Free NEC practice test · Chapter 5

Special Occupancies practice questions (Articles 518–590)

A free practice test over NEC Chapter 5 — special occupancies — for the journeyman exam: 49 questions across 7 articles, each with the answer and the why behind it.

49 questions · free · answers included NEC 2023 · Updated

How to use this practice test

These 49 journeyman-exam practice questions cover NEC Chapter 5 · Articles 518–590 across 49 code concepts, every one with the correct answer and a plain-English explanation of the rule behind it. They come from the same question bank the Loomi app trains you on — this is the free web sample, not a separate watered-down set.

Work straight down the sheet and answer before you peek: each question hides its answer behind Show answer & explanation. Questions tagged Code lookup are speed drills — race your codebook to the cited section. Printing this page gives you a clean paper worksheet with the answers left off.

Neutral conductor loading for solid-state dimmer feeders

NEC 518.5(C)

On 3-phase, 4-wire dimmer feeders, phase-control dimming makes the neutral a current-carrying conductor for ampacity adjustment; sine-wave dimming does not — and mixing the two types makes it current-carrying.

Q1 NEC 518.5(C) Code lookup

A theater is installing a 3-phase, 4-wire feeder to supply a solid-state phase-control dimmer bank. When sizing the feeder and applying ampacity adjustment factors for conductors in a raceway, which section tells you whether the neutral must be counted as a current-carrying conductor?

  1. A 518.4(A)
  2. B 518.5(A)(1)
  3. C 518.5(C)
  4. D 518.5(B)
Show answer & explanation

Correct: C — 518.5(C)

518.5(C) specifically addresses whether the neutral of a feeder supplying solid-state dimmer systems counts as current-carrying for ampacity adjustment, distinguishing phase-control from sine-wave dimming systems. 518.5(A)(1) instead covers overcurrent protection for power outlets/appliance centers, not neutral loading, and 518.4(A) covers general wiring methods, not conductor counting.

Classifying spaces as assembly occupancy

NEC 518.2

A space counts as assembly occupancy under Article 518 only when 100 or more people gather there for a common purpose, not just because it matches the examples list.

Q2 NEC 518.2

A 60-person multipurpose room is located inside a school building and is used incidentally for staff meetings. How should this room be classified?

  1. A As a mixed occupancy requiring compliance with both the school's rules and Article 518
  2. B As part of the school's other occupancy, since it holds fewer than 100 persons and is incidental to the main use
  3. C As an assembly occupancy only if the room has a dedicated exit
  4. D As an assembly occupancy under Article 518, because multipurpose rooms are listed in 518.2(A)
Show answer & explanation

Correct: B — As part of the school's other occupancy, since it holds fewer than 100 persons and is incidental to the main use

Per 518.2(B), occupancy of a room for assembly purposes by less than 100 persons, incidental to the building's other occupancy, is classified as part of that other occupancy. Being listed in 518.2(A) doesn't override the occupant-load test in 518.2(B).

Supplying portable switchboards and appliance outlet centers

NEC 518.5(A)

Power outlets and appliance outlet centers must have overcurrent protection, be locked away from the public, provide equipment grounding connections, carry a shock-hazard marking, and portable switchboards may only be fed from listed outlets rated for the load.

Q3 NEC 518.5(A)

Per 518.5(B), a portable switchboard used at a trade show may be supplied from which of the following?

  1. A A listed power outlet with sufficient voltage and ampere rating for the load
  2. B Any receptacle rated for the connected equipment's plug configuration
  3. C Any 120/208V panelboard with spare breaker space
  4. D A temporary feeder tapped ahead of the service disconnect
Show answer & explanation

Correct: A — A listed power outlet with sufficient voltage and ampere rating for the load

518.5(B) requires portable switchboards and portable power distribution equipment to be supplied only from listed power outlets or listed commercial appliance outlet centers with sufficient voltage and ampere ratings — not just any panelboard, feeder tap, or compatible receptacle.

Temporary wiring for trade shows and exhibition halls

NEC 518.3

Booth wiring follows Article 590's temporary-wiring rules, but 590.6's GFCI exemption is revoked — every other GFCI requirement in the Code still applies.

Q4 NEC 518.3

An electrician is wiring temporary power for booths at a trade show under 518.3. Which statement about GFCI protection is correct?

  1. A 590.6's GFCI requirements do not apply, but all other GFCI requirements of the Code still apply
  2. B GFCI protection is optional unless the exhibit hall authority having jurisdiction requires it
  3. C None of the Code's GFCI requirements apply because this is temporary wiring under Article 590
  4. D Only 590.6's GFCI requirements apply, and all other GFCI rules are waived for the exhibit hall
Show answer & explanation

Correct: A — 590.6's GFCI requirements do not apply, but all other GFCI requirements of the Code still apply

518.3 specifically exempts exhibition hall temporary wiring from 590.6's GFCI requirements, but is explicit that all other GFCI requirements of the Code still apply. The idea that all GFCI rules are waived, or that only 590.6 applies, both invert this — 590.6 is the one exemption, not the surviving rule, and GFCI protection isn't optional under 518.3.

Permitted wiring methods in assembly occupancies

NEC 518.4(A)

In assembly occupancies, power wiring must be metal raceway, flex metal raceway, concrete-encased nonmetallic raceway, or MI/MC/AC cable — always with an equipment grounding conductor.

Q5 NEC 518.4(A)

In an assembly occupancy, under what condition is nonmetallic raceway permitted as a general wiring method per 518.4(A)?

  1. A When it contains an insulated equipment grounding conductor only
  2. B When installed above a suspended ceiling
  3. C When the occupant load is under 100 persons
  4. D When encased in not less than 2 in. of concrete
Show answer & explanation

Correct: D — When encased in not less than 2 in. of concrete

518.4(A)(3) permits nonmetallic raceway only when encased in not less than 50 mm (2 in.) of concrete. Occupant load thresholds and ceiling location aren't the qualifying condition, and having an EGC alone doesn't exempt nonmetallic raceway from the concrete-encasement requirement — that requirement applies regardless of EGC type.

Overcurrent protection for control circuit power sources

NEC 522.10(A)(2)

Non-transformer control power sources are capped at 167% overcurrent protection for power-limited circuits and 125% for non-power-limited circuits; transformers instead follow Article 450.

Q6 NEC 522.10(A)(2)

A non-transformer power source supplies a power-limited control circuit. What is the maximum permitted rating for its overcurrent device, expressed as a percentage of VA rating divided by rated voltage?

  1. A 200 percent
  2. B 167 percent
  3. C 125 percent
  4. D 150 percent
Show answer & explanation

Correct: B — 167 percent

522.10(A)(2) caps overcurrent protection for non-transformer power-limited control power sources at 167% of the volt-ampere rating divided by rated voltage. The 125 percent figure is the cap for non-power-limited sources under 522.10(B)(2), not power-limited ones.

Sharing cable/raceway space with other control and power circuits

NEC 522.24

Control circuits can share a cable or raceway with other control circuits if all conductors share the same voltage insulation rating, and with power circuits only when the equipment is functionally associated, in a control center, or in a manhole with approved separation.

Q7 NEC 522.24

A control circuit and a power circuit run together in the same raceway. Under 522.24(B)(1), what condition permits this?

  1. A The conductors are installed underground in a manhole
  2. B All conductors are insulated for the maximum voltage in the raceway
  3. C The equipment powered is functionally associated with the control circuit
  4. D The raceway is part of a field-assembled control center
Show answer & explanation

Correct: C — The equipment powered is functionally associated with the control circuit

522.24(B)(1) allows control and power circuits to share a cable, enclosure, or raceway only where the powered equipment is functionally associated with the control circuit. The common-voltage-insulation rule applies to two control circuits together under 522.24(A), not to control-with-power mixing.

Power-limited vs. non-power-limited control circuit ratings

NEC 522.10(A)

Power-limited control circuits are capped at 30 volts and 1000 volt-amperes; non-power-limited control circuits can go up to 300 volts with no VA cap.

Q8 NEC 522.10(A)

Under 522.10(A), a power-limited control circuit must be supplied from a source rated at not more than which values?

  1. A 30 volts and 1000 volt-amperes
  2. B 300 volts and 1000 volt-amperes
  3. C 30 volts with no volt-ampere restriction
  4. D 50 volts and 1000 volt-amperes
Show answer & explanation

Correct: A — 30 volts and 1000 volt-amperes

522.10(A) sets both limits together: not more than 30 volts and 1000 volt-amperes. A source at 50 volts, or one with no VA cap, or one rated at the 300-volt non-power-limited threshold does not meet the power-limited definition.

Control circuit voltage limits for amusement attractions

NEC 522.5

Control circuits for amusement rides and attractions are capped at 150 volts nominal ac to ground or 300 volts dc to ground.

Q9 NEC 522.5 Code lookup

A control transformer for a portable amusement ride's control circuit is being installed. The secondary is designed to supply 277 volts AC to ground for the control circuit. Which section establishes whether this design is permitted?

  1. A 522.28
  2. B 522.10(A)(1)
  3. C 522.5
  4. D 522.25
Show answer & explanation

Correct: C — 522.5

522.5 caps control voltage at 150 volts nominal AC (or 300 volts DC) to ground, so a 277-volt AC control secondary fails this limit regardless of transformer construction. 522.10(A)(1) covers control transformer construction/listing requirements, not the voltage ceiling itself.

Ampacity and overcurrent protection for small control conductors

NEC 522.22

Control conductors 30 AWG through 16 AWG get their ampacity and OCP from Table 522.22, not Table 310.16 — 16 AWG is the crossover point.

Q10 NEC 522.22

A 20 AWG control conductor is installed on an amusement attraction. Which table determines its ampacity?

  1. A Table 310.15(B)(1)
  2. B Table 522.22
  3. C No ampacity table applies below 18 AWG
  4. D Table 310.16
Show answer & explanation

Correct: B — Table 522.22

Per 522.22, conductors 16 AWG and smaller use Table 522.22 for ampacity. A 20 AWG conductor falls in that range, so Table 522.22 applies, not the general conductor table (310.16) used for larger sizes per 522.23.

Flexible cord/cable type, sizing, and splice rules for amusement wiring

NEC 525.20(A)

Flexible cords/cables on amusement rides must be extra-hard usage (or hard usage only if protected from damage), wet-rated if outdoors, run continuous without splices, and single-conductor cable must be 2 AWG or larger.

Q11 NEC 525.20(A)

A flexible cable is being installed as permanent wiring on a portable amusement ride, in a location where it is not subject to physical damage. What listing is acceptable?

  1. A Extra-hard usage, or hard usage since it's not subject to physical damage
  2. B Extra-hard usage only, with no exception for hard usage
  3. C Any flexible cord regardless of usage listing
  4. D Hard usage only
Show answer & explanation

Correct: A — Extra-hard usage, or hard usage since it's not subject to physical damage

Per 525.20(A), flexible cords/cables must be listed for extra-hard usage, but where they are not subject to physical damage, hard usage is also permitted. Hard usage alone (without the physical-damage condition) and 'any cord' are not correct, and the extra-hard-usage-only choice ignores the explicit hard-usage allowance in the rule.

Where GFCI protection is required for amusement attraction receptacles/equipment

NEC 525.23(A)

Any 125-volt, 15- or 20-amp, single-phase receptacle or equipment connection near carnival rides that the public can reach or that gets plugged/unplugged for setup needs GFCI protection.

Q12 NEC 525.23(A)

At a traveling carnival, a 125-volt, 20-ampere non-locking receptacle is used each night to disconnect a ride for transport and reconnect it at the next site. Per 525.23(A), what protection is required?

  1. A AFCI protection for personnel
  2. B No additional protection beyond standard overcurrent devices
  3. C GFCI protection only if the receptacle is outdoors
  4. D GFCI protection for personnel
Show answer & explanation

Correct: D — GFCI protection for personnel

525.23(A)(1) requires GFCI protection for all 125-volt, single-phase, 15- and 20-ampere non-locking receptacles used for disassembly and reassembly, regardless of indoor/outdoor location. AFCI is not the protection type this section addresses, and skipping protection ignores the rule entirely.

Protecting exposed cords and connectors from public contact and damage

NEC 525.20(G)

Cords and connectors that the public can reach must be guarded, kept off traffic paths, and covered or buried to kill the tripping hazard.

Q13 NEC 525.20(G)

A flexible cord crossing a public walkway at a fairground is covered with nonconductive matting secured to the walkway surface. What additional condition must this matting satisfy under 525.20(G)?

  1. A It must be rated for the full ampacity of the cord it covers
  2. B It must not create a greater tripping hazard than the uncovered cable
  3. C It must be buried to a minimum depth per 300.5
  4. D It must be inspected daily by the ride operator
Show answer & explanation

Correct: B — It must not create a greater tripping hazard than the uncovered cable

525.20(G) requires that matting or any other cable protection method not constitute a greater tripping hazard than the uncovered cables. It has no ampacity rating requirement, and 300.5 burial depths are explicitly stated not to apply.

GFCI exceptions (not required, not permitted) and listing rules for cord-supplied receptacles

NEC 525.23(B)

Locking, above-grade equipment-disconnect receptacles skip GFCI protection, egress lighting can never have it, and any GFCI receptacle feeding a cord-connected branch circuit must be listed for portable use.

Q14 NEC 525.23(B)

An inspector finds egress lighting for a portable stage protected by a GFCI breaker. Per 525.23(C), what is the issue?

  1. A Egress lighting only needs GFCI protection when cord-and-plug connected
  2. B Egress lighting must never be GFCI protected
  3. C Egress lighting only needs GFCI protection if grade-accessible
  4. D Egress lighting must always be GFCI protected
Show answer & explanation

Correct: B — Egress lighting must never be GFCI protected

525.23(C) states GFCI protection is not permitted for egress lighting, since a nuisance trip could leave an evacuation path dark. The other options invert or conditionally apply a requirement that the code flatly prohibits.

Busbar sizing, terminal connections, and receptacle overcurrent protection in distribution boxes

NEC 525.22(B)

Busbars must be rated at least as high as the feeder overcurrent device, and every receptacle in the box needs its own overcurrent protection sized to the receptacle rating.

Q15 NEC 525.22(B)

In a distribution box, a receptacle rated 20 A is installed. Under what circumstance may its overcurrent protection be rated higher than 20 A?

  1. A When single-pole connectors are used instead of a standard receptacle
  2. B When the receptacle is used only for temporary lighting
  3. C When the feeder overcurrent device is rated higher than 20 A
  4. D When the receptacle supplies a motor load permitted under Article 430
Show answer & explanation

Correct: D — When the receptacle supplies a motor load permitted under Article 430

525.22(C) caps receptacle overcurrent protection at the receptacle's ampere rating, with the sole exception being motor loads permitted under Article 430. The feeder device rating, temporary lighting use, and single-pole connector use don't create an exception to this cap.

Disconnect switch location, access, and lockability for portable rides

NEC 525.21(A)

Every portable ride needs a disconnect within sight and within 6 ft of the operator's station, readily accessible even while running, and lockable if unqualified persons can reach it.

Q16 NEC 525.21(A)

Per 525.21(A), where must the disconnecting means for a portable ride be located relative to the operator's station?

  1. A Within 15 m (50 ft) of the ride, regardless of sightline
  2. B Within sight of and within 1.8 m (6 ft) of the operator's station
  3. C Within sight of the ride's main power distribution point
  4. D Anywhere on the ride structure as long as it is marked
Show answer & explanation

Correct: B — Within sight of and within 1.8 m (6 ft) of the operator's station

525.21(A) requires the disconnecting means to be located within sight of and within 1.8 m (6 ft) of the operator's station — both conditions apply together. A distance-only rule like 15 m (50 ft), a location tied to the distribution point instead of the operator, or an unspecified marked location all miss the specific sight-and-distance requirement.

Bonding metal equipment and structures at carnivals/fairs

NEC 525.30

Every metal raceway, enclosure, and portable structure frame on a carnival circuit must be bonded together, and the supply circuit's equipment grounding conductor can do that job.

Q17 NEC 525.30 Code lookup

At a traveling carnival, several ride trailers share the same power source. Their metal frames, along with the metal enclosures of the electrical equipment they support, are being connected together electrically. Which section covers this bonding requirement?

  1. A 525.31
  2. B 525.30
  3. C 525.11
  4. D 525.32
Show answer & explanation

Correct: B — 525.30

525.30 requires metal raceways, equipment enclosures, and metal frames of portable structures/trailers/trucks connected to the same source to be bonded together. 525.31 addresses grounding (connection to the grounding electrode/EGC system) rather than bonding equipment together, and 525.32 covers continuity assurance testing of the EGC, not the bonding requirement itself.

Connecting the equipment grounding conductor to system ground

NEC 525.31

The equipment grounding conductor bonds to the grounded conductor only at the service disconnect, or at the generator/first disconnect for a separately derived source.

Q18 NEC 525.31 Code lookup

A traveling carnival's generator supplies power to the midway. The equipment grounding conductor must be connected to the system grounded conductor at the generator or the first disconnecting means it feeds. Which section specifies this requirement?

  1. A 525.32
  2. B 525.11
  3. C 525.30
  4. D 525.31
Show answer & explanation

Correct: D — 525.31

525.31 specifically addresses connecting the equipment grounding conductor to the grounded conductor at the service disconnect or, for a separately derived system like a generator, at the generator or first disconnecting means. 525.30 covers bonding of equipment, not this grounded/grounding conductor connection point, and 525.32 addresses continuity assurance testing, not where the connection is made.

Mechanical protection for equipment on portable structures

NEC 525.6

Any electrical equipment or wiring method on a portable structure must be mechanically protected wherever it's exposed to physical damage.

Q19 NEC 525.6 Code lookup

A traveling carnival ride has its control panel and flexible cords mounted low on the ride's portable structure, in a spot where patrons and ride crew walking past could bump or strike them. Which section requires this equipment and wiring to be given mechanical protection?

  1. A 525.10(A)
  2. B 525.6
  3. C 525.20(H)
  4. D 525.20(G)
Show answer & explanation

Correct: B — 525.6

525.6 is the general rule requiring mechanical protection for electrical equipment and wiring methods on portable structures wherever they're subject to physical damage. 525.10(A) only addresses guarding of services, and 525.20(H) covers boxes and fittings for wiring methods, not this general physical-damage protection requirement.

Keeping Portable Structures Clear of Overhead Lines by Voltage

NEC 525.5(B)(1)

Portable structures (rides, ticket booths, stages) must stay 15 ft clear of overhead conductors in any direction — that rule applies whether the line is 600V or under, or over 600V.

Q20 NEC 525.5(B)(1)

A portable stage at a fair sits near overhead conductors operating at 480 volts. What clearance must be maintained, and is there any exception?

  1. A 15 ft in any direction, with no exceptions permitted
  2. B 10 ft in any direction, except for conductors supplying the portable structure
  3. C 15 ft horizontally only, with no vertical component
  4. D 15 ft in any direction, except for conductors supplying the portable structure
Show answer & explanation

Correct: D — 15 ft in any direction, except for conductors supplying the portable structure

Per 525.5(B)(1), portable structures must stay 15 ft (4.5 m) from overhead conductors at 600 volts or less in any direction, except conductors that supply the structure itself. The no-exceptions and horizontal-only options describe the over-600-volt rule in 525.5(B)(2), not this one, and 10 ft is not the code distance.

Protecting Motor-Generators and Transformers from Nitrate Film

NEC 540.11(A)

With nitrate film present, motor-generators, transformers, and similar control equipment must be in a separate room, or in the projection room only if arcs and sparks are kept away from film and the commutator end meets one of six enclosure options.

Q21 NEC 540.11(A)

A theater uses nitrate film. Per 540.11(A), where must the motor-generator sets supplying the projection equipment be located?

  1. A In a separate room from the projection room
  2. B In the projection booth doorway for quick access
  3. C Anywhere in the projection room, provided the equipment is grounded
  4. D In the same enclosure as the projector lamp housing
Show answer & explanation

Correct: A — In a separate room from the projection room

540.11(A) requires motor-generator sets, transformers, rectifiers, rheostats, and similar equipment to be located in a separate room where nitrate film is used. Simply grounding the equipment or placing it in the projection room without meeting the arc/spark and commutator-end conditions does not satisfy the rule.

Working Space Around Projection Equipment

NEC 540.12

Motion picture projectors, floodlights, and spotlights each need 750 mm (30 in.) of clear working space on each side and at the rear.

Q22 NEC 540.12

Per 540.12, what is the minimum clear working space required on each side and at the rear of a motion picture projector?

  1. A 900 mm (36 in.)
  2. B 600 mm (24 in.)
  3. C 750 mm (30 in.)
  4. D 1.0 m (39 in.)
Show answer & explanation

Correct: C — 750 mm (30 in.)

540.12 requires clear working space not less than 750 mm (30 in.) wide on each side and at the rear of the equipment. The other dimensions are clearances used elsewhere in the NEC (like general equipment working space in Article 110), not the value specified for projection equipment.

Projection Room Construction and Openings

NEC 540.10

Every professional projector needs a permanent, approved projection room, and every port opening in it must be closed with glass or similar approved material.

Q23 NEC 540.10

Under 540.10, what type of construction is required for a room housing a professional-type motion picture projector?

  1. A Any enclosed room, provided it is ventilated
  2. B Fire-rated construction classified as a hazardous location per Article 500
  3. C Temporary construction approved by the authority having jurisdiction for the event
  4. D Permanent construction approved for the type of building it's located in
Show answer & explanation

Correct: D — Permanent construction approved for the type of building it's located in

540.10 requires every projection room to be of permanent construction and approved for the type of building in which it is located. It also specifically states such rooms are not classified as hazardous locations under Article 500, so the fire-rated/hazardous-classification option is a plausible-sounding but incorrect distractor.

What Equipment Is Allowed in a Projection Room

NEC 540.11(B)

Projection rooms may only hold electrical equipment tied to projection, sound, lighting effects, or screen/curtain control — nothing else.

Q24 NEC 540.11(B)

Per 540.11(B), which of the following is generally NOT permitted to be installed in a projection room?

  1. A Overcurrent devices for the sound reproduction equipment
  2. B Equipment used for projector operation
  3. C Switches for controlling special-effect lamps
  4. D A general-purpose receptacle circuit unrelated to projection or sound equipment
Show answer & explanation

Correct: D — A general-purpose receptacle circuit unrelated to projection or sound equipment

540.11(B) prohibits switches, overcurrent devices, or other equipment not normally required or used for projectors, sound reproduction, or special-effect lamps. Equipment tied to projector operation, sound reproduction, or special-effect lamps is exactly what the section permits.

Bonding, grounding, and grounding electrode conductor provisions

NEC 545.11

Manufactured building panels must have bonding/grounding built in for exposed metal per Article 250, plus a clear route from the supply to the grounding electrode.

Q25 NEC 545.11

Under 545.11, prewired panels and building components in a manufactured building must provide for bonding (or bonding and grounding) of which metals?

  1. A Only metal located within 6 ft of a receptacle outlet
  2. B All exposed metals likely to become energized
  3. C Only metals that are part of the service equipment
  4. D Only metal parts exposed to weather
Show answer & explanation

Correct: B — All exposed metals likely to become energized

545.11 requires bonding/grounding provisions for all exposed metals likely to become energized, not a narrower subset limited to service equipment, weather exposure, or proximity to a receptacle.

Routing and installing supply/service-entrance conductors

NEC 545.5

Manufactured buildings must have a provided route for service or feeder conductors, service-entrance conductors are normally installed after the building reaches the site, and exposed conductors and equipment must be protected from factory through final erection.

Q26 NEC 545.5

Under NEC 545.6, service-entrance conductors for a manufactured building may be installed BEFORE the building is erected at the site only if which condition is met?

  1. A The local AHJ grants a variance for factory installation
  2. B The point of attachment is known prior to manufacture
  3. C The conductors are installed in rigid metal conduit
  4. D The service equipment is rated 400 A or less
Show answer & explanation

Correct: B — The point of attachment is known prior to manufacture

545.6 allows pre-erection installation of service-entrance conductors only when the point of attachment is known prior to manufacture. There's no AHJ-variance exception, no conduit-type exception, and no ampacity threshold mentioned in this section.

Approved wiring methods and cable securing in manufactured buildings

NEC 545.4(A)

Any Code-recognized raceway or cable method is allowed in manufactured buildings with listed fittings, and in closed construction, 10 AWG or smaller cables need securing only at boxes and fittings if protected from damage.

Q27 NEC 545.4(A)

In closed construction of a manufactured building, a cable with 10 AWG conductors is installed with adequate protection against physical damage. Where must this cable be secured, per 545.4(B)?

  1. A Nowhere, since closed construction exempts all securing requirements
  2. B At intervals not exceeding those required for exposed cable runs
  3. C At every framing member the cable passes through
  4. D Only at cabinets, boxes, or fittings
Show answer & explanation

Correct: D — Only at cabinets, boxes, or fittings

545.4(B) allows cable in closed construction to be secured only at cabinets, boxes, or fittings when conductors are 10 AWG or smaller and physical protection is provided — it does not require securing at regular intervals, at every framing member, or eliminate securing entirely.

Disconnecting means and branch-circuit overcurrent protection for relocatable structures

NEC 545.24(A)

Each relocatable structure gets exactly one readily accessible disconnecting means plus its own panelboard protecting every branch circuit.

Q28 NEC 545.24(A)

Per 545.24(A), how many disconnecting means are permitted for a relocatable structure?

  1. A Two — one for lighting loads and one for power loads
  2. B Exactly one, in a readily accessible location
  3. C Up to six, applying the six-disconnect rule used for services
  4. D One per panelboard installed in the structure
Show answer & explanation

Correct: B — Exactly one, in a readily accessible location

545.24(A) calls for a single disconnecting means for each relocatable structure. The six-disconnect grouping rule is a service-equipment concept from a different article and doesn't apply here, and splitting the disconnect by load type or by panelboard count both add disconnects beyond the one this section allows.

Listed receptacles, switches, and interconnection fittings for on-site assembly

NEC 545.10

In manufactured buildings, integral-enclosure devices and concealed interconnection fittings are only permitted when tested, identified, and listed to applicable standards.

Q29 NEC 545.10

Under 545.10, what is required before a receptacle with an integral enclosure and mounting means can be installed in a manufactured building?

  1. A It must use the same enclosure type as field-installed devices
  2. B It must be tested, identified, and listed to applicable standards
  3. C It must be approved on-site by the authority having jurisdiction at final assembly only
  4. D It must be installed only in modules assembled after final site placement
Show answer & explanation

Correct: B — It must be tested, identified, and listed to applicable standards

545.10 permits a receptacle or switch with integral enclosure and mounting means where it is tested, identified, and listed to applicable standards. There's no separate requirement tying approval to a specific assembly stage, matching field enclosure types, or restricting installation to modules assembled after site placement.

Bonding exposed metal parts to the panelboard chassis

NEC 545.26

Every exposed metal part on a relocatable structure that could become energized must bond back to the panelboard's grounding terminal or enclosure, with an accessible bonding terminal on the chassis.

Q30 NEC 545.26 Code lookup

A manufactured home dealer is wiring the panelboard inside a mobile home. Several exposed metal parts near the panelboard (the range hood frame, metal cabinet trim) are not normally energized but could become energized under fault conditions. Which section requires these exposed non-current-carrying metal parts to be bonded to the panelboard's grounding terminal or enclosure?

  1. A 545.26
  2. B 545.11
  3. C 545.27
  4. D 545.24(B)
Show answer & explanation

Correct: A — 545.26

545.26 specifically requires exposed non-current-carrying metal parts likely to become energized to be bonded to the panelboard's grounding terminal or enclosure, with a bonding conductor run to an accessible chassis terminal. 545.27 instead covers intersystem bonding (grounding electrode bonding for communication/other systems), not chassis metal parts, so it doesn't apply here.

Grounding the feeder and shared grounding electrode tap

NEC 545.22(D)

Relocatable structure feeders ground per Article 250, and when structures are joined into one unit, the chassis bonding conductor can double as the grounding electrode tap conductor.

Q31 NEC 545.22(D)

Two relocatable structures are structurally connected to form a single unit. Under 545.22(D)(2), what grounding arrangement is permitted?

  1. A A common grounding electrode conductor and tap arrangement per 250.64(D)(1), using the 545.26 chassis bonding conductor as the tap conductor
  2. B A common grounding electrode conductor, but only if each structure also retains its own separate tap conductor
  3. C A fully independent grounding electrode system for each structure, bonded together only at the service equipment
  4. D Omission of a grounding electrode conductor entirely, relying on the feeder equipment grounding conductor alone
Show answer & explanation

Correct: A — A common grounding electrode conductor and tap arrangement per 250.64(D)(1), using the 545.26 chassis bonding conductor as the tap conductor

545.22(D)(2) permits a common grounding electrode conductor with a tap arrangement per 250.64(D)(1) when structures are structurally joined into one unit, and specifically allows the 545.26 chassis bonding conductor to serve as that tap conductor. Fully independent electrode systems, omitting the GEC, or requiring each structure to keep its own separate tap all defeat the purpose of the shared arrangement this section permits.

Site-isolating device requirements (location, rating, operation, marking)

NEC 547.41(A)

When one distribution point feeds two or more buildings on an agricultural site, a single pole-mounted site-isolating device must disconnect all ungrounded conductors at once, without needing overcurrent protection.

Q32 NEC 547.41(A)

How must a site-isolating device operate when it disconnects the service?

  1. A It must simultaneously disconnect all ungrounded service conductors
  2. B It must open each ungrounded conductor individually, in sequence
  3. C It must disconnect the grounded conductor first, then the ungrounded conductors
  4. D It only needs to disconnect the conductor with the highest calculated load
Show answer & explanation

Correct: A — It must simultaneously disconnect all ungrounded service conductors

547.41(A)(3) requires simultaneous disconnection of all ungrounded service conductors from the premises wiring — sequential or single-conductor switching would leave part of the system energized and doesn't satisfy the rule.

GFCI protection requirements and exceptions in agricultural buildings

NEC 547.28

Agricultural buildings follow the 210.8(B) GFCI rule, but the 125-volt, 15- and 20-amp receptacle requirement is waived in equipotential-plane areas, outdoors, damp/wet locations, and livestock dirt confinement areas.

Q33 NEC 547.28

In an agricultural building, GFCI protection for receptacles in areas not otherwise addressed by Article 547 is required per which section?

  1. A 210.8(B)
  2. B 215.9
  3. C 547.5
  4. D 210.8(A)
Show answer & explanation

Correct: A — 210.8(B)

547.28 directs agricultural buildings to follow 210.8(B) for GFCI protection in areas not otherwise covered by the article. 210.8(A) covers dwelling units, not this scope, and 547.5 and 215.9 address unrelated topics.

Enclosure protection against dust, moisture, and corrosion

NEC 547.22

In agricultural buildings, enclosures must be sealed against dust, weatherproof in wet locations, and corrosion-resistant where corrosive conditions exist.

Q34 NEC 547.22

A livestock barn has a wash-down area where walls and equipment are periodically hosed off with water. Per 547.23, what is required for boxes and conduit bodies installed there?

  1. A They must be dust-tight with no openings, per the dusty-area rule
  2. B They must be placed to prevent moisture accumulation only, with no listing requirement
  3. C They only need corrosion-resistant materials, since washing is not classified as wet
  4. D They must be listed for wet locations, with weatherproof equipment enclosures
Show answer & explanation

Correct: D — They must be listed for wet locations, with weatherproof equipment enclosures

547.23 classifies periodically washed or sprayed surfaces as wet locations, not just damp — this requires boxes and conduit bodies listed for wet locations and weatherproof equipment enclosures, a stricter standard than the general damp/wet 'prevent moisture from entering' rule that applies to merely damp areas.

Physical damage protection and rodent-resistant wiring

NEC 547.26

In agricultural buildings, nonmetallic cable can't be concealed in walls or ceilings of spaces adjoining livestock confinement areas because rodents will chew through it.

Q35 NEC 547.26 Code lookup

An electrician is running cable to a small office and lunchroom built onto the side of a livestock confinement barn, where the office walls are contiguous with the animal containment area. Which section governs whether nonmetallic cable can be concealed within those office walls?

  1. A 547.26
  2. B 547.23
  3. C 547.24
  4. D 547.20
Show answer & explanation

Correct: A — 547.26

547.26 specifically prohibits concealing nonmetallic cable in walls/ceilings of areas contiguous with livestock confinement areas due to rodent damage risk. 547.24 covers corrosive atmosphere protection and 547.23 covers damp/wet locations — neither addresses rodent-driven concealment restrictions; 547.20 sets general wiring method requirements but not this specific concealment ban.

Approved wiring methods for agricultural buildings

NEC 547.20

Agricultural buildings only allow a short list of wiring methods — Type UF, Type NMC, copper Type SE, jacketed Type MC, or raceways rated for the location.

Q36 NEC 547.20

Which of the following wiring methods is explicitly permitted for agricultural buildings under 547.20?

  1. A Type NMC cable
  2. B Type SE cable with aluminum conductors
  3. C Type NM cable
  4. D Unjacketed interlocked-armor Type MC cable
Show answer & explanation

Correct: A — Type NMC cable

547.20 lists Type NMC cable as a permitted wiring method. Type SE is permitted only in copper, not aluminum; Type MC must be jacketed to qualify; and ordinary Type NM (without corrosion resistance) is not on the list at all.

Service disconnect and conductors when located at the building/structure

NEC 547.41(B)

When the service disconnect and overcurrent protection sit at the building or structure instead of the distribution point, size conductors under Article 220 Part V, install them under Article 225 Part II, and bond per 250.32 with an unspoiled equipment grounding conductor.

Q37 NEC 547.41(B) Code lookup

A cattle barn is supplied by overhead conductors from a distribution point on the same premises, and the service disconnecting means and overcurrent protection for the barn are installed at the barn itself rather than at the distribution point. Which section specifies how to size the supply conductors feeding the barn under this arrangement?

  1. A 547.42
  2. B 547.41(B)(2)
  3. C 547.41(A)(5)
  4. D 547.41(B)(1)
Show answer & explanation

Correct: D — 547.41(B)(1)

547.41(B)(1) governs conductor sizing (per Article 220 Part V) when the disconnect and OCPD sit at the building rather than the distribution point; 547.41(A)(5) covers site-isolating device ratings and 547.42 covers the opposite arrangement where the disconnect stays at the distribution point, so neither addresses sizing supply conductors run to the building.

Bonding equipotential planes to the grounding system

NEC 547.44(B)

An equipotential plane must be bonded with solid copper conductor, 8 AWG or larger, to the grounding electrode system or an equipment grounding terminal.

Q38 NEC 547.44(B)

An equipotential plane in a livestock building must be bonded to the grounding electrode system or an equipment grounding terminal using a conductor that is at minimum which of the following?

  1. A 6 AWG aluminum
  2. B 10 AWG solid copper
  3. C 8 AWG solid copper
  4. D 8 AWG stranded copper
Show answer & explanation

Correct: C — 8 AWG solid copper

Per 547.44(B), the bonding conductor must be solid copper, insulated, covered, or bare, and not smaller than 8 AWG. The 10 AWG option is undersized, the stranded-copper option fails the solid-conductor requirement, and aluminum is not permitted for this bonding conductor.

Where equipotential planes are required (indoor/outdoor livestock areas)

NEC 547.44(A)

An equipotential plane is required wherever livestock (not poultry) can contact metallic equipment that might become energized, on concrete floors indoors or concrete slabs outdoors.

Q39 NEC 547.44(A)

Under 547.44(A), which scenario requires an equipotential plane?

  1. A A concrete floor in a poultry-only confinement building with energized metallic feeders
  2. B A dirt-floor pasture with an energized metal gate accessible to livestock
  3. C A concrete floor in a livestock confinement area with metallic equipment accessible to the animals that may become energized
  4. D A concrete slab in a livestock area with no metallic equipment present
Show answer & explanation

Correct: C — A concrete floor in a livestock confinement area with metallic equipment accessible to the animals that may become energized

547.44(A)(1) requires an equipotential plane indoors where there's a concrete floor in a confinement area and accessible metallic equipment that may become energized. The poultry-only building doesn't qualify because 547.44 excludes poultry from the definition of livestock. The dirt-floor pasture and the slab with no metallic equipment both lack a required element of the trigger.

Which agricultural buildings Article 547 covers

NEC 547.1

Article 547 only applies to the parts of ag buildings with excessive dust/dust-with-water or a corrosive atmosphere — not the whole farm.

Q40 NEC 547.1

Under 547.1, which part of a farm property does Article 547 apply to?

  1. A Only buildings or areas meeting the excessive dust or corrosive atmosphere conditions of 547.1(A) or (B)
  2. B Any building located on agricultural property, regardless of use
  3. C Only buildings that house livestock, regardless of dust or moisture conditions
  4. D Only detached outbuildings, not areas adjacent to the farmhouse
Show answer & explanation

Correct: A — Only buildings or areas meeting the excessive dust or corrosive atmosphere conditions of 547.1(A) or (B)

547.1 limits the article's scope to agricultural buildings, or parts/adjacent areas of similar nature, that meet the conditions specified in 547.1(A) or (B) — dust/dust-with-water or corrosive atmosphere. Simply being on agricultural property or housing livestock, without those conditions, isn't enough to bring a building under Article 547.

Securing and mounting cables/raceways in agricultural buildings

NEC 547.21

Secure all cables within 200 mm (8 in.) of every cabinet, box, or fitting, and nonmetallic wiring can mount flush to the surface without the usual 6 mm airspace.

Q41 NEC 547.21

In an agricultural building covered by Article 547, within what distance of a junction box must a cable be secured?

  1. A 200 mm (8 in.)
  2. B 450 mm (18 in.)
  3. C 300 mm (12 in.)
  4. D 150 mm (6 in.)
Show answer & explanation

Correct: A — 200 mm (8 in.)

547.21 requires cables to be secured within 200 mm (8 in.) of each cabinet, box, or fitting. The other distances are not the figure specified in this section.

Enclosure requirements for switches, receptacles, breakers, and motors

NEC 547.29

In agricultural buildings, every switch, receptacle, breaker, controller, and fuse must use a 547.22 dust-tight enclosure, and motors must be totally enclosed or equivalently protected.

Q42 NEC 547.29 Code lookup

A pushbutton station controlling a spray booth exhaust fan motor is being installed in a Class I spray finishing room. Which section specifies the enclosure requirements for this pushbutton station?

  1. A 547.22
  2. B 547.30
  3. C 547.28
  4. D 547.29
Show answer & explanation

Correct: D — 547.29

547.29 covers switches, pushbuttons, and similar control devices and points to 547.22's enclosure requirements. 547.30 governs enclosures for motors themselves (rotating machinery), and 547.28 addresses GFCI protection, not enclosure type, so neither applies to a pushbutton station.

GFCI vs. assured equipment grounding conductor program for other receptacles

NEC 590.6(B)

Temporary receptacles not covered by 590.6(A) must have GFCI protection or be part of a written, enforced assured equipment grounding conductor program.

Q43 NEC 590.6(B)

On a construction site, a receptacle not covered by 590.6(A) supplies power to a portable saw. Which is a code-compliant way to protect this receptacle under 590.6(B)?

  1. A GFCI protection for personnel
  2. B An unwritten, informal grounding check done by the site foreman
  3. C A double-insulated tool with no grounding conductor at all
  4. D A one-time continuity test performed at project completion
Show answer & explanation

Correct: A — GFCI protection for personnel

590.6(B) permits either GFCI protection per 590.6(B)(1) or a full assured equipment grounding conductor program per 590.6(B)(2). An informal or undocumented check doesn't satisfy 590.6(B)(2), which requires a written, continuously enforced program, and a one-time end-of-project test doesn't meet the recurring testing schedule required.

GFCI protection for temporary receptacle outlets

NEC 590.6(A)

Every 125-volt, 15/20/30-amp receptacle used for temporary power — cord set, permanent outlet, or generator — needs GFCI protection for personnel.

Q44 NEC 590.6(A)

A contractor is using a building's existing permanent 125-volt, 20-ampere receptacle to power tools during demolition work. Per 590.6(A)(2), what is required?

  1. A Ground-fault circuit-interrupter protection for personnel
  2. B AFCI protection instead of GFCI protection
  3. C An assured equipment grounding conductor program only
  4. D No additional protection, since the receptacle is already part of permanent wiring
Show answer & explanation

Correct: A — Ground-fault circuit-interrupter protection for personnel

Under 590.6(A)(2), permanent receptacle outlets used for temporary electric power still require GFCI protection for personnel — being part of permanent wiring does not exempt them. The assured equipment grounding conductor program is a separate, narrow alternative limited to specific industrial situations under 590.6(A), and AFCI protection is not the requirement this section addresses.

Physical protection, termination, and support of flexible cords and cables

NEC 590.4(H)

Temporary-wiring cords must be shielded from physical damage, clamped into boxes with listed fittings, and supported off the floor at intervals that keep them safe.

Q45 NEC 590.4(H)

A flexible cord enters a temporary lighting box containing a receptacle device to be terminated. How must the cord be secured to the box?

  1. A With electrical tape wrapped around the cord at the knockout
  2. B With a fitting listed for connecting flexible cords or cables to boxes
  3. C No securing is required if the box is mounted above head height
  4. D By tying a knot in the cord inside the box for strain relief
Show answer & explanation

Correct: B — With a fitting listed for connecting flexible cords or cables to boxes

590.4(I) requires a fitting listed for the purpose of connecting flexible cords/cables to boxes. Tape, knots, and mounting height are not substitutes for a listed fitting.

Grounding-type receptacles and wet-location protection in temp wiring

NEC 590.4(D)

Every temporary receptacle must be grounding-type with a real equipment grounding path, and 15/20 A, 125/250 V receptacles in wet locations need 406.9(B)(1) protection — and receptacles can never share a circuit with temporary lighting.

Q46 NEC 590.4(D)

On a construction site, a contractor wants to add job-site receptacles to the same branch circuit that feeds the temporary string lighting for the framing crew. Is this permitted under 590.4(D)(1)?

  1. A Yes, as long as the lighting and receptacles are on separate poles of a multiwire branch circuit
  2. B Yes, as long as the receptacles are GFCI protected
  3. C Yes, as long as the combined load stays under 20 amperes
  4. D No — receptacles shall not be installed on any branch circuit that supplies temporary lighting
Show answer & explanation

Correct: D — No — receptacles shall not be installed on any branch circuit that supplies temporary lighting

590.4(D)(1) states receptacles on construction sites shall not be installed on any branch circuit that supplies temporary lighting — this is a flat prohibition, not conditioned on GFCI protection, load level, or multiwire pole separation.

Branch circuit wiring methods and origination for temporary power

NEC 590.4(C)

Temporary branch circuits must originate from approved equipment and use hard-usage cable, cord, or (in limited cases) single insulated conductors.

Q47 NEC 590.4(C)

Per 590.4(C), a temporary branch circuit is being fed directly from a portable generator's cord without passing through any panelboard or switch enclosure. Is this compliant?

  1. A Yes, as long as the cord is listed for hard usage
  2. B Yes, because temporary installations are exempt from origination requirements
  3. C No — all branch circuits must originate in approved power outlets, switchgear, switchboards, panelboards, motor control centers, or fused switch enclosures
  4. D Yes, as long as the voltage to ground does not exceed 150 volts
Show answer & explanation

Correct: C — No — all branch circuits must originate in approved power outlets, switchgear, switchboards, panelboards, motor control centers, or fused switch enclosures

590.4(C) requires all branch circuits to originate in approved supply equipment such as a power outlet, switchgear, switchboard, panelboard, motor control center, or fused switch enclosure. Cord rating and the 150V-to-ground limit are separate requirements that apply to single insulated conductors under 590.3(B), not a substitute for proper origination.

Disconnecting means and lamp protection for temporary circuits

NEC 590.4(E)

Every temporary circuit needs a way to kill all ungrounded conductors at once, and every temporary lamp needs a guard to survive the job site.

Q48 NEC 590.4(E)

A temporary multiwire branch circuit is installed on a construction site. What does 590.4(E) require for its disconnecting means?

  1. A A disconnect only for the neutral conductor at the panelboard
  2. B A means to disconnect simultaneously all ungrounded conductors at the point of origin
  3. C A separate single-pole switch for each ungrounded conductor located anywhere along the circuit
  4. D No disconnecting means, since temporary circuits are exempt from this requirement
Show answer & explanation

Correct: B — A means to disconnect simultaneously all ungrounded conductors at the point of origin

590.4(E) requires multiwire branch circuits to have a means to disconnect all ungrounded conductors simultaneously at the power outlet or panelboard where the circuit originates. Separate single-pole switches without simultaneous operation don't meet this, disconnecting only the neutral is not what's required, and temporary circuits are not exempt.

Overcurrent protective device reuse inspection and service OCPD current-limiting rules

NEC 590.8

Reused OCPDs in temporary installations must be inspected for good condition, and solidly grounded wye services over 150 V to ground with high available fault current need current-limiting protection.

Q49 NEC 590.8

A temporary service is solidly grounded wye at 480Y/277 V, with an available fault current of 14,000 amperes. Per 590.8(B), what is required of the service overcurrent protective device?

  1. A No special requirement applies because the installation is temporary
  2. B It must have a minimum interrupting rating of 10,000 amperes
  3. C It must be current limiting only if the system exceeds 600 V phase-to-phase
  4. D It must be current limiting
Show answer & explanation

Correct: D — It must be current limiting

277 V to ground exceeds 150 V, the system is 480 V phase-to-phase (not over 1000 V), and available fault current exceeds 10,000 A, so 590.8(B) requires a current-limiting device. There's no 600 V phase-to-phase carve-out, and an interrupting rating figure is a different requirement than current limiting.

Loomi · NEC exam prep