Free NEC practice test · Article 706

Energy Storage Systems practice questions

A free NEC Article 706 practice test for the journeyman exam: 15 questions on Energy Storage Systems, each with the answer and the why behind it.

15 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 15 journeyman-exam practice questions cover NEC Article 706 across 15 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

ESS Disconnecting Means — Requirement, Location & Dwelling Emergency Shutdown

NEC 706.15(A)

Every ESS needs a readily accessible disconnect within sight and 10 ft, or lockable if it isn't — and one- and two-family dwellings also need an outside emergency shutdown that stops power export.

Q1 NEC 706.15(A)

An ESS disconnecting means is installed 25 ft from the ESS but within sight of it. Does this comply with 706.15(B)?

  1. A Yes, because it is within sight of the ESS
  2. B No, because it exceeds the 3 m (10 ft) distance limit regardless of sight
  3. C No, because ESS disconnects must always be located within the ESS enclosure
  4. D Yes, because only out-of-sight disconnects have a distance limit
Show answer & explanation

Correct: B — No, because it exceeds the 3 m (10 ft) distance limit regardless of sight

706.15(B) requires the disconnect to be located within the ESS, OR within sight AND within 3 m (10 ft) of it — both conditions apply together, not sight alone. At 25 ft it fails the distance requirement even though it's visible. Being lockable per 110.25 is only the compliance path for disconnects that are not within sight; it doesn't waive the distance rule for one that is within sight.

Where and how ESS circuits need overcurrent protection

NEC 706.31(A)

ESS circuits are protected at the source, sized at least 125% of max current (or 100% if the assembly is listed for it), and protected right at the storage component wherever a circuit passes through a wall, floor, or ceiling.

Q2 NEC 706.31(A)

A circuit conductor is connected at one end to an ESS supply with integral fault protection and is rated for that supply's maximum circuit current. The other end connects to a utility service whose available maximum circuit current exceeds the conductor's ampacity. Where must overcurrent protection be installed?

  1. A At the point of connection to the utility service, the higher current source
  2. B Nowhere, since the ESS supply's integral fault protection covers the whole conductor
  3. C At both ends of the conductor, regardless of source ratings
  4. D At the ESS supply end, since that end already has integral fault protection
Show answer & explanation

Correct: A — At the point of connection to the utility service, the higher current source

Per 706.31(A), when a conductor is protected at one end by a supply with integral fault protection but connects to a source with greater available current than the conductor's ampacity, the overcurrent device belongs at the higher-current source end — not at the already-protected ESS end and not at both ends.

Battery Disconnecting Means — Requirement & Location

NEC 706.15(E)(1)

A field-serviceable battery separate from the ESS electronics needs its own disconnect for all ungrounded conductors, readily accessible and within sight of the battery.

Q3 NEC 706.15(E)(1)

A field-serviceable battery bank is installed separate from its ESS electronics. Which conductors does 706.15(E)(1) require a disconnecting means for?

  1. A All ungrounded conductors
  2. B Only the grounded (neutral) conductor
  3. C Only conductors feeding the inverter
  4. D Only equipment grounding conductors
Show answer & explanation

Correct: A — All ungrounded conductors

706.15(E)(1) requires a disconnecting means for all ungrounded conductors to the battery. Grounded and equipment grounding conductors aren't what the disconnecting means requirement targets.

Battery Disconnect Remote Activation & Marking

NEC 706.15(E)(4)

If the disconnect's remote controls aren't within sight of the battery, the disconnect must be lockable open and field-marked with location, voltage, fault current, and an arc-flash label.

Q4 NEC 706.15(E)(4)

Which of the following is NOT one of the four items required on the field marking described in 706.15(E)(4)?

  1. A Nominal battery voltage
  2. B The battery manufacturer's warranty period
  3. C Available fault current derived from the battery system
  4. D Date the fault current calculation was performed
Show answer & explanation

Correct: B — The battery manufacturer's warranty period

706.15(E)(4) requires nominal battery voltage, available fault current, an arc-flash label, and the date the calculation was performed. A warranty period is not part of the required marking — a plausible-sounding but non-code item.

Calculating maximum rated current for an ESS circuit

NEC 706.30(A)

The maximum current for an ESS circuit always comes from the nameplate or listed rating of the specific equipment on that circuit, not a calculation.

Q5 NEC 706.30(A)

An ESS uses the same terminals for both charging and discharging, and the two operations have different rated currents. Per 706.30(A)(1), what is the circuit's rated current?

  1. A The discharge rating only, since that represents the load-serving condition
  2. B The charge rating only, since that represents the source-side condition
  3. C The greater of the charge and discharge ratings
  4. D The average of the charge and discharge ratings
Show answer & explanation

Correct: C — The greater of the charge and discharge ratings

706.30(A)(1) states that where the same terminals are used for both charging and discharging, the rated current shall be the greater of the two — not an average, and not automatically the discharge or charge value alone.

Commissioning and ongoing maintenance recordkeeping for ESS

NEC 706.7

Every ESS must be commissioned when installed and kept in a written maintenance record — except one- and two-family dwellings, which are exempt from both.

Q6 NEC 706.7 Code lookup

A commercial ESS installation (not a one- or two-family dwelling) has just been installed and energized. Before it goes into service, the electrician needs to know which section requires the system to be commissioned and points to NFPA 855 for guidance on how to do it.

  1. A 706.5
  2. B 706.3
  3. C 706.7(B)
  4. D 706.7(A)
Show answer & explanation

Correct: D — 706.7(A)

706.7(A) is the specific commissioning requirement (with the one- and two-family dwelling exemption and the NFPA 855 reference). 706.7(B) is the parallel maintenance-recordkeeping rule, not commissioning; 706.5 covers listing of equipment; 706.3 covers qualified personnel — neither addresses commissioning.

DC-rated overcurrent devices, current limiting, and fuse disconnects

NEC 706.31(C)

ESS dc overcurrent devices must be dc-listed with matching ratings, current limiting is required per dc output circuit, and accessible fuses energized from both sides need a disconnecting means.

Q7 NEC 706.31(C) Code lookup

An ESS installer is selecting a fuse and circuit breaker for the dc output circuit of a battery energy storage system. Which section requires that the overcurrent device be listed specifically for dc use with ratings matching the voltage, current, and interrupting duty of the application?

  1. A 706.31(C)
  2. B 706.31(D)
  3. C 706.30(B)
  4. D 706.31(B)
Show answer & explanation

Correct: A — 706.31(C)

706.31(C) specifically requires dc-rated listing plus matching voltage, current, and interrupting ratings for overcurrent devices in dc ESS circuits. 706.31(B) instead addresses how the device's ampere rating itself is sized, not its dc listing or interrupting rating.

Identifying and labeling multiple power sources (ESS directory)

NEC 706.21

An ESS needs a directory pointing to every power source at the building — 705.10 if there's a utility service, 710.10 if the ESS stands alone.

Q8 NEC 706.21

A retail store has a utility electric service and also installs a battery ESS for demand-charge management. Under 706.21(A), which section governs the required directory of power sources?

  1. A 710.10
  2. B 706.21(B)
  3. C 705.10
  4. D 110.21(B)
Show answer & explanation

Correct: C — 705.10

706.21(A) states that facilities with utility services and an ESS must install plaques or directories per 705.10. The 710.10 path is for stand-alone systems with no utility service, 110.21(B) governs the marking/label format itself rather than the directory, and 706.21(B) applies only to stand-alone-system facilities.

ESS Disconnect Marking & Arc-Flash Labeling

NEC 706.15(C)

Every ESS disconnect must be permanently marked "ENERGY STORAGE SYSTEM DISCONNECT" plus voltage, fault current, arc-flash label, and calculation date — except the last three don't apply to one- and two-family dwellings.

Q9 NEC 706.15(C)

An ESS is installed in a one-family dwelling. Per 706.15(C), which marking is still required on the disconnecting means?

  1. A The arc-flash label per NFPA 70E
  2. B The date the fault current calculation was performed
  3. C The permanent "ENERGY STORAGE SYSTEM DISCONNECT" marking with open/closed indication
  4. D The available fault current derived from the ESS
Show answer & explanation

Correct: C — The permanent "ENERGY STORAGE SYSTEM DISCONNECT" marking with open/closed indication

706.15(C) exempts one- and two-family dwellings from list items (2), (3), and (4) — fault current, the arc-flash label, and the calculation date. The permanent "ENERGY STORAGE SYSTEM DISCONNECT" marking and the open/closed position indication are not part of that exempted list, so they still apply to dwellings.

Diversion charge controllers and diversion load circuit requirements

NEC 706.33(B)(2)

A diversion charge controller needs a backup overcharge safeguard, and its diversion load and circuit must be sized well above the controller's and source's ratings.

Q10 NEC 706.33(B)(2)

A circuit has a diversion charge controller and diversion load. Per 706.33(B)(2), how must the diversion load's power rating compare to the charging source's power rating?

  1. A Equal to the charging source's power rating
  2. B At least 150 percent of the charging source's power rating
  3. C At least 125 percent of the charging source's power rating
  4. D No more than 100 percent of the charging source's power rating
Show answer & explanation

Correct: B — At least 150 percent of the charging source's power rating

706.33(B)(2)(1) requires the diversion load's power rating to be at least 150 percent of the charging source's power rating. The 125 percent figure is a common continuous-load multiplier from elsewhere in the Code but isn't what this section specifies, and equal-to or capped-at-100-percent sizing would leave no margin.

Required ESS nameplate markings

NEC 706.4

Every energy storage system needs a visible nameplate listing the maker, ratings, fault current, and max voltage/current — eight items, no exceptions.

Q11 NEC 706.4

An inspector reviewing an ESS nameplate finds the manufacturer name, rated frequency, and kVA rating, but no fault current value. Per 706.4, is this nameplate complete?

  1. A Yes, fault current is optional if maximum output current is listed instead
  2. B No, available fault current derived by the ESS at the output terminals is a required marking
  3. C Yes, fault current is only required for utility-interactive systems
  4. D No, but only because the phase count is also missing
Show answer & explanation

Correct: B — No, available fault current derived by the ESS at the output terminals is a required marking

706.4(5) requires the available fault current derived by the ESS at the output terminals on every ESS nameplate — it's not conditional on utility-interactive status, and it isn't satisfied by listing maximum current instead, since 706.4(6) requires that separately.

Flywheel energy storage system (FESS) safety requirements

NEC 706.51

FESS store energy in a spinning mass, so the Code bars them from one- and two-family dwellings and requires bearing monitoring plus containment for catastrophic failure.

Q12 NEC 706.51

A contractor wants to install a flywheel energy storage system (FESS) in a new two-family dwelling to back up the panel. Per the NEC, is this permitted?

  1. A No, FESS shall not be used for one- or two-family dwelling units
  2. B No, but only because two-family dwellings exceed the FESS power rating limit
  3. C Yes, but only if the containment means is rated for residential occupancies
  4. D Yes, as long as the FESS is listed and bearing monitoring is provided
Show answer & explanation

Correct: A — No, FESS shall not be used for one- or two-family dwelling units

706.51(1) flatly prohibits FESS in one- or two-family dwelling units regardless of listing, bearing monitoring, or containment features — those are separate requirements under 706.51(2) and (3) for installations where FESS is otherwise permitted. There is no power-rating exception in this section.

Segmenting Series-Connected Battery Strings Over 240V DC

NEC 706.15(E)(2)

Battery strings over 240V dc must have disconnects that break the string into segments of 240V dc or less for safe maintenance.

Q13 NEC 706.15(E)(2)

A battery energy storage system has series-connected strings totaling 480 volts dc nominal. Per 706.15(E)(2), what must be provided?

  1. A A ground-fault protective device sized for 480 volts dc
  2. B Provisions to segment the string into sections not exceeding 240 volts dc nominal
  3. C No additional disconnecting means, since the system is fully enclosed
  4. D A single load-break disconnect rated for the full 480 volts dc
Show answer & explanation

Correct: B — Provisions to segment the string into sections not exceeding 240 volts dc nominal

706.15(E)(2) requires strings exceeding 240 volts dc nominal to have provisions to disconnect them into segments not exceeding 240 volts dc nominal for maintenance by qualified persons. A single full-voltage disconnect doesn't achieve the segmenting the rule requires, and the section addresses disconnection, not ground-fault protection or exemption by enclosure.

Sizing ESS output and neutral conductor ampacity

NEC 706.30(B)

Size ESS output conductors to the greater of the nameplate-rated current or the OCPD rating, and on a shared neutral, add the ESS output to the unbalanced load.

Q14 NEC 706.30(B)

Under 706.30(B), the ampacity of an ESS's output circuit conductors must be at least equal to which of the following?

  1. A 125% of the nameplate-rated circuit current
  2. B The nameplate-rated circuit current only, regardless of the overcurrent device rating
  3. C The greater of the nameplate-rated circuit current or the ESS overcurrent protective device rating
  4. D The average of the nameplate rating and the overcurrent device rating
Show answer & explanation

Correct: C — The greater of the nameplate-rated circuit current or the ESS overcurrent protective device rating

706.30(B) requires output conductor ampacity to be at least the greater of the nameplate-rated circuit current (per 706.30(A)(1)) or the ESS overcurrent protective device rating. Using the nameplate current alone ignores a higher OCPD rating, averaging the two values isn't the rule, and the flat 125% multiplier isn't part of 706.30(B) — that's a continuous-load framing from elsewhere, not this rule.

ESS voltage limits in dwelling units

NEC 706.20(B)

A dwelling ESS is capped at 100V dc unless live parts stay inaccessible during maintenance, which raises the cap to 600V dc.

Q15 NEC 706.20(B)

Under 706.20(B), what is the maximum dc voltage permitted for an ESS in a one- and two-family dwelling unit if live parts are accessible during routine maintenance?

  1. A 100 volts dc
  2. B 1000 volts dc
  3. C 50 volts dc
  4. D 600 volts dc
Show answer & explanation

Correct: A — 100 volts dc

706.20(B) sets the default dwelling-unit ESS limit at 100 volts dc between conductors or to ground. The 600 volts dc option only applies when live parts are NOT accessible during routine maintenance, so it doesn't apply here. 50 volts dc and 1000 volts dc are not thresholds established by this section.

Loomi · NEC exam prep

2,035 questions free on the web. 12,934 in the app.

Loomi's full journeyman bank is timed, NEC-referenced, and runs on spaced repetition that hammers what you miss. Try everything free for 3 days.

Get launch access