MC or AC
  2. B Type THHN or THWN
  3. C Type CL2 or CL3
  4. D Type FPLP, FPLR, or FPL
Show answer & explanation

Correct: D — Type FPLP, FPLR, or FPL

760.179(C) requires marking as Type FPLP, FPLR, or FPL. Type CL2/CL3 are Class 2/3 cable markings, MC/AC are metal-clad and armored cable, and THHN/THWN are building-wire insulation types — none apply to line-type fire detector cable.

Installing NPLFA cables exposed, through floors/walls, and in hoistways

NEC 760.53(A)

Exposed NPLFA cable needs secure support and physical protection; cable crossing a floor or wall, or run in a hoistway, needs raceway protection unless building construction already guards it.

Q3 NEC 760.53(A) Code lookup

A contractor is running multiconductor NPLFA cable exposed down a stairwell wall, and part of the run drops below 7 ft to reach a pull station near the floor. Which section specifies the maximum support-fastening interval for the cable in that lower 7 ft zone?

  1. A 760.53(A)(2)
  2. B 760.53(A)(3)
  3. C 760.53(A)(1)
  4. D 760.51(C)
Show answer & explanation

Correct: C — 760.53(A)(1)

760.53(A)(1) governs exposed NPLFA cable and sets the 450 mm (18 in.) fastening interval within 7 ft of the floor; 760.53(A)(2) instead addresses cable passing through a floor or wall, and 760.53(A)(3) covers hoistway installations — neither has a fastening-interval rule.

NPLFA cable types for plenum, riser, and general use

NEC 760.176(C)

NPLFP is required in ducts and plenums, NPLFR is required in vertical shafts between floors, and plain NPLF is general-purpose only — it can't go in either space.

Q4 NEC 760.176(C)

A non-power-limited fire alarm cable is being run through a mechanical room duct used for environmental air. Which cable type satisfies this installation per 760.176?

  1. A Type NPLF
  2. B Type NPLFR
  3. C Any NPLFA cable installed in conduit
  4. D Type NPLFP
Show answer & explanation

Correct: D — Type NPLFP

760.176(C) requires Type NPLFP for use in ducts and other spaces used for environmental air, with listed fire-resistant and low smoke-producing characteristics. Type NPLFR is for vertical risers, not air spaces, and plain Type NPLF is explicitly excluded from duct and plenum use per 760.176(E). Running any NPLFA cable in conduit does not substitute for the required plenum listing.

NPLFA overcurrent protection sizing for 18/16 AWG and larger conductors

NEC 760.43

18 AWG NPLFA conductors cap at 7 A of overcurrent protection, 16 AWG caps at 10 A, and 14 AWG and larger are protected at ampacity without 310.14 adjustment or correction factors.

Q5 NEC 760.43

An NPLFA (non-power-limited fire alarm) circuit is wired with 18 AWG conductors. What is the maximum overcurrent protection permitted for these conductors?

  1. A 10 amperes
  2. B 15 amperes
  3. C 7 amperes
  4. D 20 amperes
Show answer & explanation

Correct: C — 7 amperes

760.43 sets a hard cap of 7 amperes of overcurrent protection for 18 AWG NPLFA conductors. The 10-ampere figure is the cap for 16 AWG conductors, not 18 AWG — mixing up the two gauge/cap pairs is the most common error.

Branch circuit requirements for fire alarm power supply

NEC 760.121(B)

The fire alarm control unit needs its own dedicated branch circuit — no shared loads, no GFCI/AFCI, and a red 'FIRE ALARM CIRCUIT' disconnect that can be locked on.

Q6 NEC 760.121(B)

An inspector is reviewing the branch circuit that feeds a building's fire alarm control unit. Which of the following is a violation of 760.121(B)?

  1. A The circuit is protected by a GFCI breaker at the panel
  2. B The disconnect is secured in the 'on' position
  3. C The circuit supplies only the fire alarm equipment
  4. D The disconnect is marked with red identification reading 'FIRE ALARM CIRCUIT'
Show answer & explanation

Correct: A — The circuit is protected by a GFCI breaker at the panel

760.121(B)(2) prohibits supplying the fire alarm branch circuit through GFCI or AFCI protection, since a nuisance trip could disable fire alarm power. The dedicated-load requirement, the red 'FIRE ALARM CIRCUIT' marking, and securing the disconnect in the on position are all required or permitted, not violations.

PLFA separation in hoistways and other special applications

NEC 760.136(F)

In hoistways PLFA conductors need rigid raceway; everywhere else, keep 2 in. from power conductors unless raceway, cable, or a fixed nonconductor separates them.

Q7 NEC 760.136(F)

In a general (non-hoistway) application, PLFA conductors are installed in the open, in the same space as unenclosed power conductors, with no raceway, cable, or fixed nonconductor separating them. What separation does 760.136(H) require?

  1. A No minimum, since PLFA circuits are inherently limited energy
  2. B At least 300 mm (12 in.)
  3. C At least 150 mm (6 in.)
  4. D At least 50 mm (2 in.)
Show answer & explanation

Correct: D — At least 50 mm (2 in.)

760.136(H) sets the default separation at 50 mm (2 in.) between PLFA conductors and electric light, power, Class 1, non-power-limited fire alarm, or medium-power network-powered broadband circuit conductors, unless one of the listed exceptions applies.

PLFA cables in cable routing assemblies and communications raceways

NEC 760.3(K)

Power-limited fire alarm cable can run in listed cable routing assemblies (Table 800.154(c)) or listed communications raceways (Table 800.154(b)), each with its own installation rules.

Q8 NEC 760.3(K)

Which statement correctly distinguishes cable routing assemblies from communications raceways when installing PLFA cable, per 760.3(K) and (L)?

  1. A Cable routing assemblies need no listing, while communications raceways must be listed
  2. B Cable routing assemblies follow the ENT rules in 362.24–362.56; communications raceways follow 800.110(C)
  3. C Both follow identical installation rules, since only the selection table differs
  4. D Cable routing assemblies follow 800.110(C) and 800.113; communications raceways follow 800.113 and the ENT rules in 362.24–362.56
Show answer & explanation

Correct: D — Cable routing assemblies follow 800.110(C) and 800.113; communications raceways follow 800.113 and the ENT rules in 362.24–362.56

760.3(K) points cable routing assemblies to 800.110(C) and 800.113, while 760.3(L) points communications raceways to 800.113 plus the ENT installation rules in 362.24–362.56 — the two installation rule sets are not interchangeable, and both pathway types require 800.182 listing.

Fire alarm circuits in corrosive, damp, or wet locations

NEC 760.3(C)

Fire alarm wiring gets no special break in corrosive, damp, or wet locations — it must meet the same general protection rules as any other wiring.

Q9 NEC 760.3(C)

A fire alarm cable run passes through an area classified as a damp location. Under 760.3(C), how must this installation be handled?

  1. A Only the raceway needs a wet-location listing; conductor insulation rules don't apply to fire alarm cable
  2. B It must comply with the general corrosive, damp, and wet location provisions that apply to any wiring method
  3. C Any wiring method is acceptable as long as the cable itself carries a fire alarm listing
  4. D It is exempt from location-based protection rules because fire alarm circuits are power-limited
Show answer & explanation

Correct: B — It must comply with the general corrosive, damp, and wet location provisions that apply to any wiring method

760.3(C) requires fire alarm circuits and equipment in corrosive, damp, or wet locations to comply with the same general provisions that govern every wiring method there — there's no fire-alarm-specific exception, and a fire alarm listing alone doesn't substitute for location-based protection.

NPLFA cable marking requirements

NEC 760.176(G)

NPLFA cable jackets must show voltage rating, conductor size, and temperature rating over 60°C, with "-CI" added for circuit-integrity-listed cable.

Q10 NEC 760.176(G)

A multiconductor NPLFA cable has a temperature rating of 75°C (167°F). Per 760.176(G), what must appear on its jacket?

  1. A Only the conductor size, since temperature marking is optional below 90°C
  2. B Only the temperature rating, since conductor size marking applies only to power-limited cables
  3. C The conductor size and the temperature rating, since it exceeds 60°C (140°F)
  4. D Neither marking, since 75°C cable is exempt from the jacket marking table
Show answer & explanation

Correct: C — The conductor size and the temperature rating, since it exceeds 60°C (140°F)

760.176(G) requires the jacket to always show conductor size, and to show the temperature rating whenever it exceeds 60°C (140°F). At 75°C, both markings are required. Treating 90°C as the trigger point, exempting conductor size, or exempting the cable entirely all misstate the rule.

Circuit integrity cable and fire-resistive systems for survivability

NEC 760.176(F)

Survivability circuits need CI cable, a fire-resistive cable system, or an electrical circuit protective system — each has its own marking and installation rules to keep the listed rating valid.

Q11 NEC 760.176(F)

An installer plans to run CI-marked cable inside a metal raceway to protect a survivability circuit. Under what condition is this permitted?

  1. A It is permitted if the cable is also rated for power-limited circuits
  2. B It is permitted as long as the raceway is metallic rather than nonmetallic
  3. C It is never permitted; CI cable must always be installed in free air
  4. D Only if the raceway installation is specifically listed and marked as part of an electrical circuit protective fire-resistive cable system
Show answer & explanation

Correct: D — Only if the raceway installation is specifically listed and marked as part of an electrical circuit protective fire-resistive cable system

Per 760.176(F)(1), CI cable only keeps its listed fire-resistive rating in free air; it may be installed in a raceway only where specifically listed and marked as part of an electrical circuit protective fire-resistive cable system under 760.176(F)(2). Raceway material and power-limited rating are not the deciding factors.

NPLFA cable conductor and insulation requirements

NEC 760.176(A)

NPLFA conductors must be 18 AWG or larger copper, rated at least 600 V and 60°C, with 14 AWG and larger using Table 310.4(1) insulation types.

Q12 NEC 760.176(A)

Per 760.176(A), what conductor material and size is required for non-power-limited fire alarm (NPLFA) cable?

  1. A 18 AWG or larger solid or stranded aluminum
  2. B 12 AWG or larger solid copper only
  3. C 18 AWG or larger solid or stranded copper
  4. D 16 AWG or larger solid or stranded copper
Show answer & explanation

Correct: C — 18 AWG or larger solid or stranded copper

760.176(A) requires NPLFA conductors to be 18 AWG or larger solid or stranded copper. A 16 AWG minimum is not the stated threshold, aluminum is not permitted, and solid copper only (excluding stranded) is too restrictive.

Conductor fill counting and ampacity adjustment in raceways and cable trays

NEC 760.51

Count NPLFA conductors per 300.17, but only apply the 310.15(C)(1) adjustment factors when fire alarm conductors carry continuous load over 10% of ampacity.

Q13 NEC 760.51

A raceway contains only non-power-limited fire alarm circuit conductors and Class 1 circuit conductors. What method is used to determine how many conductors the raceway may contain?

  1. A The conduit and tubing fill tables in Chapter 9, applied only to fire alarm cable
  2. B 300.17, the same conductor-counting method used for general raceway fill
  3. C 392.22, the cable tray fill rule
  4. D 310.15(C)(1), since ampacity adjustment also sets the maximum conductor count
Show answer & explanation

Correct: B — 300.17, the same conductor-counting method used for general raceway fill

760.51(A) states the number of conductors is determined per 300.17. 310.15(C)(1) governs ampacity adjustment, not conductor count, and 392.22 applies to cable trays, not raceways.

Conductor sizing, ampacity limits, and copper-only requirement for 18/16 AWG and larger

NEC 760.49(A)

Fire alarm conductors must be copper; 18 and 16 AWG are allowed only in a raceway, enclosure, or listed cable and only within Table 402.5 ampacities, while anything larger than 16 AWG follows 310.14.

Q14 NEC 760.49(A)

An installer wants to use aluminum conductors for a non-power-limited fire alarm circuit to save cost. Per 760.49(A), is this permitted?

  1. A Yes, but only for conductors larger than 16 AWG
  2. B Yes, provided the circuit is installed in a raceway
  3. C No, only copper conductors are permitted for fire alarm systems
  4. D Yes, provided the aluminum conductors are upsized one wire gauge
Show answer & explanation

Correct: C — No, only copper conductors are permitted for fire alarm systems

760.49(A) states only copper conductors are permitted for fire alarm systems — there is no aluminum allowance, upsized or otherwise, and the raceway requirement applies to 18/16 AWG copper conductors, not to permitting aluminum.

Overcurrent device location, including transformer and electronic power source secondary protection

NEC 760.45

NPLFA overcurrent protection must sit right where the conductor gets its supply, unless a 2-wire transformer or electronic power source secondary lets primary-side protection cover it.

Q15 NEC 760.45

An NPLFA circuit is supplied from the secondary of a single-phase transformer. Under what condition can the primary-side overcurrent device be considered protection for the secondary conductors?

  1. A The transformer is listed for fire alarm use regardless of secondary configuration
  2. B The secondary has only a 2-wire (single-voltage) output and the protection meets 450.3 and the voltage-ratio limit
  3. C The secondary conductors are shorter than 3 m (10 ft)
  4. D The secondary is a 3-wire, multi-tap configuration sized per 450.3
Show answer & explanation

Correct: B — The secondary has only a 2-wire (single-voltage) output and the protection meets 450.3 and the voltage-ratio limit

760.45 permits primary-side overcurrent protection to serve as protection for the secondary only when the secondary is a 2-wire (single-voltage) configuration, sized per 450.3 and the secondary-to-primary voltage ratio. A 3-wire or multi-tap secondary is explicitly excluded from this allowance, and there is no exception based on conductor length or general fire-alarm listing.

NPLFA power source and dedicated branch circuit requirements

NEC 760.41(A)

Non–power-limited fire alarm circuits run on their own dedicated branch circuit, red-marked, GFCI/AFCI-free, and never sharing loads with anything else.

Q16 NEC 760.41(A)

Per 760.41(B), what type of overcurrent protection is prohibited on the branch circuit supplying non–power-limited fire alarm equipment?

  1. A A standard thermal-magnetic circuit breaker
  2. B GFCI or AFCI protection
  3. C A fused disconnect rated for the load
  4. D A permanently identified overcurrent device at the control unit
Show answer & explanation

Correct: B — GFCI or AFCI protection

760.41(B) explicitly bars supplying the fire alarm branch circuit through GFCI or AFCI protection, since a nuisance trip could disable the fire alarm system. A permanently identified standard breaker or fused disconnect is the expected setup, not the prohibited one.

Installing PLFA cable terminations, floor/wall penetrations, and exposed runs

NEC 760.130(B)(1)

Exposed PLFA cable needs physical protection and support, and must be raceway-protected for 7 ft when it passes through a floor or wall unless building construction already shields it.

Q17 NEC 760.130(B)(1) Code lookup

A power-limited fire alarm cable is fished within a concealed wall cavity and runs exposed on a sidewall down to a junction box located 4 ft above the finished floor. Which section specifies the maximum support interval and physical protection requirements for this exposed run?

  1. A 760.130(B)(1)
  2. B 760.130(B)(3)
  3. C 760.130(B)(2)
  4. D 760.136(A)
Show answer & explanation

Correct: A — 760.130(B)(1)

760.130(B)(1) sets the securing interval (not more than 18 in.) and physical-damage protection for PLFA cable exposed on sidewalls or fished in concealed spaces within 7 ft of the floor. 760.130(B)(2) instead governs cable passing through a floor or wall, and 760.136(A) covers separation from other circuit conductors, not support/protection.

Listed PLFA cable types and permitted substitutions

NEC 760.154

PLFA cable must match Table 760.154 for its location, but Table 760.154(A) lets a better fire-rated cable substitute for a lower-rated one — never the reverse.

Q18 NEC 760.154 Code lookup

A fire alarm system design calls for FPLR cable in a vertical riser, but the installer has FPLP cable with a compatible listing on hand and wants to know which cable substitutions are permitted for power-limited fire alarm cables. Which section's table lists these substitutions?

  1. A 760.176
  2. B 760.154
  3. C 760.154(A)
  4. D 760.139
Show answer & explanation

Correct: C — 760.154(A)

760.154(A) hosts Table 760.154(A), Cable Substitutions, and Figure 760.154(A) illustrating which PLFA/fire alarm cable types may substitute for others. 760.154 hosts the separate table listing where each PLFA cable type is permitted to be used in buildings, not the substitution hierarchy; 760.176 covers listing and marking requirements for NPLFA cables, not substitutions.

NPLFA vs. PLFA wiring methods on the load side

NEC 760.130

Load-side fire alarm wiring is either NPLFA (regular conductor rules, no ampacity adjustment) or PLFA (limited-energy cable rules from 722.135) — pick one system and follow its own install rules.

Q19 NEC 760.130 Code lookup

A fire alarm installer is running non-power-limited fire alarm (NPLFA) conductors and wants to know which wiring methods and separation rules apply to those conductors on the load side of the power source. Which section covers this?

  1. A 760.121(A)
  2. B 760.130(B)
  3. C 760.127
  4. D 760.130(A)
Show answer & explanation

Correct: D — 760.130(A)

760.130(A) is titled NPLFA Wiring Methods and Materials and specifically governs NPLFA conductors on the load side. 760.130(B) instead covers PLFA conductors and cables, and 760.127 governs the supply side rather than the load side.

Separating PLFA circuits from power/Class 1 circuits — general rule and barrier methods

NEC 760.136(A)

PLFA cables can't share a raceway, box, or enclosure with power or Class 1 conductors unless separated by a barrier or an internal raceway.

Q20 NEC 760.136(A) Code lookup

A fire alarm contractor is running power-limited fire alarm (PLFA) cable in the same cable tray as unrelated 480V power feeder conductors, with no separation between them. Which section states the general rule prohibiting this?

  1. A 760.130(B)(1)
  2. B 760.139(A)
  3. C 760.136(A)
  4. D 760.133
Show answer & explanation

Correct: C — 760.136(A)

760.136(A) is the general prohibition on placing PLFA cables in the same cable, cable tray, enclosure, or raceway as electric light, power, Class 1, NPLFA, or medium-power network-powered broadband conductors unless an exception in 760.136(B)-(G) applies. 760.139(A) instead governs mixing multiple PLFA circuits with each other, not with power conductors, so it doesn't fit this scenario.

General raceway installation rules for fire alarm wiring

NEC 760.3(F)

Fire alarm circuits in raceway follow the same Chapter 3 rules as power wiring: no mixing without permission, protect against temperature extremes, support vertical runs, size the raceway to fit, and bush the ends.

Q21 NEC 760.3(F)

A raceway is installed solely to mechanically protect fire alarm cable where it runs through a framing member, and the cable emerges from the raceway into open space. What is required at that point?

  1. A A junction box, since all raceway terminations require one
  2. B A grounding bushing, per 250.97
  3. C A bushing, per 300.15(C)
  4. D Nothing, because fire alarm circuits are exempt from bushing requirements
Show answer & explanation

Correct: C — A bushing, per 300.15(C)

Per 760.3(J), a bushing is required where cables emerge from a raceway used for mechanical support or protection, in accordance with 300.15(C). A junction box isn't required just because a raceway ends, and fire alarm wiring has no blanket exemption from this rule. A grounding bushing under 250.97 addresses bonding at service equipment, not this scenario.

Removing and tagging abandoned fire alarm cables

NEC 760.25

Accessible abandoned fire alarm cable must be removed unless it's tagged for future use with a tag durable enough to survive the environment.

Q22 NEC 760.25 Code lookup

A building owner is decommissioning an old fire alarm system. Several NPLFA cables run through accessible ceiling spaces but are no longer connected to any device. Which section states whether these accessible abandoned cables must be removed?

  1. A 760.3(A)
  2. B 760.25
  3. C 760.24
  4. D 760.30
Show answer & explanation

Correct: B — 760.25

760.25 directly requires removal of the accessible portion of abandoned fire alarm cables. 760.24 governs mechanical execution of work (support and installation of cables still in use), not abandonment, and 760.30 covers circuit identification/labeling of active circuits, not abandoned ones.

Circuit integrity (CI) cable support spacing

NEC 760.24(B)

CI cable is supported every 24 in. max, but drops to every 18 in. max within 7 ft of the floor, and all supports and fasteners must be steel.

Q23 NEC 760.24(B) Code lookup

You're installing a fire-rated circuit integrity (CI) cable run for a fire pump feeder that stays exposed on the wall, more than 8 feet above the floor. Which section gives the maximum spacing between supports for this CI cable?

  1. A 760.24(A)
  2. B 760.21
  3. C 760.3(H)
  4. D 760.24(B)
Show answer & explanation

Correct: D — 760.24(B)

760.24(B) is the CI cable subsection that sets the 24 in. (610 mm) general support spacing (tightening to 18 in. within 7 ft of the floor). 760.24(A) only states the general mechanical-execution requirement without a spacing figure, and 760.3(H) addresses vertical support of fire-resistive cables in shafts, not routine support spacing.

Identifying fire alarm circuits at terminals and junctions

NEC 760.30

Fire alarm circuit conductors must be identified at terminals and junctions so nobody triggers a false alarm while testing other systems.

Q24 NEC 760.30 Code lookup

An electrician is servicing an HVAC control system and needs to work in a junction box that also contains fire alarm circuit conductors. To avoid accidentally tripping the fire alarm system while testing the HVAC wiring, the fire alarm conductors in that box must be marked so they aren't confused with the other circuits. Which section requires this identification at terminal and junction points?

  1. A 760.32
  2. B 760.35
  3. C 760.30
  4. D 760.25
Show answer & explanation

Correct: C — 760.30

760.30 specifically requires fire alarm circuits to be identified at terminal and junction locations to prevent unintentional signals during testing/servicing of other systems. 760.32 governs circuits that extend between buildings, and 760.35 sets general NPLFA/PLFA circuit requirements — neither addresses labeling at junctions.

Fire alarm circuits extending outdoors beyond one building

NEC 760.32

A fire alarm circuit that leaves one building and runs outdoors to another must follow Article 805, Parts II–IV, plus Article 300, Part I — not just Article 760.

Q25 NEC 760.32

A power-limited fire alarm circuit runs outdoors from one building to a detached garage on the same property. Which additional installation requirements apply?

  1. A Article 725 only, since it is a power-limited circuit
  2. B No additional requirements beyond Article 760 because it is power-limited
  3. C Article 805, Parts II, III, and IV, plus Article 300, Part I
  4. D Article 800, Parts III and IV only
Show answer & explanation

Correct: C — Article 805, Parts II, III, and IV, plus Article 300, Part I

Per 760.32, both NPLFA and PLFA circuits that extend beyond one building and run outdoors must meet Article 805, Parts II, III, and IV, and Article 300, Part I. Article 725 doesn't govern fire alarm circuits, being power-limited doesn't exempt the circuit from this rule, and Article 800 covers communications circuits, not the article referenced by 760.32.

Fire alarm cables in ducts, plenums, and air-handling spaces

NEC 760.3(B)

Fire alarm cables in ducts or plenums must meet 300.22, and power-limited cable needs the right Table 760.154 listing plus 722.135 installation rules.

Q26 NEC 760.3(B) Code lookup

A power-limited fire alarm cable meeting Table 760.154 is being installed in a plenum space above a suspended ceiling that is used for environmental air (not a fabricated duct). Which section permits this installation method?

  1. A 760.3(A)
  2. B 760.3(G)
  3. C 760.3(B)
  4. D 760.3(L)
Show answer & explanation

Correct: C — 760.3(B)

760.3(B) specifically permits power-limited fire alarm cable listed to Table 760.154 to be installed in plenums used for environmental air per 722.135. 760.3(A) addresses spread of fire/products of combustion generally, not the plenum cable permission itself, and 760.3(G) covers raceways exposed to different temperatures, not plenum cabling.

EGC identification and green-insulated signal conductors

NEC 760.3(N)

Green normally means equipment ground, but 760.3(N) allows green-insulated conductors to carry ungrounded fire alarm signals in FPL-type cables.

Q27 NEC 760.3(N)

Under 760.3(N), a green-insulated conductor in a Type FPL cable may be used as which of the following?

  1. A A grounded (neutral) conductor in any raceway
  2. B An equipment grounding conductor only, with no other use permitted
  3. C An ungrounded signal conductor, if installed per 760.154(A)
  4. D A grounding electrode conductor for the fire alarm control panel
Show answer & explanation

Correct: C — An ungrounded signal conductor, if installed per 760.154(A)

760.3(N) creates a specific exception: in FPLP, FPLR, FPL, and substitute cables, green insulation may be an ungrounded signal conductor when installed per 760.154(A). Green is otherwise reserved for equipment grounding conductors per 250.119, which is why the other options describe grounding-related uses rather than the actual exception.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access